Plan Review Details - Permit 14080042
Plan Review Stops For Permit 14080042
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-02-26 Cont ID  
Sent By jwitmer Date 2015-02-26 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2015-02-26 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-22 Cont ID  
Sent By jwitmer Date 2014-09-22 Time 16:51 Rev Time 0.00
Received By jwitmer Date 2014-09-22 Time 16:30 Sent To  
Notes
2014-09-22 16:51:42BUILDING PLAN REVIEW
 REVISION: 14080042
 PERMIT: 14021040
 ADD: 721 39TH ST.
 CONT: HERMAN EILBERG CONTRACTING
 TEL: (561)961-9971
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 22/ 2014
 ACTION: DENIED
  
 NOTE: THIS REVISION WAS SUBMITTED UNDER 14090653, IT IS
 A RESUB OF A REVISION # 14080042. THERE IS A CREDIT
 THAT CAN BE TAKEN ON THE NEXT CYCLE OF REVIEWS.
  
 1) THE REVISION IS FOR THE REMOVAL OF THE BLOCK WALL
 AND NEW WOOD FRAME EXTERIOR WALLS. THE REVISION STATES
 THERE IS NO INCREASE IN VALUE OF WORK. NOT IN THE SCOPE
 OF THE ORIGINAL PERMI, THIS IS A INCREASE IN THE SCOPE
 OF WORK AND INCREASED VALUE OF THE PROJECT. PLEASE
 PROVIDE THE VALUE IN THE INCREASE OF WORK!!!! 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE REVISION IS LACKING THE ELEMENTS REQUIRED FOR
 PLANS REVIEW. THE PLANS DO NOT PROVIDE WHAT THE ROOM IS
 TO BE USED FOR, IF SLEEPING ROOM THEN IT MUST SHOW
 COMPLIANCE WITH 2010 FBC-R 310.1.1.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
  
 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN;
 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY)
 REQUIREMENTS SHALL INCLUDE:
 WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING
 ASSEMBLY AND MATERIALS CONNECTOR
 BUILDING ENVELOPE WALL & OPENING PROTECTION WINDOWS
 INTERIOR FINISHES WALL & CEILING
 ROOFING ASSEMBLIES ROOFING IS A SEPARATE PERMIT.
  
 4) R612.5 PERFORMANCE.
 EXTERIOR WINDOWS AND DOORS SHALL BE DESIGNED TO RESIST
 THE DESIGN WIND LOADS SPECIFIED IN TABLE R301.2(2)
 ADJUSTED FOR HEIGHT AND EXPOSURE PER TABLE R301.2(3).
 FOR TESTING REQUIRED IN SECTIONS R612.6, R612.7, AND
 R612.8, DESIGN PRESSURES DETERMINED FROM TABLE
 R301.2(2) OR ASCE 7 ARE PERMITTED TO BE MULTIPLIED BY
 0.6.
  
 R612.6 TESTING AND LABELING.
 EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS:
  
 ANSI/AAMA/NWWDA101/I.S.2 OR ANSI/AAMA/WDMA
 101/I.S.2/NAFS OR AAMA/WDMA/CSA 101/I.S.2/A440 OR TAS
 202 (HVHZ SHALL COMPLY WITH TAS 202 UTILIZING ASTM E
 1300-98 OR ASTM E 1300-04 02).
  
 EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE
 LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING
 PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT.
 THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A
 PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL
 APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING
 THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER,
 POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT
 MAXIMUM SIZE, GLAZING THICKNESS, IMPACT RESISTANCE.
 APPROVAL NUMBER, APPLICABLE TEST STANDARD(S), AND
 APPROVED PRODUCT CERTIFICATION AGENCY, TESTING
 LABORATORY, EVALUATION ENTITY OR MIAMI-DADE PRODUCT
 APPROVAL.THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE
 RATING PER REFERENCE STANDARD. THE TEMPORARY
 SUPPLEMENTAL LABEL SHALL REMAIN ON THE WINDOW OR DOOR
 UNTIL FINAL APPROVAL BY THE BUILDING OFFICIAL.
  
 5) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) A ROOFING CONTRACTOR WILL BE REQUIRED FOR THE
 ROOFING PERMIT SINCE THIS IS FLAT WORK FL STATUE 489.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 12:42 Sent To  
Notes
2014-08-04 13:34:25BUILDING PLAN REVIEW
 REVISION: 14080042
 PERMIT: 14021040
 ADD: 721 39TH ST.
 CONT: HERMAN EILBERG CONTRACTING
 TEL: (561)961-9971
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 04/2014
 ACTION: DENIED
  
 1) THE REVISION IS FOR THE REMOVAL OF THE BLOCK WALL
 AND NEW WOOD FRAME EXTERIOR WALLS. THE REVISION STATES
 THERE IS NO INCREASE IN VALUE OF WORK? NOT IN THE SCOPE
 OF THE ORIGINAL PERMIT. 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE REVISION IS LACKING THE ELEMENTS REQUIRED FOR
 PLANS REVIEW. THE PLANS SHOW A NEW EXTERIOR FRAME WALL,
 MISSING THE SUB-SHEATHING ON THE EXTERIOR OF THE WALL
 AS WELL AS THE WALL FINISH.
 703.1.2 WIND RESISTANCE.
 WALL COVERINGS, BACKING MATERIALS AND THEIR ATTACHMENTS
 SHALL BE CAPABLE OF RESISTING WIND LOADS IN ACCORDANCE
 WITH TABLES R301.2(2) AND R301.2(3). WIND-PRESSURE
 RESISTANCE OF THE SIDING AND BACKING MATERIALS SHALL BE
 DETERMINED BY ASTM E 330 OR OTHER APPLICABLE STANDARD
 TEST METHODS. WHERE WIND-PRESSURE RESISTANCE IS
 DETERMINED BY DESIGN ANALYSIS, DATA FROM APPROVED
 DESIGN STANDARDS AND ANALYSIS CONFORMING TO GENERALLY
 ACCEPTED ENGINEERING PRACTICE SHALL BE USED TO EVALUATE
 THE SIDING AND BACKING MATERIAL AND ITS FASTENING. ALL
 APPLICABLE FAILURE MODES INCLUDING BENDING RUPTURE OF
 SIDING, FASTENER WITHDRAWAL AND FASTENER HEAD
 PULL-THROUGH SHALL BE CONSIDERED IN THE TESTING OR
 DESIGN ANALYSIS. WHERE THE WALL COVERING AND THE
 BACKING MATERIAL RESIST WIND LOAD AS AN ASSEMBLY, USE
 OF THE DESIGN CAPACITY OF THE ASSEMBLY SHALL BE
 PERMITTED.
  
 R703.1.3 LOAD RESISTANCE.
 ALL EXTERIOR WALLS, WALL COVERINGS AND SOFFITS SHALL BE
 CAPABLE OF RESISTING THE DESIGN PRESSURES SPECIFIED IN
 TABLE R301.2(2) FOR WALLS. MANUFACTURED SOFFITS SHALL
 BE LABELED IN ACCORDANCE WITH SECTION R616 OF THIS
 CODE.
  
 R703.2 WEATHER-RESISTANT SHEATHING PAPER.
 ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND
 BREAKS, COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT OR
 OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED
 OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. SUCH
 FELT OR MATERIAL SHALL BE APPLIED HORIZONTALLY, WITH
 THE UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS
 THAN 2 INCHES (51 MM). WHERE JOINTS OCCUR, FELT SHALL
 BE LAPPED NOT LESS THAN 6 INCHES (152 MM). THE FELT OR
 OTHER APPROVED MATERIAL SHALL BE CONTINUOUS TO THE TOP
 OF WALLS AND TERMINATED AT PENETRATIONS AND BUILDING
 APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE
 EXTERIOR WALL ENVELOPE AS DESCRIBED IN SECTION R703.1.
  
  
 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN;
 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY)
 REQUIREMENTS SHALL INCLUDE:
 WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING
 ASSEMBLY AND MATERIALS CONNECTOR
 BUILDING ENVELOPE WALL & OPENING PROTECTION WINDOWS
 INTERIOR FINISHES WALL & CEILING
 ROOFING ASSEMBLIES ROOFING IS A SEPARATE PERMIT.
  
 4) R612.5 PERFORMANCE.
 EXTERIOR WINDOWS AND DOORS SHALL BE DESIGNED TO RESIST
 THE DESIGN WIND LOADS SPECIFIED IN TABLE R301.2(2)
 ADJUSTED FOR HEIGHT AND EXPOSURE PER TABLE R301.2(3).
 FOR TESTING REQUIRED IN SECTIONS R612.6, R612.7, AND
 R612.8, DESIGN PRESSURES DETERMINED FROM TABLE
 R301.2(2) OR ASCE 7 ARE PERMITTED TO BE MULTIPLIED BY
 0.6.
  
 R612.6 TESTING AND LABELING.
 EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS:
  
 ANSI/AAMA/NWWDA101/I.S.2 OR ANSI/AAMA/WDMA
 101/I.S.2/NAFS OR AAMA/WDMA/CSA 101/I.S.2/A440 OR TAS
 202 (HVHZ SHALL COMPLY WITH TAS 202 UTILIZING ASTM E
 1300-98 OR ASTM E 1300-04 02).
  
 EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE
 LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING
 PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT.
 THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A
 PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL
 APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING
 THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER,
 POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT
 MAXIMUM SIZE, GLAZING THICKNESS, IMPACT RESISTANCE.
 APPROVAL NUMBER, APPLICABLE TEST STANDARD(S), AND
 APPROVED PRODUCT CERTIFICATION AGENCY, TESTING
 LABORATORY, EVALUATION ENTITY OR MIAMI-DADE PRODUCT
 APPROVAL.
  
 THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE RATING
 PER REFERENCE STANDARD. THE TEMPORARY SUPPLEMENTAL
 LABEL SHALL REMAIN ON THE WINDOW OR DOOR UNTIL FINAL
 APPROVAL BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-26 Cont ID  
Sent By dhayes Date 2015-02-26 Time 15:28 Rev Time 0.00
Received By dhayes Date 2015-02-26 Time 15:28 Sent To  
Notes
2015-02-26 15:35:54DATE: 2/27/2015
 PROJECT: 721 39TH ST FLORIDA RM
 PERMIT#: 14080042
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) SMOKE DETECTORS REQUIRED. WHEN ALTERATIONS, REPAIRS,
 OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR
 MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. SEE FBC-RESIDENTIAL 314.3 AND 314.3.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-05 Cont ID  
Sent By dhayes Date 2014-08-05 Time 15:41 Rev Time 0.00
Received By dhayes Date 2014-08-05 Time 15:37 Sent To  
Notes
2014-08-05 16:03:56DATE: 8/5/2014
 PROJECT: 721 39TH ST FLORIDA RM
 PERMIT#: 14080042
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SMOKE DETECTORS REQUIRED. WHEN ALTERATIONS, REPAIRS,
 OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR
 MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. SEE FBC-RESIDENTIAL 314.3 AND 314.3.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-26 Cont ID  
Sent By dhayes Date 2015-02-26 Time 15:28 Rev Time 0.00
Received By dhayes Date 2015-02-09 Time   Sent To  
Notes
2015-02-18 10:17:58SENT TO JW DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-22 Cont ID  
Sent By jwitmer Date 2014-09-22 Time 16:51 Rev Time 0.00
Received By jwitmer Date 2014-09-22 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-05 Cont ID  
Sent By dhayes Date 2014-08-05 Time 16:04 Rev Time 0.00
Received By dhayes Date 2014-08-01 Time 17:51 Sent To  
Notes
2014-08-01 17:52:37REVISION SENT TO JIM WITMER'S DESK FOR REVIEW. JG.