| 2014-08-04 13:34:25 | BUILDING PLAN REVIEW |
| | REVISION: 14080042 |
| | PERMIT: 14021040 |
| | ADD: 721 39TH ST. |
| | CONT: HERMAN EILBERG CONTRACTING |
| | TEL: (561)961-9971 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 04/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION IS FOR THE REMOVAL OF THE BLOCK WALL |
| | AND NEW WOOD FRAME EXTERIOR WALLS. THE REVISION STATES |
| | THERE IS NO INCREASE IN VALUE OF WORK? NOT IN THE SCOPE |
| | OF THE ORIGINAL PERMIT. 2010 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, W P B |
| | ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| | BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| | PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| | FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE REVISION IS LACKING THE ELEMENTS REQUIRED FOR |
| | PLANS REVIEW. THE PLANS SHOW A NEW EXTERIOR FRAME WALL, |
| | MISSING THE SUB-SHEATHING ON THE EXTERIOR OF THE WALL |
| | AS WELL AS THE WALL FINISH. |
| | 703.1.2 WIND RESISTANCE. |
| | WALL COVERINGS, BACKING MATERIALS AND THEIR ATTACHMENTS |
| | SHALL BE CAPABLE OF RESISTING WIND LOADS IN ACCORDANCE |
| | WITH TABLES R301.2(2) AND R301.2(3). WIND-PRESSURE |
| | RESISTANCE OF THE SIDING AND BACKING MATERIALS SHALL BE |
| | DETERMINED BY ASTM E 330 OR OTHER APPLICABLE STANDARD |
| | TEST METHODS. WHERE WIND-PRESSURE RESISTANCE IS |
| | DETERMINED BY DESIGN ANALYSIS, DATA FROM APPROVED |
| | DESIGN STANDARDS AND ANALYSIS CONFORMING TO GENERALLY |
| | ACCEPTED ENGINEERING PRACTICE SHALL BE USED TO EVALUATE |
| | THE SIDING AND BACKING MATERIAL AND ITS FASTENING. ALL |
| | APPLICABLE FAILURE MODES INCLUDING BENDING RUPTURE OF |
| | SIDING, FASTENER WITHDRAWAL AND FASTENER HEAD |
| | PULL-THROUGH SHALL BE CONSIDERED IN THE TESTING OR |
| | DESIGN ANALYSIS. WHERE THE WALL COVERING AND THE |
| | BACKING MATERIAL RESIST WIND LOAD AS AN ASSEMBLY, USE |
| | OF THE DESIGN CAPACITY OF THE ASSEMBLY SHALL BE |
| | PERMITTED. |
| | |
| | R703.1.3 LOAD RESISTANCE. |
| | ALL EXTERIOR WALLS, WALL COVERINGS AND SOFFITS SHALL BE |
| | CAPABLE OF RESISTING THE DESIGN PRESSURES SPECIFIED IN |
| | TABLE R301.2(2) FOR WALLS. MANUFACTURED SOFFITS SHALL |
| | BE LABELED IN ACCORDANCE WITH SECTION R616 OF THIS |
| | CODE. |
| | |
| | R703.2 WEATHER-RESISTANT SHEATHING PAPER. |
| | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| | BREAKS, COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT OR |
| | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. SUCH |
| | FELT OR MATERIAL SHALL BE APPLIED HORIZONTALLY, WITH |
| | THE UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS |
| | THAN 2 INCHES (51 MM). WHERE JOINTS OCCUR, FELT SHALL |
| | BE LAPPED NOT LESS THAN 6 INCHES (152 MM). THE FELT OR |
| | OTHER APPROVED MATERIAL SHALL BE CONTINUOUS TO THE TOP |
| | OF WALLS AND TERMINATED AT PENETRATIONS AND BUILDING |
| | APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE |
| | EXTERIOR WALL ENVELOPE AS DESCRIBED IN SECTION R703.1. |
| | |
| | |
| | 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN; |
| | 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) |
| | REQUIREMENTS SHALL INCLUDE: |
| | WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING |
| | ASSEMBLY AND MATERIALS CONNECTOR |
| | BUILDING ENVELOPE WALL & OPENING PROTECTION WINDOWS |
| | INTERIOR FINISHES WALL & CEILING |
| | ROOFING ASSEMBLIES ROOFING IS A SEPARATE PERMIT. |
| | |
| | 4) R612.5 PERFORMANCE. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE DESIGNED TO RESIST |
| | THE DESIGN WIND LOADS SPECIFIED IN TABLE R301.2(2) |
| | ADJUSTED FOR HEIGHT AND EXPOSURE PER TABLE R301.2(3). |
| | FOR TESTING REQUIRED IN SECTIONS R612.6, R612.7, AND |
| | R612.8, DESIGN PRESSURES DETERMINED FROM TABLE |
| | R301.2(2) OR ASCE 7 ARE PERMITTED TO BE MULTIPLIED BY |
| | 0.6. |
| | |
| | R612.6 TESTING AND LABELING. |
| | EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: |
| | |
| | ANSI/AAMA/NWWDA101/I.S.2 OR ANSI/AAMA/WDMA |
| | 101/I.S.2/NAFS OR AAMA/WDMA/CSA 101/I.S.2/A440 OR TAS |
| | 202 (HVHZ SHALL COMPLY WITH TAS 202 UTILIZING ASTM E |
| | 1300-98 OR ASTM E 1300-04 02). |
| | |
| | EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE |
| | LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING |
| | PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT. |
| | THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A |
| | PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL |
| | APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING |
| | THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER, |
| | POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT |
| | MAXIMUM SIZE, GLAZING THICKNESS, IMPACT RESISTANCE. |
| | APPROVAL NUMBER, APPLICABLE TEST STANDARD(S), AND |
| | APPROVED PRODUCT CERTIFICATION AGENCY, TESTING |
| | LABORATORY, EVALUATION ENTITY OR MIAMI-DADE PRODUCT |
| | APPROVAL. |
| | |
| | THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE RATING |
| | PER REFERENCE STANDARD. THE TEMPORARY SUPPLEMENTAL |
| | LABEL SHALL REMAIN ON THE WINDOW OR DOOR UNTIL FINAL |
| | APPROVAL BY THE BUILDING OFFICIAL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |