Plan Review Details - Permit 14071212
Plan Review Stops For Permit 14071212
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-03-18 Cont ID  
Sent By rmcdouga Date 2015-03-18 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2015-03-18 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-23 Cont ID  
Sent By rmcdouga Date 2014-12-23 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2014-12-23 Time 12:36 Sent To P
Notes
2014-12-23 15:15:03APPROVED WITH EXCEPTION
 SUBMIT AN ADDITIONAL SET OF TRUSS DRAWINGS FOR APPROVAL
 PRIOR TO ROOF FRAMING INSPECTION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2014-11-12 Time 07:06 Sent To P
Notes
2014-11-13 17:13:53PLAN REVIEW COMMENTS
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THERE WAS ONLY ONE SET OF ENGINEERED TRUSS
 DRAWINGS IN THE RE-SUBMITTAL PACKAGE.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS THAT
 ADEQUATELY REPRESENT THE STRUCTURE AND ITS COMPONENTS.
 SEE COMMENTS #1 & #6 FROM 1ST REVIEW. FBC ENERGY
 CONSERVATION SECT. 103.2.2
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY.
 A) "STICKY BACK" ROOF TILE UNDERLAYMENT AS SPECIFIED ON
 THE PLANS.
 B) THE 6' X 8' OVERHEAD GARAGE DOOR.
 C) THE PRODUCT APPROVAL FOR THE 3M, AH-160 FOAM ROOF
 TILE ADHESIVE THAT HAD BEEN SUPERSEDED WAS REPLACED
 WITH PRODUCT APPROVALS FOR 3M, RTA-1 (NOA 12-0228.18).
 THE INSTALLATION NOTES REQUIRE THIS PRODUCT TO BE USED
 WITH APPROVED ROOF TILES THAT LIST IT AS A METHOD OF
 ATTACHMENT WITH A SPECIFIED MINIMUM ATTACHMENT
 RESISTANCE. THE PRODUCT APPROVAL FOR THE ROOF TILE THAT
 WAS SUBMITTED DOES NOT LIST THIS PRODUCT. FBC-R 301.1
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-15 Cont ID  
Sent By rmcdouga Date 2014-09-15 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2014-09-11 Time 09:50 Sent To  
Notes
2014-09-11 10:02:12PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE ENERGY COMPLIANCE FORM THAT WAS SUBMITTED FOR
 THIS SINGLE FAMILY DWELLING IS WORST CASE AND DOES NOT
 MATCH THE ORIENTATION OF THE STRUCTURE. THE HVAC LOAD
 CALCULATIONS THAT WERE SUBMITTED SPECIFY THAT THE FRONT
 DOOR FACES NORTHEAST. BASED ON THE SURVEY THAT WAS
 SUBMITTED, THE FRONT DOOR FACES WEST. FBC ENERGY
 CONSERVATION 403.6.1
  
 2) IDENTIFY THE ELEVATION THAT WILL BE USED FOR THIS
 DWELLING AND CROSS OUT THE OTHERS. FBC 107.2.1
  
 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE PRODUCT APPROVALS FOR THE ROOF TILE
 UNDERLAYMENT AND THE 6 FOOT WIDE OVERHEAD GARAGE DOOR.
 THE SLIDING GLASS DOOR NOA NO. 11- 1018.14 AND THE ROOF
 TILE ADHESIVE NOA NO. 12-0228.18 HAVE BEEN SUPERSEDED.
 THE FIXED WINDOW NOA NO. 13-0502.03 ONLY HAD 9 COPIES
 OF THE FIRST PAGE. THE INSTALLATION DRAWINGS ARE
 MISSING.
  
 4) SPECIFY THE REQUIRED EMBEDMENT DEPTH OF THE 3/4"
 DIA. ANCHOR BOLTS FOR THE COLUMN BASE IN DETAIL 1 ON
 S-1.
  
 5) FBC 109.3 THE VALUATION ON THE APPLICATION OF
 $239,116.00 IS LOW AND HAS BEEN ADJUSTED TO $432,598.00
 BASED ON THE LATEST ICC VALUATION DATA.
  
 6) THE ENERGY CALCULATIONS LIST INSULATED DOORS FOR THE
 DOORS WITH GLASS INSERTS. THE SIMULATED PERFORMANCE
 METHOD SECTION 405.5.1 REQUIRES ALL GLAZING IN DOORS TO
 BE INCLUDED IN THE TOTAL WINDOW AREA. 405.5.3 DOORS
 WITH GLAZING. FOR DOORS THAT ARE OPAQUE OR WHERE THE
 GLASS IS LESS THAN ONE-THIRD OF THE AREA OF THE DOOR,
 THE TOTAL DOOR AREA SHALL BE INCLUDED IN THE DOOR
 CALCULATION. FOR UNLABELED SLIDING GLASS DOORS OR WHEN
 GLASS AREAS IN DOORS IS GREATER THAN OR EQUAL TO
 ONE-THIRD OF THE AREA OF THE DOOR, THE GLAZING PORTION
 SHALL BE INCLUDED IN THE GLAZING CALCULATION AND THE
 OPAQUE PORTION OF THE DOOR SHALL BE INCLUDED IN THE
 DOOR CALCULATION. WHEN GLASS AREA IN DOORS IS GREATER
 THAN OR EQUAL TO ONE-THIRD OF THE AREA OF THE DOOR, THE
 DOOR SHALL BE INCLUDED IN THE GLAZING CALCULATION AS A
 TOTAL FENESTRATION USING THE TESTED U-FACTOR AND SOLAR
 HEAT GAIN COEFFICIENT.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-12 Cont ID  
Sent By rmcdouga Date 2014-11-12 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2014-11-12 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-13 Cont ID  
Sent By rmcdouga Date 2014-09-13 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2014-09-13 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-03-18 Cont ID  
Sent By rmcdouga Date 2015-03-18 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2015-03-06 Time 09:12 Sent To  
Notes
2015-03-09 09:12:40RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2015-01-20 Time 11:58 Sent To  
Notes
2015-01-20 11:58:51SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 10:03 Rev Time 0.00
Received By tklarge Date 2014-12-08 Time   Sent To  
Notes
2014-12-23 18:05:18SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-08 Cont ID  
Sent By rmcdouga Date 2014-12-08 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2014-12-08 Time 18:06 Sent To  
Notes
2014-12-08 18:10:02SUBMITTAL OF PRODUCT APPROVALS WITH THE DESIGNER OF
 RECORD REVIEW STAMP WERE PUT WITH DENIED PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-15 Cont ID  
Sent By tklarge Date 2014-11-15 Time 07:55 Rev Time 0.00
Received By tklarge Date 2014-10-30 Time 07:15 Sent To  
Notes
2014-10-31 07:15:27R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-15 Cont ID  
Sent By rmcdouga Date 2014-09-15 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2014-07-31 Time 09:59 Sent To  
Notes
2014-08-04 09:59:38SENT TO R23. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2015-02-25 Cont ID  
Sent By rmcdouga Date 2015-02-25 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2015-02-25 Time 08:29 Sent To  
Notes
2015-02-25 08:29:57MU2014-16458

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2015-01-21 Time 14:52 Sent To  
Notes
2015-01-21 14:52:24(REPEAT COMMENT) SUBMIT A COPY OF THE PAID IMPACT FEE
 RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-12-23 Cont ID  
Sent By rmcdouga Date 2014-12-23 Time 18:06 Rev Time 0.00
Received By rmcdouga Date 2014-12-23 Time 18:05 Sent To  
Notes
2014-12-23 18:06:18(REPEAT COMMENT) SUBMIT A COPY OF THE PAID IMPACT FEE
 RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-11-12 Cont ID  
Sent By rmcdouga Date 2014-11-12 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2014-11-12 Time 07:06 Sent To  
Notes
2014-11-12 17:09:53A COPY OF THE PAID IMPACT FEE RECEIPT IS REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-15 Cont ID  
Sent By rmcdouga Date 2014-09-15 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2014-09-15 Time 07:07 Sent To  
Notes
2014-09-15 07:08:20SUBMIT A COPY OF THE PAID IMPACT FEE RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2015-03-18 Cont ID  
Sent By rmcdouga Date 2015-03-18 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2015-03-18 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2015-01-21 Time 14:51 Sent To  
Notes
2015-01-21 14:50:54PLAN REVIEW COMMENTS
  
  
 4TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) BASED ON THE SURVEY THAT WAS SUBMITTED, THE FRONT
 DOOR FACES WEST. ACCORDING TO THE LOAD CALCULATION THE
 TOTAL COOLING LOAD IS 3.22 TONS FOR THE WHOLE HOUSE
 WITH A WEST ORIENTATION. SYSTEM 1 HAS A TOTAL COOLING
 LOAD OF 1.56 TONS AND SYSTEM 2 HAS A TOTAL COOLING LOAD
 OF 1.66 TONS. FROM THE CALULATIONS IT APPEARS THAT BOTH
 UNITS SHOULD BE 2 TONS AT MOST. THE PLANS SPECIFY A 2.5
 TON AND A 2 TON. THE 403.6.1.1 COOLING EQUIPMENT
 CAPACITY. COOLING ONLY EQUIPMENT SHALL BE SELECTED SO
 THAT ITS TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED
 TOTAL LOAD BUT NOT MORE THAN 1.15 TIMES GREATER THAN
 THE TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER'S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD. (
 ACCORDING TO THE LOAD CALCULATIONS A WEST FACING
 BUILDING HAS THE LOWEST REQUIRED LOAD. WHY DO THE PLANS
 SPECIFY EQUIPMENT THAT WAS DETERMINED TO BE WORST
 CASE?)
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-12-23 Cont ID  
Sent By rmcdouga Date 2014-12-23 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2014-12-23 Time 13:18 Sent To  
Notes
2014-12-23 14:22:43PLAN REVIEW COMMENTS
  
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) BASED ON THE SURVEY THAT WAS SUBMITTED, THE FRONT
 DOOR FACES WEST. ACCORDING TO THE LOAD CALCULATION THE
 TOTAL COOLING LOAD IS 3.22 TONS FOR THE WHOLE HOUSE
 WITH A WEST ORIENTATION. SYSTEM 1 HAS A TOTAL COOLING
 LOAD OF 1.56 TONS AND SYSTEM 2 HAS A TOTAL COOLING LOAD
 OF 1.66 TONS. FROM THE CALULATIONS IT APPEARS THAT BOTH
 UNITS SHOULD BE 2 TONS AT MOST. THE PLANS SPECIFY A 2.5
 TON AND A 2 TON. THE 403.6.1.1 COOLING EQUIPMENT
 CAPACITY. COOLING ONLY EQUIPMENT SHALL BE SELECTED SO
 THAT ITS TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED
 TOTAL LOAD BUT NOT MORE THAN 1.15 TIMES GREATER THAN
 THE TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER'S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-12 Cont ID  
Sent By rmcdouga Date 2014-11-12 Time 17:10 Rev Time 0.00
Received By rmcdouga Date 2014-11-12 Time 07:06 Sent To  
Notes
2014-11-12 17:12:01PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. ( REPEAT COMMENT
 )
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-15 Cont ID  
Sent By rmcdouga Date 2014-08-20 Time   Rev Time 0.75
Received By rmcdouga Date   Time   Sent To  
Notes
2014-09-15 07:19:43PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) PROVIDE EQUIPMENT SIZING CALCULATIONS BASED ON THE
 ACTUAL BUILDING ORIENTATION FOR THIS LOT, AS REQUIRED
 BY SECTION 403.6 OF THE 2010 FBC - ENERGY CONSERVATION.
 THE CALCULATIONS THAT WERE SUBMITTED AND THE EQUIPMENT
 LISTED ON THE A/C PLAN ARE FOR WORST CASE.
  
 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
2014-08-20 14:50:55LOADED AND REVIEWED BY RBERGSMA

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 10:02 Rev Time 0.00
Received By tklarge Date 2014-12-24 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-15 Cont ID  
Sent By rmcdouga Date 2014-11-15 Time 17:02 Rev Time 0.00
Received By tklarge Date 2014-11-15 Time 07:55 Sent To  
Notes
2014-11-15 07:40:331)VENT FOR TUB & SHOWER IN MASTER BATH SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.2010
 FBCR SEC.P3104.3. A FLAT DRY VENT AS DRAWN IS NOT
 PERMITTED BY THE PLUMBING CODE.2ND REQUEST.
 2)THERE ARE TWO WET BAR OPTIONS SHOWN ON THE SANITARY
 RISER BUT ONLY ONE SHOWN ON THE FLOOR PLAN AND IT IS
 ALSO CROSSED OFF AS AN OPTION ON SHT. A-1. CLARIFY.2ND
 REQUEST.
 3) THE FLOOR PLAN HAS A NOTE" STUB-OUT FOR FUTURE
 SUMMER KITCHEN" BUT NOTHING IS SHOWN ON THE SANITARY
 RISER. WPB AMEND TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-31 Cont ID  
Sent By tklarge Date 2014-08-31 Time   Rev Time 0.00
Received By tklarge Date 2014-08-31 Time 05:30 Sent To  
Notes
2014-08-31 05:50:391) REMOVE THE SHUTOFF VALVE SHOWN ON THE 3" BUILDING
 DRAIN ON THE ISOMETRIC ON SHT. A-3.2010 FBCR SEC.
 P3002.3.1.
 2) VENT FOR TUB & SHOWER IN MASTER BATH SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.2010
 FBCR SEC.P3104.3
 3) THERE ARE TWO WET BAR OPTIONS SHOWN ON THE SANITARY
 RISER BUT ONLY ONE IS SHOWN ON THE FLOOR PLAN AND IT IS
 ALSO CROSSED OFF AS AN OPTION ON SHT. A-1. CLARIFY.
 4) SHOW THE LENGTH DIMENSION OF EACH SECTION OF GAS
 RISER TO CONFIRM THE TOTAL LONGEST LENGTH FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET. INCLUDE
 ALL DROPS AND STUB-OUTS. WPB ADMIN. AMEND. TO 2010 FBC
 SEC. 107.2.1.
 5) THE GAS RISER IS SHOWING 2 1/2 " VALVES ON 1" GAS
 LINES. CLARIFY.
 6) I CALCULATED 247,000 BTU'S AND THE GAS LOAD ON THE
 PLAN STATES 265.000 BTU'S CLARIFY.
 7) NOTE ON SHT. A-3 STATES "SEE GAS PLAN AT SHEET E-1."
 THERE IS NO GAS PLAN ON E-1 EXCEPT FOR THE GAS METER
 AND A NOTE THAT STATES" 1 1/4" GAS UP TO ATTIC" AND IT
 SHOWS THE GAS APPLIANCES. CLARIFY.
 8) SHT.A-1-GARAGE-NOTE REFERS TO 2010 FBC SEC. 3034 FOR
 PROTECTION OF WATER HEATER. THERE IS NO SUCH CODE
 SECTION IN THE BUILDING CODE OR IN THE RESIDENTIAL
 CODE. CLARIFY.
 9) SHT.A-3-THE GAS NOTES REFER TO AN LP GAS SYSTEM AND
 ALSO NATURAL GAS AND THE SPECIFIC GRAVITY YOU HAVE
 LISTED FOR THE TYPE OF GAS IS FOR LP GAS AND A GAS
 METER AND A CONNECTION TO THE GAS COMPANY IS SHOWN ON
 THE RISER DIAGRAM. WHAT IS IT, LP OR NATURAL? REMOVE
 ANY NOTES THAT ARE NOT APPLICABLE TO THE CORRECT TYPE
 OF GAS.
 10) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION
 CONTROL OF THE WATER SUPPLY SYSTEM IN ACCORDANCE WITH
 2010 FBCR SEC. P2903.4 & P2903.4.2.DUE TO THE
 INSTALLATION OF A BACKFLOW PREVENTER FOR THE IRRIGATION
 SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 15:08 Sent To  
Notes
2014-11-13 15:13:57ROOFING MATERIALS:
 ENTEGRA ESTATE "S" TILE - NOA NO. 11-0510.02 (ATTACHED
 WITH 2-10D RING SHANK NAILS)
 3M FOAM ROOF TILE ADHESIVE RTA-1
 NO PRODUCT APPROVAL FOR UNDERLAYMENT WAS SUBMITTED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-11-03 Cont ID  
Sent By dkittred Date 2014-11-03 Time 12:41 Rev Time 0.00
Received By dkittred Date 2014-11-03 Time 10:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-06 Cont ID  
Sent By dkittred Date 2014-08-06 Time 16:29 Rev Time 0.00
Received By dkittred Date 2014-08-06 Time 10:14 Sent To  
Notes
2014-08-06 16:29:28PLANNING AND ZONING COMMENTS: ***FAILED***
  
 8/6/14
  
 ITEMS TO BE REVISED/SUBMITTED:
  
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF. PLEASE ADJUST
 CALCULATIONS TABLE.)
  
 OTHER COMMENTS:
  
 2. SEPARATE PERMIT WILL BE REQUIRED FOR THE DRIVEWAY.
  
 3. NOTE ADDED TO PLAN THAT MECHANICAL EQUIPMENT (A/C
 UNIT) MUST BE AT LEAST 4' FROM THE PROPERTY LINE.
  
 4. NOTE ADDED TO PLAN THAT PRIVACY WALL NOT UNDER ROOF
 CANNOT EXCEED 6' IN HEIGHT.
  