| 2014-08-02 15:23:09 | DATE: 8/2/2014 |
| | PROJECT: ORNEGA CIRCLE |
| | PERMIT#: 14071193 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NEC 408.36(D) BACK-FED DEVICES. PLUG-IN-TYPE |
| | OVERCURRENT PROTECTION DEVICES OR PLUG-IN TYPE MAIN LUG |
| | ASSEMBLIES THAT ARE BACK-FED AND USED TO TERMINATE |
| | FIELD-INSTALLED UNGROUNDED SUPPLY CONDUCTORS SHALL BE |
| | SECURED IN PLACE BY AN ADDITIONAL FASTENER THAT |
| | REQUIRES OTHER THAN A PULL TO RELEASE THE DEVICE FROM |
| | THE MOUNTING MEANS ON THE PANEL. PROVIDE AND INDICATE |
| | ON THE PLANS THE MANUFACTURER COMPLIANT DEVICE TO BE |
| | USED WITH THE BACK-FED MAIN BREAKER |
| | |
| | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. |
| | SIGN THE PLANS. |
| | |
| | 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| | 505.2.4 IDENTIFY THE PHOTOCELL AS THE LIGHTING |
| | CONTROLLER FOR CODE COMPLIANCE. |
| | |
| | 4) PROVIDE A FIXTURE SCHEDULE AND A COPY OF THE FIXTURE |
| | PROPOSED TO BE USED FOR THE MOMUMENT WALL SIGN AND A |
| | DETAIL OF THE INSTALLATION METHOD TO INDICATE |
| | COMPLIANCE WITH NEC 110.3 AND FBC 107.2.1 |
| | |
| | ADDITIONAL PERMITS AND SHOP DRAWINGS REQUIRED FOR THE |
| | INSTALLATION OF THE MONUMENT SIGNS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |