| Plan Review Stops For Permit 14071125 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-11-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-26 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-26 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-03 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-10-29 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2014-10-29 16:52:32 | BUILDING PLAN REVIEW | | | PERMIT: 14071125 | | | ADD: | | | CONT: | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. NOV. 03/2014 | | | ACTION: DENIED | | | | | | | | | 1) THE SUBMITTED PERMIT APPLICATION IS FOR THE INTERIOR | | | DEMOLITION AND VALUE REFLECTED IS FOR A INTERIOR DEMO | | | ONLY. THE NEW SUBMITTED PLANS SHOW THE NEW INTERIOR | | | BUILD OUT AND CEILING PLANS, NOT A INTERIROR DEMO, | | | WITHIN THE TITALBLOCK THE PLANS STATE INTERIOR | | | DEMOLITION AND REMODAL. THE ORIGINAL PLANS THE REMODAL | | | WAS BLACKED OUT. | | | | | | THE NEW INTERIOR BUILD OUT PLANS INDICATE A A2 ASSEMBLY | | | OCCUPANCY, A RESTARUANT WITH AN OCCUPANT LOAD IN THE | | | DINING AREA WITH ONLY ONE EXIT THE (2) ENTRY/ EXIT | | | DOORS ARE NOT 1/2 THE DIAGONAL DISTANCE APART TO BE | | | CONSIDERED 2 SEPARATE EXITS. | | | SEE 2010 FBC-B TABLE 1015.1 SPACES WITH ONE EXIT OR | | | EXIT ACCESS DOORWAY. | | | | | | 1014.2 EGRESS THROUGH INTERVENING SPACES. EGRESS | | | THROUGH INTERVENING SPACES SHALL COMPLY WITH THIS | | | SECTION. | | | ( 4.) EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. | | | | | | 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS. | | | WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED | | | FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR | | | EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART | | | EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE | | | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR | | | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN | | | EXIT DOORS OR EXIT ACCESS DOORWAYS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-08-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-25 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-25 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2014-08-25 07:23:59 | PLANS FOR INTERIOR DOEM OF NON-LAOD BEARING WALLS ONLY. | | | CROSSED OUT PLANS FOR PROPOSED REMODAL. JW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-11-26 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-26 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-26 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-10-22 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-10-22 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-10-22 |
Time |
08:52 |
Sent To |
B |
|
| Notes |
| 2014-10-22 08:52:36 | TO MISC. 2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-09-03 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-03 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-09-03 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2014-11-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-11-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-11-17 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-10-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-10-17 |
Time |
15:33 |
Sent To |
E |
|
| Notes |
| 2014-10-17 15:49:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | EXIT PATH SIGNS WERE REDUCED WHERE NOT REQUIRED AS | | | INDICATED AND HAND WRITTEN ON THE PLAN. | | | | | | THE EXIT SIGN AT THE DOOR TO THE STORAGE AREA WAS | | | REMOVED AS EXITING THROUGH A STORAGE AREA IS A | | | VIOLATION IN ADDITION TO IT NOT BEING REQUIRED. | | | | | | THE FIRE INSPECTOR WILL VERIFY AT THE TIME OF FIRE | | | INSPECTION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-08-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-08-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-08-15 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2014-08-15 10:06:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE SUBMITTED PLAN DOES NOT PROVIDE A LIFE SAFETY PLAN, | | | INCLUDING OCCUPANY TYPE, CONSTRUCTION TYPE, BUILDING | | | LIFE SAFETY FEATURES, OCCUPANY LOADS, EXIT PATHS, | | | EXITS, EXIT LIGHTS, EXIT DOOR HARDWARE, EMERGENCY | | | LIGHTING, AND SEATING PLAN. | | | | | | THE OCCUPANCY SEPARATION FIRE RATING IS NOT PROVIDED. | | | | | | THE CEILING DESIGN/TYPE IS NOT PROVIDED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-11-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-26 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-14 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2014-11-15 08:50:10 | B14 NEW PLANS WERE SUBMITTED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-06 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-10-17 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2014-10-22 13:41:41 | 10/22 TO JW DESK | | | | | 2014-10-17 11:24:50 | SENT TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-09-03 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-03 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-30 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2014-08-14 17:55:43 | B24 | | | | | | | | 2014-07-30 13:27:06 | BLDG <5000 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-11-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-25 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-25 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-11-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-06 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-06 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2014-11-06 06:46:25 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ANY | | | CHANGES/ALTERATIONS TO THE PLUMBING SYSTEM. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | 2) SOME OF THE PLUMBING FIXTURES SHOWN ON SHT. 1 ARE | | | NOT SHOWN ON SHT. 2. CLARIFY. | | | 3) WILL ANY ADDITIONAL SEATS BE ADDED? IF SO SUBMIT A | | | SEATING PLAN. INDICATE SUCH ON BOTH SETS OF PLANS. | | | 4) SUBMIT REVISED CALCULATIONS FOR THE GREASE TRAP IF | | | THE OCCUPANT LOAD HAS INCREASED. INDICATE THE PREVIOUS | | | OCCUPANT LOAD AND THE NEW OCCUPANT LOAD ON THE PLANS. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 5) REVISE THE WORK DESCRIPTION ON THE APPLICATION. THE | | | APPLICATION STATES "DEMOLITION OF INTERIOR PARTITION" | | | WHEN THIS IS A REMODEL. WPB AMEND. TO 2010 FBC | | | SEC.105.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|