Plan Review Details - Permit 14071125
Plan Review Stops For Permit 14071125
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-03 Cont ID  
Sent By jwitmer Date 2014-11-03 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2014-10-29 Time 16:49 Sent To  
Notes
2014-10-29 16:52:32BUILDING PLAN REVIEW
 PERMIT: 14071125
 ADD:
 CONT:
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 03/2014
 ACTION: DENIED
  
  
 1) THE SUBMITTED PERMIT APPLICATION IS FOR THE INTERIOR
 DEMOLITION AND VALUE REFLECTED IS FOR A INTERIOR DEMO
 ONLY. THE NEW SUBMITTED PLANS SHOW THE NEW INTERIOR
 BUILD OUT AND CEILING PLANS, NOT A INTERIROR DEMO,
 WITHIN THE TITALBLOCK THE PLANS STATE INTERIOR
 DEMOLITION AND REMODAL. THE ORIGINAL PLANS THE REMODAL
 WAS BLACKED OUT.
  
 THE NEW INTERIOR BUILD OUT PLANS INDICATE A A2 ASSEMBLY
 OCCUPANCY, A RESTARUANT WITH AN OCCUPANT LOAD IN THE
 DINING AREA WITH ONLY ONE EXIT THE (2) ENTRY/ EXIT
 DOORS ARE NOT 1/2 THE DIAGONAL DISTANCE APART TO BE
 CONSIDERED 2 SEPARATE EXITS.
 SEE 2010 FBC-B TABLE 1015.1 SPACES WITH ONE EXIT OR
 EXIT ACCESS DOORWAY.
  
 1014.2 EGRESS THROUGH INTERVENING SPACES. EGRESS
 THROUGH INTERVENING SPACES SHALL COMPLY WITH THIS
 SECTION.
 ( 4.) EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR
 EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART
 EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 EXIT DOORS OR EXIT ACCESS DOORWAYS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 07:22 Sent To  
Notes
2014-08-25 07:23:59PLANS FOR INTERIOR DOEM OF NON-LAOD BEARING WALLS ONLY.
 CROSSED OUT PLANS FOR PROPOSED REMODAL. JW

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-11-26 Cont ID  
Sent By dhayes Date 2014-11-26 Time 16:07 Rev Time 0.00
Received By dhayes Date 2014-11-26 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-22 Cont ID  
Sent By dhayes Date 2014-10-22 Time 08:52 Rev Time 0.00
Received By dhayes Date 2014-10-22 Time 08:52 Sent To B
Notes
2014-10-22 08:52:36TO MISC. 2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 16:44 Rev Time 0.00
Received By dhayes Date 2014-09-03 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-11-17 Cont ID  
Sent By pleduc Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-17 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-17 Cont ID  
Sent By pleduc Date 2014-10-17 Time   Rev Time 0.00
Received By pleduc Date 2014-10-17 Time 15:33 Sent To E
Notes
2014-10-17 15:49:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 EXIT PATH SIGNS WERE REDUCED WHERE NOT REQUIRED AS
 INDICATED AND HAND WRITTEN ON THE PLAN.
  
 THE EXIT SIGN AT THE DOOR TO THE STORAGE AREA WAS
 REMOVED AS EXITING THROUGH A STORAGE AREA IS A
 VIOLATION IN ADDITION TO IT NOT BEING REQUIRED.
  
 THE FIRE INSPECTOR WILL VERIFY AT THE TIME OF FIRE
 INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-15 Cont ID  
Sent By pleduc Date 2014-08-15 Time   Rev Time 0.00
Received By pleduc Date 2014-08-15 Time 09:15 Sent To  
Notes
2014-08-15 10:06:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTED PLAN DOES NOT PROVIDE A LIFE SAFETY PLAN,
 INCLUDING OCCUPANY TYPE, CONSTRUCTION TYPE, BUILDING
 LIFE SAFETY FEATURES, OCCUPANY LOADS, EXIT PATHS,
 EXITS, EXIT LIGHTS, EXIT DOOR HARDWARE, EMERGENCY
 LIGHTING, AND SEATING PLAN.
  
 THE OCCUPANCY SEPARATION FIRE RATING IS NOT PROVIDED.
  
 THE CEILING DESIGN/TYPE IS NOT PROVIDED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2014-11-14 Time 08:50 Sent To  
Notes
2014-11-15 08:50:10B14 NEW PLANS WERE SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-06 Cont ID  
Sent By jwitmer Date 2014-11-06 Time 06:50 Rev Time 0.00
Received By tklarge Date 2014-10-17 Time 11:24 Sent To  
Notes
2014-10-22 13:41:4110/22 TO JW DESK
  
2014-10-17 11:24:50SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 16:45 Rev Time 0.00
Received By dhayes Date 2014-07-30 Time 13:26 Sent To  
Notes
2014-08-14 17:55:43B24
  
  
2014-07-30 13:27:06BLDG <5000

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-25 Cont ID  
Sent By tklarge Date 2014-11-25 Time 09:55 Rev Time 0.00
Received By tklarge Date 2014-11-25 Time 09:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By tklarge Date 2014-11-06 Time 06:49 Rev Time 0.00
Received By tklarge Date 2014-11-06 Time 06:25 Sent To  
Notes
2014-11-06 06:46:251) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ANY
 CHANGES/ALTERATIONS TO THE PLUMBING SYSTEM. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 2) SOME OF THE PLUMBING FIXTURES SHOWN ON SHT. 1 ARE
 NOT SHOWN ON SHT. 2. CLARIFY.
 3) WILL ANY ADDITIONAL SEATS BE ADDED? IF SO SUBMIT A
 SEATING PLAN. INDICATE SUCH ON BOTH SETS OF PLANS.
 4) SUBMIT REVISED CALCULATIONS FOR THE GREASE TRAP IF
 THE OCCUPANT LOAD HAS INCREASED. INDICATE THE PREVIOUS
 OCCUPANT LOAD AND THE NEW OCCUPANT LOAD ON THE PLANS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 5) REVISE THE WORK DESCRIPTION ON THE APPLICATION. THE
 APPLICATION STATES "DEMOLITION OF INTERIOR PARTITION"
 WHEN THIS IS A REMODEL. WPB AMEND. TO 2010 FBC
 SEC.105.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  