| 2014-11-21 15:22:29 | BUILDING PLAN REVIEW |
| | PERMIT:14071105 |
| | ADD: 1517 CAMERON SAMUEL LN. |
| | CONT: KAST |
| | TEL: (561)346-4994 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. NOV.21/2014 |
| | ACTION: DENIED |
| | |
| | 1A) COMPLIED WITH CORRECTED ADDRESS. |
| | |
| | 1B) COMPLIED. |
| | |
| | 2) COMPLIED. NEW SITE PLAN. |
| | |
| | 3) COMPLIED. 3 ORIGINAL SOILS REPORTS. |
| | |
| | 4) 2ND REQUEST. COVERSHEET: THE BUILDING CODE ANALYSIS |
| | INDICATES THIS BUILDING TO BE A FIRE SPRINKLERED |
| | BUILDING. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS.:107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.5 |
| | . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| | FIRE SPRINKLERS. THE DESIGNER OF RECORD HAS TAKEN AREA |
| | INCREASES WITH THE INSTALLATION OF A NFPA 13 SYSTEM, |
| | 2010 FBC-B 504.2., 903.2.1.2 AND 903.2.1.3. |
| | |
| | 5) COMPLIED. FITNESS CENTER WITH EQUIPMENT LAYOUT. |
| | |
| | 6) SHEET A-1.0: |
| | 6A) COMPLIED. FIRE BOX SIZING. |
| | |
| | 6B) 2ND REQUEST. THE THEATER SEATING SHOW RAISED |
| | SEATING, THE S6 SHEET SHOWS GEO FOAM NO MANUFACTURERS |
| | SPECS WERE SUBMITTED NOR DOES THE PLANS INDICATE THE |
| | END OF THE FOAM ARE ENCAPSULATED BY CONCRETE ON THE |
| | SIDES. FBC-B 2603.4.1.1. THE STRUCTURAL ENGINEER HAS |
| | SHOWN ON SHEET S-6 THE FOAM BEING TOTALLY ENCLOSED. THE |
| | CONTRACTOR HAS NOT SUBMITTED PRODUCT TESTING REPORTS |
| | AND MANUFACTURERS SPECS FOR THE STRUCTURAL FOAM, NOR |
| | HAS IT BEEN REVIEWED BY THE ENGINEER OF RECORD FOR |
| | APPROVAL, BY SHOP DRAWING STAMP, APPROVED OR APPROVED |
| | WITH COMMENT. |
| | |
| | 7) COMPLIED. 12/02/14 |
| | . THE CONTRACTOR HAS NOT SUBMITTED THE MANUFACTURERS |
| | SPEC AND REPORT WHERE THIS PRODUCT CAN BE USED AND |
| | LIMITATIONS OF SAID PRODUCT. |
| | SHEET A4.1 INDICATES THE USE OF ICYNENE INSULATION AS |
| | WELL AS THE COVER SHEET ALSO HAS NOTES FOR ICYNENE. |
| | ICYNENE IS TO BE INSTALLED UNDER THE ROOF DECK. PLEASE |
| | SUBMIT THE FULL ICYNENE REPORT LISTED ERS 1826 FOR |
| | REVIEW; 2010 FBC-B 2603.4.1.6. PLEASE PROVIDE WHICH |
| | AREAS ARE GOING TO HAVE ICYNENE TYPE INSULATION AND |
| | WHICH AREAS OF THE ROOFING ARE GOING TO HAVE ROOF TOP |
| | INSULATION ON TOP OF THE ROOF DECK AS DEPICTED IN |
| | DETAILS B-E. THE ENERGY SPECS INDICATE A R-33, PLEASE |
| | PROVIDE HOW MUCH INSULATION IT WILL TAKE TO PROVIDE |
| | THIS VALUE. |
| | |
| | . |
| | |
| | 8) SEMI- COMPLIED. SHEETA-2.2 & A-4.1. SHEET A-2.2 |
| | DETIAL # 1 SHOWS THE USE OF 1 INCH RIGID INSULATION |
| | BOARD AND THE 5/8 INCH DRYWALL EXTENDING 6 IN. ABOVE |
| | THE CEILING LEAVING THE INSULATION BOARD EXPOSED ABOVE |
| | THE CEILING. PLEASE PROVIDE COMPLIANCE WITH 2603.4 |
| | THERMAL BARRIERS OR 2603.4.1. PROVIDE THE MANUFACTURERS |
| | SPEC SHEET FOR THE 1 INCH RIGID INSULATION, INCLUDE |
| | FLAME SPREAD & SMOKE DEVELOPMENT. |
| | |
| | 9A) DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF |
| | RECORD. |
| | MISSING PRODUCT APPROVALS, MAY BE SUBMITTED AS DEFERRED |
| | SUBMITTALS UPON WRITTEN REQUEST: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STAND |
| | |
| | 9B)DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF |
| | RECORD. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) NEW COMMENT!!!!! THIS BUILDING QUALIFIES AS A |
| | THRESHOLD BUILDING, AN ASSEMBLY OCCUPANCY WITH AN |
| | OCCUPANT LOAD GREATER THAN 500 OCCUPANTS & 5,000 SQ. |
| | FT. IN AREA. PLEASE SEE NEW COMMENTS THAT WILL BE |
| | REQUIRED AS A THRESHOLD BUILDING. THIS MORNING I |
| | E-MAILED MATTHEW SLATTER THE REQUIREMENTS FOR A |
| | THRESHOLD BUILDING AND FORMS THAT WILL BE REQUIRED TO |
| | BE SIGNED. |
| | |
| | 10A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 10B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 |
| | W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR |
| | THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY |
| | FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM |
| | INSPECTIONS REQUIRED BY THIS CODE. PLEASE FILE OUT |
| | FORMS BY ALL INTERESTED PARTIES. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 10C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 10D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 10D)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 10E) NOTICE!!!! PLEASE CALL THE CITY OF WEST PALM |
| | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | |
| | 10F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 10G) NOTE SINCE THIS IS A THRESHOLD PROJECT (3) SETS OF |
| | PLANS, REPORTS, AND PRODUCT APPROVALS WILL BE REQUIRED, |
| | A 3RD SET WILL BE FOR THE THRESHOLD INSPECTORS USE. |
| | |
| | 11A) NOTICE THIS BUILDING CAN NO LONGER BE CLASSIFIED |
| | AS A BUILDING CATEGORY II WITH A OCCUPANT LOAD OF 762 |
| | OCCUPANTS. ASCE 7-10 TABLE 1.5-1 RISK AS WELL AS 2010 |
| | FBC-B TABLE 1604.5. BUILDINGS FOR PUBLIC ASSEMBLY WITH |
| | OCCUPANT LOADS GREATER THAN 300. |
| | CATEGORIES LIST THIS AS A CATEGORY III WHICH WILL |
| | INCREASE THE PRESSURES SINCE THE WIND SPEED VULT WILL |
| | BE 180 MPH. |
| | |
| | THIS WILL EFFECT SHEET S-6 WITH ALL PRESSUES FLAT ROOF, |
| | SLPOED ROOFS (5:12 PITCH) AS WELL AS WALL PRESSURES IN |
| | ZONES 4 & 5. PLEASE UPDATE CHARTS. INDICATE IF |
| | PRESSURES ARE VULT OR VASD. THERE ARE ALSO PRESSURES |
| | THAT ARE TAKEN FROM RAS 128 FOR BUILDINGS THAT ARE LESS |
| | THAN 40 FT IN HEIGHT, EXPOSURE "C" FOR A FLAT ROOF, |
| | PLEASE NOTE THESE PRESSURES CAN ONLY BE USED FOR |
| | BUILDING CATEGORY II BUILDINGS. |
| | |
| | 11B) SHEET S-6 ALSO IS MISSING THE WALL PRESSURES FOR |
| | WALL ZONES 4 & 5. COMPONENTS & CLADDING PRESSURES |
| | POSITVE & NEGATIVE TABLE 1609.2(2) . |
| | |
| | 12-13) COMPLIED. |
| | |
| | 14) NEW COMMENT: THE COMBINED OCCUPANT LOAD OF |
| | BUILDING, POOL AND POOL DECK IS 1,247 SHOW COMPLIANCE |
| | WITH: |
| | 2010 FBC-B F] 907.2.1.1 SYSTEM INITIATION IN GROUP A |
| | OCCUPANCIES WITH AN OCCUPANT LOAD OF 1,000 OR MORE. |
| | ACTIVATION OF THE FIRE ALARM IN GROUP A OCCUPANCIES |
| | WITH AN OCCUPANT LOAD OF 1,000 OR MORE SHALL INITIATE A |
| | SIGNAL USING AN EMERGENCY VOICE/ALARM COMMUNICATIONS |
| | SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2. |
| | |
| | EXCEPTION: WHERE APPROVED, THE PRERECORDED ANNOUNCEMENT |
| | IS ALLOWED TO BE MANUALLY DEACTIVATED FOR A PERIOD OF |
| | TIME, NOT TO EXCEED 3 MINUTES, FOR THE SOLE PURPOSE OF |
| | ALLOWING A LIVE VOICE ANNOUNCEMENT FROM AN APPROVED, |
| | CONSTANTLY ATTENDED LOCATION. |
| | |
| | 15) ENERGY GAUGE FORM 506-2010 ONLY ONE REPORT WAS |
| | SUBMITTED, NOTE THAT THE ENGINEEER SEALED THE REPORT |
| | BUT DID NOT SIGN NOR DATE THE REPORT. 61G15-23.002(2) |
| | FL. ADMIN. CODE. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |