Plan Review Details - Permit 14070980
Plan Review Stops For Permit 14070980
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By dhayes Date 2014-07-29 Time 14:50 Rev Time 0.00
Received By dhayes Date 2014-07-29 Time 14:50 Sent To  
Notes
2014-07-29 15:30:03DATE: 7/29/2014
 PROJECT: 827 FERNWOOD DR.
 PERMIT#: 14070980
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.
 QUALIFIER TO SIGN PLANS.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 107.2.1 PROVIDE THE
 FOLLOWING ADDITIONAL INFORMATION FOR CLARIFICATION.
  
 EXISTING SYSTEM LOAD AND VOLTAGE.
 LOAD CALCULLATION REQUIRED TO SUPPPORT PANEL SIZE.
 SERVICE ENTRANCE CONDUCTORE SIZE.
 GROUNDING ELECTRODE SYSTEM SIZE, TYPE AND DETAIL.
 BRANCH CIRCUITS IN THE PANEL BEING RELOCATED IN THE
 11/4" RACEWAY.
  
 3) THERE'S A MENTION ON THE PERMIT APLICATION OF THE
 INSTALLATION OF A WATER HEATER. ADDITIONAL INFORMATION
 IS REQUIRED FOR THIS AS WELL. ADDITIONAL INFORMATION
 REQUITRED. FBC 107.2.1.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-29 Cont ID  
Sent By dhayes Date 2014-07-29 Time 15:30 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2014-07-25 11:25:57ROUTED TO ELECTRICAL LESS THAN $5000