Plan Review Details - Permit 14070935
Plan Review Stops For Permit 14070935
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By jwitmer Date 2014-10-03 Time 11:51 Rev Time 0.00
Received By jwitmer Date 2014-10-03 Time 11:51 Sent To  
Notes
2014-10-03 11:52:37NO REVIEW, IN THE RAIROAD RIGHT OF WAY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-10-10 Cont ID  
Sent By dhayes Date 2014-10-10 Time 16:50 Rev Time 0.00
Received By dhayes Date 2014-10-10 Time 16:50 Sent To  
Notes
2014-10-10 16:57:1110/10/2014
 PROJECT: SFRTA GENERATOR / UPS
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: NOTE
  
 1) VERIFY THE LOAD AND CIRCUIT SIZE AT EQUIPMENT RACK
 P1. THE PANEL SCHEDULE FOR PANEL UPS01 INDICATES A
 100AMP 3PHASE CIRCUIT BREAKER ON CIRCUIT #15,17,19 WITH
 A 1.75 KW LOAD. THIS APPEARS TO BE AN OVERSIGHT ONLY TO
 BE VERIFIED IN THE FIELD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-09-30 Cont ID  
Sent By DHAYES Date 2014-09-30 Time 07:59 Rev Time 0.00
Received By dhayes Date 2014-09-30 Time 07:33 Sent To FIRE
Notes
2014-09-30 11:09:289/30/2014
 PROJECT: SFRTA ELECTRICAL RENNOVATION
 PERMIT#: 14070935
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE EQUIPMENT MANUFACTURER DOCUMENTATION FOR THE
 UPS UNIT.
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR CONCRETE SLAB, LOW VOLTAGE SCOPE SUCH
 AS BUT LIMITED TO, ACCESS CONTROL, DATA/COM, NETWORK,
 STRUCTURED CABLING, AUDIO, VIDEO, CCTV, & SECURITY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 11:37 Rev Time 0.00
Received By dhayes Date 2014-09-15 Time 11:31 Sent To FIRE
Notes
2014-09-15 11:57:22DATE: 9/15/2014
 PROJECT: SRFTA ELECTRICAL RENNOVATION
 PERMIT#: 14070935
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E-01
 SYSTEM PHASE AND VOLTAGE IS NOT INDICATED ON THE RISER
 ANYWHERE.
 NOTE 5 CALLS FOR A 100AMP ENCLOSED CIRCUIT BREAKER BUT
 THE RISER LEADS ME TO BELIEVE THIS SHOULD BE A 400AMP
 ENCLOSED CIRCUIT BREAKER AS THE SERVICE ENTRANCE MAIN
 DISCONNECT.
 NOTE 18 CALLS FOR #2WIRE IN 1/2" CONDUIT. CLARIFICATION
 REQUIRED. INDICATE THE NUMBER AND TYPE OF WIRE
 INSTALLED, CORRECT THE CONDUIT SIZE.
 NOTE 19 CALLS FOR A 110AMP FEED WITH #2WIRE IN 1/2"
 CONDUIT. CLARIFICATION REQUIRED. INDICATE THE NUMBER
 AND TYPE OF WIRE INSTALLED, CORRECT THE CONDUIT SIZE.
 DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM
 AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR
 REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL
 BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
 PANEL SCHEDULE A THE CIRCUIT FOR UPS CALLS FOR A 3POLE
 110AMP BREAKER. HOWEVER THE CONDUIT AND WIRE SIZES
 INDICATE 6 SINGLE POLE CIRCUITS WITH 1/2" CONDUIT AND
 #12WIRE. CLARIFICATION REQUIRED.
 PANEL SCHEDULE A THE CIRCUIT FOR PANEL A-1 CALLS FOR A
 3 POLE 100AMP BREAKER. HOWEVER THE CONDUIT AND WIRE
 SIZES INDICATE 3 SINGLE POLE CIRCUITS WITH 1/2" CONDUIT
 AND #12WIRE. CLARIFICATION REQUIRED
 PANEL SCHEDULE UPS01 THE CIRCUIT FOR THE EQUIPMENT RACK
 P1 CALLS FOR A 3 POLE 100AMP BREAKER. HOWEVER THE
 CONDUIT AND WIRE SIZES INDICATE 3 SINGLE POLE CIRCUITS
 WITH 1/2" CONDUIT AND #12WIRE. CLARIFICATION REQUIRED
 PANEL SCHEDULE UPS01 THE CIRCUIT FOR THE EQUIPMENT MAIN
 BREAKER FOR UPS CALLS FOR A 3 POLE 100AMP BREAKER.
 HOWEVER THE CONDUIT AND WIRE SIZES INDICATE 3 SINGLE
 POLE CIRCUITS WITH 1/2" CONDUIT AND #12WIRE.
 CLARIFICATION REQUIRED
  
 2) SHEET E-02
 PROVIDE GROUNDING TERMINATION DETAIL. A 4/0CU GROUND
 RING IS SPECIFIED. INDICATE HOW AND WHERE THE GROUNDING
 ELECTRODE CONDUCTORS ARE TO TERMINATE TO THE GENERATOR
 AND EQUIPMENT GROUND.
  
 3) SHEET E-03
 INDICATE ON THE PLANS THE TYPE AND SIZE OF CONDUIT AND
 WIRE. INDICATE THE NUMBER OF WIRES IN EACH CONDUIT RUN
 INCLUDING HOW MANY CIRCUIT CONDUCTORS, NEUTRALS AND
 GROUNDS. THE SAME APPLIES TO THE DATA CONDUITS AND
 WIRE. INDICATE THE TYPE AND HOW MANY IN EACH.
 PROVIDE A DRAWING OF THE WIRING INSTALLATION DETAIL FOR
 THE EPO.
 PROVIDE A SCALLED DRAWING OF THE EQUIPMENT CLOSET
 INCLUDEING THE EQUIPMENT CLEARANCES REQUIRED BY THE
 MANUFACTURER OF THE UPS AND PER THE NEC 110
 PROVIDE A LOW VOLTAGE OUTLET DETAIL INDICATING WHERE
 CONDUITS ARE TO USED AND WHERE THE LOW VOLTAGE CABLE
 WILL BE INSTALLED IN FREE AIR.
 INDICATE THE CABLE INSTALLATION TYPE TO BE USED AND
 INDICATE THE ENVIRONMENT IT IS TO BE USED IN. EG:
 PLENUM AIR CEILING.
  
 4) SHEET E-04
 MAKES NO SENSE. UNNESESSARY EXCEPT FOR THE SITE PLAN
 INDICATING THE PROPOSED LOCATION OF THE GENERATOR.
 ADDITIONAL INFORMATION REQUIRED. THE GENERATOR EXHAUST
 MUST BE AT LEAST 10' AWAY FROM ANY OPERABLE WINDOWS,
 DOORS OR MECHANICAL VENTS. REVISE TO VERIFY COMPLIANCE.
  
 5) SHEET E-05
 PROVIDE A MANUFACURER'S PRODUCT APPROVAL DATA SHEET FOR
 THE RECESSED BOX FOR ELECTRIC AND COAX. MUST BE
 APPROVED FOR USE WITH HIGH AND LOW VOLTAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By dhayes Date 2014-08-04 Time 10:33 Rev Time 0.00
Received By dhayes Date 2014-08-04 Time 10:33 Sent To  
Notes
2014-08-04 13:14:41DATE: 8/4/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 NOTE: CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 107.2.1 PLANS ARE TOO
 SMALL TO BE LEGIBLE. PROVIDE ENLARGED PLANS WITH
 ADDITIONAL DETAIL. ONLY ONE SET OF PLANS WAS SUBMITTED.
 TWO SETS ARE REQUIRED. ONE SET TO BE KEPT AS A FILE
 COPY AND ONE SET FOR THE APPLICANT. SEE NOTES BELOW FOR
 ADDITIONAL DETAIL REQUIRED:
  
 SHEET E-01. CLARIFICATION REQUIRED. FBC WPB AMENDMENTS.
 107.3.2
  
 1) NOTE 6 CALL OUT A 400AMP ENCLOSED CIRCUIT BREAKER
 BUT THE LINE DIAGRAM INDICATES VIA NOTE 8 THAT THE
 WIRING FROM THE LOAD SIDE IS UNDERSIZED. IF THIS IS
 INFACT A LOAD CENTER AND NOT AN ENCLOSED CIRCUIT
 BREAKER PLEASE REVISE PLANS AND NOTES TO REFLECT A CODE
 COMPLIANT INSTLATION.
 2) A PANEL SCHEDULE IS NEEDED FOR PANEL "A" NOTE 10
 REFERS TO "SEE SCHEDULE" SCHEDULE IS REQUIRED TO
 INDICATE CIRCUITS TO A/C CU, WALL MOUNTED A/C UNIT. AND
 UPS.
 3) A LOAD CALCULATION IS REQUIRED TO DETERMINE THE
 TOTAL CONNECTED LOAD AT THE SERVICE.
 4) PANEL A-1 APPEARS NEW BY WAY OF THE SOLID BLACK LINE
 IT IS DRAWN IN WITH. NO NOTES OR SCEDULES ASSOCIATED
 WITH PANEL "A-1" EXPLAIN.
 5) SFRTA WPB UPS01 SCHEDULE HAS CONFLICTING
 INFORMATION. BY IT'S TITLE IT IS A 120V 100AMP MAIN
 BREAKER PANEL. HOWEVER IF YOU LOOK AT THE BUSS
 ARRANGEMENT IT APPEARS TO BE FED BY A 3PHASE 400AMP
 MAIN BREAKER. THERE ARE CIRCUITS IN THIS PANEL THAT ARE
 IDENTIFIED TO FEED THE EQUIPMENT RACK P1. THESE ARE
 3PHASE RECEPTACLES ACCORDING TO THE INFORMATION ON
 SHEET E-03.
  
 SHEET E-02
  
 1) SEVERAL DETAILS ARE MISSING FROM THE "ONE LINE
 DIAGRAM". ADDITIONAL INFORMATION REQUIRED.
 1A. SYSTEM OPERATING VOLTAGE.
 1B. A FEEDER SCHEDULE INDICATING THE WIRE SIZES
 1C. A GROUNDING DETAIL.
  
 2) PROVIDE MANUFACTURER EQUIPMENT SPECIFICATIONS ON
 GENERATOR AND UPS
 3) PROVIDE SEPARATE PLANS AND SPECIFICATIONS ON
 CONCRETE SLAB
 4) PROVIDE A LOAD CALCULATION FOR THE TOTAL CONNECTED
 LOAD PROPOSED ON THE GENERATOR. SEE NEC 702.5 CAPACITY
 AND RATING BELOW:
 (A) AVAILABLE SHORT-CIRCUIT CURRENT. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 AVAILABLE SHORT-CIRCUIT CURRENT AT ITS TERMINALS.
 (B) SYSTEM CAPACITY. THE CALCULATIONS OF LOAD ON THE
 STANDBY SOURCE SHALL BE MADE IN ACCORDANCE WITH ARTICLE
 220 OR BY ANOTHER APPROVED METHOD.
 AUTOMATIC TRANSFER EQUIPMENT. WHERE AUTOMATIC TRANSFER
 EQUIPMENT IS USED, AN OPTIONAL STANDBY SYSTEM SHALL
 COMPLY WITH (2)(A) OR (2)(B).
 (A) FULL LOAD. THE STANDBY SOURCE SHALL BE CAPABLE OF
 SUPPLYING THE FULL LOAD THAT IS TRANSFERRED BY THE
 AUTOMATIC TRANSFER EQUIPMENT.
 (B) LOAD MANAGEMENT. WHERE A SYSTEM IS EMPLOYED THAT
 WILL AUTOMATICALLY MANAGE THE CONNECTED LOAD, THE
 STANDBY SOURCE SHALL HAVE A CAPACITY SUFFICIENT TO
 SUPPLY THE MAXIMUM LOAD THAT WILL BE CONNECTED BY THE
 LOAD MANAGEMENT SYSTEM.
  
 SHEET E-03
 1) A REVISED PANEL SCHEDULE IS REQUIRED TO IDENTIFY THE
 CIRCUITRY TO EACH OF THE NEW OUTLETS.
 2) IDENTIFY FM 200
 3) PROVIDE MANUFACTURER'S EQUIPMENT SPECIFICATIONS ON
 THE A/C WALL UNIT.
 4) PROVIDE EQUIPMENT AND MOUNTING DETAIL SPECIFICATIONS
 ON GPS ANTENNA.
 5) PROVIDE MANUFACTURERS EQUIPMENT SPECIFICATIONS ON
 THE UPS AND BATTERY CABINETS INCLUDING BATTERIES
 MOUNTING CONNECTION AND VENTLIATION DETAILS.
  
 FIRE SUPRESSION PLANS.
 1) MANUFACTURER EQUIPMENT SUBMITTALS REQUIRED FOR
 ENTIRE SYSTEM INCLUDING ALL COMPONENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-10-02 Cont ID  
Sent By PLEDUC Date 2014-10-02 Time   Rev Time 0.00
Received By pleduc Date 2014-10-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-09-16 Cont ID  
Sent By pleduc Date 2014-09-16 Time   Rev Time 0.00
Received By pleduc Date 2014-09-16 Time 09:27 Sent To B
Notes
2014-09-16 09:29:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE NOTE COMMENTS OF MECHANICAL AND ELECTRICAL.
  
 THIS PERMIT WAS PASSED BY FIRE PREVENTION PREVIOUSLY,
 FIRE PREVENTION WILL ADDRESS ON APPROVAL OF THE ABOVE
 DIVISIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-28 Cont ID  
Sent By dhayes Date 2014-08-04 Time 13:15 Rev Time 0.00
Received By scaldero Date 2014-07-28 Time 11:03 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-10-10 Cont ID  
Sent By dhayes Date 2014-10-10 Time 16:51 Rev Time 0.00
Received By dhayes Date 2014-10-06 Time 09:34 Sent To  
Notes
2014-10-07 09:35:26RE-SUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date 2014-09-30 Time   Rev Time 0.00
Received By rmcdouga Date 2014-09-25 Time 07:14 Sent To  
Notes
2014-09-26 07:16:01C08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2014-09-25 Time   Rev Time 0.00
Received By dhayes Date 2014-09-05 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-07-25 Time 13:44 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 13:43 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By HMOSER Date 2014-09-26 Time   Rev Time 0.00
Received By rbergsma Date   Time   Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By hmoser Date 2014-07-30 Time 18:04 Rev Time 0.00
Received By hmoser Date 2014-07-30 Time 17:44 Sent To E
Notes
2014-07-30 18:04:35PLAN DENIED
  
 1) PROVIDE MORE INFORMATION ON THE GENERATOR
 PER SECTION 107 FBC 2010
 2) PROVIDE EQUIPMENT SCHEDULE FOR THE
 AIR CONDITIONING ON THE PLANS.
 PER SECTION 107 FBC 2010
 3) PROVIDE DUCT SIZE FOR ALL NEW DUCT ON THE PLAN
 4) PROVIDE ENERGY CALCULATIONS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2014-07-25 Cont ID  
Sent By jwitmer Date 2014-07-25 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2014-07-25 Time 13:42 Sent To  
Notes
2014-07-25 13:43:26IN RAILWAY RIGHT OF WAY.