| 2014-07-31 07:40:13 | PLUMBING PLAN REVIEW |
| | PERMIT: 14070933 |
| | ADD: 326 FERN ST. |
| | CONT: STRATICON |
| | TEL: (561) 436-4733 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 31/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SEE BUILDING COMMENTS IN REGUARDS TO OCCUPANCY & |
| | OCCUPANT LOAD. THIS OCCUPANCY IS TO BE CONSIDERED A |
| | BUSINESS OCCUPANCY WITH A OCCUPANT LOAD OF 16 |
| | OCCUPANTS, 2010 FBC-B 304.1 & TABLE 1004.1.1. |
| | |
| | 2) SHEET A2.01 T IS MISSING A DRINKING FOUNTAIN PER |
| | SECTION 2010 FBC-P TABLE 403.1(2). |
| | |
| | 3) 2010 FBC-ACCESSIBILITY CODE 211.2 MINIMUM NUMBER. NO |
| | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 4) SHEET P0.1 THE SANITARY RISER SHOWS THE USE OF AN |
| | AIR ADMITTANCE VALVE WITH THE NEW SINK. PLEASE BE AWARE |
| | THE LIMITATION ON THE USE OF AIR ADMITTANCE VALVES. |
| | 2010 FBC-P WHERE PERMITTED. |
| | 917.3.1 LOCATION OF BRANCH. |
| | THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE |
| | DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| | 917.3.2 RELIEF VENT. |
| | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| | THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR |
| | EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE |
| | STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED |
| | TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL |
| | BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL |
| | BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |
| | |
| | 4) THE NEW SINK DOES NOT INDICATE WHAT THE USAGE OF |
| | THIS SINK IS FOR, IF IT IS TO BE USED FOR A BREAK ROOM |
| | SINK IT MUST MEET THE 2010 FL ACCESIBILITY |
| | REQUIREMENTS: 606.1 GENERAL. |
| | LAVATORIES AND SINKS SHALL COMPLY WITH 606.1-5. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |