| 2014-07-29 07:56:34 | PLUMBING PLAN REVIEW |
| | PERMIT:14070851 |
| | ADD: 1815 PALM BEACH LAKES BLVD (STAR BUCKS & PEI WEI) |
| | CONT:EMJ |
| | TEL: LEXIE 348-4805 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 29/2014 |
| | |
| | ACTION: PLUMBING PROVISO |
| | |
| | THIS GREASE INTERCEPTOR HAS BEEN DESIGNED UNDER THE |
| | 2010 FBC-PLUMBING CODE SECTION CONCRETE VAULT TYPE |
| | INTERCEPTORS (TABLE 1003.5.1). |
| | |
| | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| | REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE |
| | INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| | MUNICIPAL CODE OF ORDINANCES. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |