Plan Review Details - Permit 14070781
Plan Review Stops For Permit 14070781
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-11-03 Cont ID  
Sent By shill Date 2014-11-03 Time 17:45 Rev Time 0.00
Received By shill Date 2014-11-03 Time 17:45 Sent To  
Notes
2014-11-03 17:46:33SEPARATE PERMIT REQUIRED FOR ELECTRIC, PLUMBING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-10-22 Cont ID  
Sent By SHILL Date 2014-10-22 Time 16:56 Rev Time 0.00
Received By shill Date 2014-10-22 Time 16:56 Sent To  
Notes
2014-10-22 17:10:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS ARE FROM PREVIOUS LIST. A RESPONSE LETTER WAS
 PROVIDED BUT THE PLANS WERE NOT REVISED.
  
 PRIOR TO RESUBMITTAL, CONTRACTOR IS TO VERIFY THE
 FOLLOWING - ***DO NOT RESUBMIT UNLESS COMMENTS ARE
 ADDRESSED***
  
 VERIFY THAT DESIGN PROFESSIONALS HAVE INCLUDED FLOOD
 DESIGN CRITERIA FOR ALL PROPOSED IMPROVEMENTS WHICH ARE
 BELOW 7'.
  
 THIS INCLUDES THE GATE AND THE HARDSCAPE. THE SAME
 PLANS WERE SUBMITTED, RESPONSE LETTER STATES THAT "ALL
 NEW ELECTRICAL FIXTURES AND EQUIPMENT TO BE MOUNTED
 ABOVE 7' BFE. THE GATE AND HARDSCAPE ARE TO BE BELOW
 7'. THEY ARE TO RESIST FLOOD LOADS, AND PLANS NEED TO
 BE REVISED TO STATE SUCH.
  
 SEE PREVIOUS COMMENTS FOR ELEVATION CERTIFICATE. THE
 SAME ELEVATION CERTIFICATE WAS SUBMITTED. IT IS NOT AN
 ORIGINAL.
  
 FOR YOUR CONVENIENCE, THE PREVIOUS COMMENT LIST IS
 BELOW:
  
  
 1. PLEASE REVISE THE ELEVATION CERTIFICATE IN THE
 FOLLOWING FIELDS:
  
 B6, FIRM INDEX DATE, 3/1/1979
 B7, FIRM PANEL, 3/1/1979
 SECTION D, MARK BOX REGARDING LATITUDE/LONGITUDE
 SECTION D, RAISED IMPRESSION SEAL REQUIRED
 SECTION D, COMMENTS, INCLUDE SOURCE OF
 LATITUDE/LONGITUDE PER INSTRUCTIONS
  
 2. COMMENT FROM PREVIOUS LIST:
  
 BASED ON THE SPOT ELEVATIONS ON THE SURVEY, THE
 PROPOSED IMPROVEMENT IS BELOW THE BASE FLOOD ELEVATIONS
 AND ALL IMPROVEMENTS ARE TO BE DESIGNED TO RESIST FLOOD
 LOADS FBC 2010 RESIDENTIAL 301. FIXTURES AND EQUIPMENT
 ARE TO BE ABOVE BFE (7') OR TO BE FLOOD RESISTANT. GAS
 FIXTURES ARE PROPOSED BELOW BFE. PLEASE REVISE PLAN OR
 SUBMIT DATA WHICH DEMONSTRATES THAT PROPOSED FIXTURES
 WILL RESIST FLOOD LOADS.
  
 2ND REVIEW, I WAS UNABLE TO FIND ANYWHERE IN THE PLAN
 THAT THE DESIGNER INCLUDES FLOOD LOADS IN DESIGN
 CRITERIA. PLEASE REVISE PLAN. WHEN RESUBMITTING, SWAP
 OUT SHEETS WHICH HAVE CHANGED SO THERE ARE TWO COMPLETE
 COLLATED SETS FOR PERMIT ISSUANCE. A RESPONSE LETTER
 INDICATING HOW THIS ITEM HAS BEEN ADDRESSED WOULD BE
 HELPFUL. IT APPEARS THAT NEW SHEETS WERE SUBMITTED, NEW
 INFORMATION, BUT NOT CLEAR HOW THE REQUIREMENT THAT THE
 PROPOSED IMPROVEMENT RESIST FLOOD LOADS IF BELOW BASE
 FLOOD ELEVATION OF 7' HAS BEEN MET.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-25 Cont ID  
Sent By shill Date 2014-09-25 Time 17:49 Rev Time 0.00
Received By shill Date 2014-09-25 Time 17:49 Sent To  
Notes
2014-09-25 18:21:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLEASE REVISE THE ELEVATION CERTIFICATE IN THE
 FOLLOWING FIELDS:
  
 B6, FIRM INDEX DATE, 3/1/1979
 B7, FIRM PANEL, 3/1/1979
 SECTION D, MARK BOX REGARDING LATITUDE/LONGITUDE
 SECTION D, RAISED IMPRESSION SEAL REQUIRED
 SECTION D, COMMENTS, INCLUDE SOURCE OF
 LATITUDE/LONGITUDE PER INSTRUCTIONS
  
 2. COMMENT FROM PREVIOUS LIST:
  
 BASED ON THE SPOT ELEVATIONS ON THE SURVEY, THE
 PROPOSED IMPROVEMENT IS BELOW THE BASE FLOOD ELEVATIONS
 AND ALL IMPROVEMENTS ARE TO BE DESIGNED TO RESIST FLOOD
 LOADS FBC 2010 RESIDENTIAL 301. FIXTURES AND EQUIPMENT
 ARE TO BE ABOVE BFE (7') OR TO BE FLOOD RESISTANT. GAS
 FIXTURES ARE PROPOSED BELOW BFE. PLEASE REVISE PLAN OR
 SUBMIT DATA WHICH DEMONSTRATES THAT PROPOSED FIXTURES
 WILL RESIST FLOOD LOADS.
  
 2ND REVIEW, I WAS UNABLE TO FIND ANYWHERE IN THE PLAN
 THAT THE DESIGNER INCLUDES FLOOD LOADS IN DESIGN
 CRITERIA. PLEASE REVISE PLAN. WHEN RESUBMITTING, SWAP
 OUT SHEETS WHICH HAVE CHANGED SO THERE ARE TWO COMPLETE
 COLLATED SETS FOR PERMIT ISSUANCE. A RESPONSE LETTER
 INDICATING HOW THIS ITEM HAS BEEN ADDRESSED WOULD BE
 HELPFUL. IT APPEARS THAT NEW SHEETS WERE SUBMITTED, NEW
 INFORMATION, BUT NOT CLEAR HOW THE REQUIREMENT THAT THE
 PROPOSED IMPROVEMENT RESIST FLOOD LOADS IF BELOW BASE
 FLOOD ELEVATION OF 7' HAS BEEN MET.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-23 Cont ID  
Sent By shill Date 2014-07-23 Time 13:41 Rev Time 0.00
Received By shill Date 2014-07-23 Time 13:41 Sent To  
Notes
2014-07-23 13:54:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SURVEY STATES THIS IS IN A B ZONE, BUT IT APPEARS TO
 BE LOCATED IN AN A ZONE. PLEASE REVISE SURVEY TO SHOW
 LINE OF FLOOD ZONE A.
  
 2. THE PERMIT FOR THE ELEVATOR WAS ISSUED WITH PROVISO
 THAT AN ELEVATION CERTIFICATE BE SUBMITTED. THIS WAS A
 CONDITION OF ISSUANCE OF PERMIT. PLEASE SUBMIT AT THIS
 TIME.
  
 3. BASED ON THE SPOT ELEVATIONS ON THE SURVEY, THE
 PROPOSED IMPROVEMENT IS BELOW THE BASE FLOOD ELEVATIONS
 AND ALL IMPROVEMENTS ARE TO BE DESIGNED TO RESIST FLOOD
 LOADS FBC 2010 RESIDENTIAL 301. FIXTURES AND EQUIPMENT
 ARE TO BE ABOVE BFE (7') OR TO BE FLOOD RESISTANT. GAS
 FIXTURES ARE PROPOSED BELOW BFE. PLEASE REVISE PLAN OR
 SUBMIT DATA WHICH DEMONSTRATES THAT PROPOSED FIXTURES
 WILL RESIST FLOOD LOADS.
  

Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-10-22 Cont ID  
Sent By DHAYES Date 2014-10-22 Time 17:10 Rev Time 0.00
Received By shill Date 2014-10-22 Time 17:10 Sent To  
Notes
2014-10-22 17:30:21SEPARATE PERMIT REQUIRED
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-25 Cont ID  
Sent By dhayes Date 2014-09-25 Time 14:33 Rev Time 0.00
Received By dhayes Date 2014-09-25 Time 14:33 Sent To  
Notes
2014-09-25 15:32:17DATE: 9/25/2014
 PROJECT: PARMALEE RESIDENCE
 PERMIT#: 14070781
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO FBC- 107.3.5.3 MINIMUM PLAN REVIEW
 CRITERIA RESIDENTIAL; PROVIDE AN ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES, FIXTURE SCHEDULE,
 SYMBOLS KEY LEGEND, AND INDICATE ALL CONDUIT AND WIRE
 SIZSE FOR CIRCUITS ON SITE PLAN AND FLOOR PLAN
 RESPECTIVELY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-09-16 Cont ID  
Sent By fmittner Date 2014-09-16 Time 15:23 Rev Time 0.00
Received By fmittner Date 2014-09-16 Time 15:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-07-22 Cont ID  
Sent By fmittner Date 2014-07-22 Time 09:36 Rev Time 0.00
Received By fmittner Date 2014-07-22 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By Zoning Date   Time   Rev Time 0.00
Received By jwitmer Date 2014-12-10 Time 16:29 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2014-11-04 Cont ID  
Sent By shill Date   Time 17:46 Rev Time 0.00
Received By shill Date 2014-10-31 Time 16:01 Sent To  
Notes
2014-10-31 16:02:05TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-22 Cont ID  
Sent By shill Date 2014-10-22 Time 17:32 Rev Time 0.00
Received By shill Date 2014-10-17 Time 18:24 Sent To  
Notes
2014-10-17 18:24:46R27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-25 Cont ID  
Sent By shill Date 2014-09-25 Time 18:24 Rev Time 0.00
Received By shill Date 2014-09-03 Time 17:15 Sent To  
Notes
2014-09-03 17:17:40R27
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-23 Cont ID  
Sent By shill Date 2014-07-23 Time 13:54 Rev Time 0.00
Received By shill Date 2014-07-23 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2014-10-22 Cont ID  
Sent By TKLARGE Date 2014-10-22 Time 17:31 Rev Time 0.00
Received By shill Date 2014-10-22 Time 17:30 Sent To  
Notes
2014-10-22 17:31:27SEPARATE PERMIT REQUIRED
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-25 Cont ID  
Sent By tklarge Date 2014-09-25 Time 10:31 Rev Time 0.00
Received By tklarge Date 2014-09-25 Time 10:31 Sent To  
Notes
2014-09-25 10:41:52WPB ADMIN. AMEND. TO 2010 FBC 107.2.1
 1) THE PLANS REFER TO IRRIGATION AND DRAINAGE TO THE
 URNS. IRRIGATION SHALL BE UNDER A SEPARATE PERMIT. WHAT
 TYPE OF DRAINAGE WILL BE PROVIDED?
 2) SUBMIT PIPING PLANS FOR THE FOUNTAINS AND MANUF.
 SPECIFICATION SHEETS FOR THE FOUNTAIN EQUIPMENT.
 3) SUBMIT DETAILS ON THE FOUNTAINS.
 4) SHT. P-1 SHOWS THE FOUNTAINS DRAINING INTO THE
 SANITARY SYSTEM. THIS MAY BE NOT PERMITTED BY THE
 CITY'S UTILITY DEPT. SUBMIT A RISER DIAGRAM SHOWING THE
 CONNECTION TO THE FOUNTAINS.
 5) SUBMIT MANUF. SPECIFICATIONS ON THE BACKFLOW
 PREVENTER AND THE AUTOFILL.
 6) A SEPARATE PERMIT IS REQUIRED FOR THE GAS WORK TO BE
 DONE. SUBMIT MANUF. SPECS. FOR THE GAS COMPONENTS AND A
 GAS DRAWING AND OTHER APPLICABLE DOCUMENTS WHEN
 APPLYING FOR THE GAS PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By FMITTNER Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2014-09-16 Cont ID  
Sent By fmittner Date 2014-09-16 Time 15:24 Rev Time 0.00
Received By fmittner Date 2014-09-16 Time 15:24 Sent To  
Notes
2014-09-16 15:26:24NEWLY SUPPLIED DETAILS SHOW GATES IN EXCESS OF 6"-7"
 (CODE PERMITS 6' PLUS 10% FOR DECORATIVE ELEMENTS).
 ALSO GATE LOCATION ON DETAILS IS NOT INDICATED HOW IT
 CORRESPONDS TO SITE PLAN. QUESTIONS CONTACT FRIEDERIKE
 MITTNER 822-1457.
  
 PUT BACK IN BOX R 27

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-22 Cont ID  
Sent By fmittner Date 2014-07-22 Time 09:36 Rev Time 0.00
Received By fmittner Date 2014-07-22 Time 09:36 Sent To  
Notes
2014-07-22 09:37:384' MAX HEIGHT IN FIRST 25' FROM FLAGLER DRIVE.
 DECORATIVE ELEMENTS NOT TO EXCEED 10% OF MAX HEIGHT
 INCLUDING URNS.