Plan Review Details - Permit 14070773
Plan Review Stops For Permit 14070773
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-05 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2014-08-05 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-18 Cont ID  
Sent By dhayes Date 2014-09-18 Time 13:21 Rev Time 0.00
Received By dhayes Date 2014-09-18 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-28 Cont ID  
Sent By dhayes Date 2014-08-28 Time 11:39 Rev Time 0.00
Received By dhayes Date 2014-08-28 Time 09:50 Sent To  
Notes
2014-08-28 10:58:24DATE: 8/28/2014
 PROJECT: MORSE LIFE
 PERMIT#: DATE: 8/28/2014
 PROJECT: MORSE LIFE
 PERMIT#: 14070773
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE CIRCUIT FEEDING T-13 TO PANEL L-22 IS OVERSIZED.
 REVISE THE OCPD AND FEEDER ACCORDINGLY.
  
 2) PROVIDE THE PANEL SCHEDULES WITH LOAD CALCULATIONS
 FOR PANEL MDP PANEL H7 AND PANEL L22 IN ORDER TO VERIFY
 THE LOADS, CIRCUITS, OCPD'S FEEDING THE PANELS AFFECTED
 IN THIS RENNOVATION PROJECT.
  
 3) INDICATE THE LOCATIONS OF THE PANELS AFFECTED IN
 THIS RENNOVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-30 Cont ID  
Sent By wjolin Date 2014-07-30 Time 13:15 Rev Time 0.00
Received By wjolin Date 2014-07-30 Time 11:31 Sent To  
Notes
2014-07-30 11:49:314847 FRED GLADSTONE DRIVE
 PERMIT #14070773
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A3.1: INDICATE THE SMOKE/FLAME SPREAD RATING OF
 THE ACOUSTICAL WALL PANELS. INTERIOR WALL AND CEILING
 FINISH MATERIALS SHALL BE CLASS A OR IN GENERAL
 ASSEMBLY AREAS HAVING AN OCCUPANT LOAD OF MORE THAN 300
 PERSONS ANS SHALL BE CLASS A, B OR C IN ASSEMBLY AREAS
 HAVING OCCUPANT LOADS OF 300 OR FEWER.
  
 SHEET A4: VERIFY EXIT/EXIT ACCESS DOORS EQUIPPED WITH
 PANIC HARDWARE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-19 Cont ID  
Sent By cpuell Date 2014-09-18 Time 13:30 Rev Time 0.00
Received By skennedy Date 2014-09-09 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-28 Cont ID  
Sent By cpuell Date 2014-08-28 Time 12:27 Rev Time 0.00
Received By cpuell Date 2014-07-24 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-08-12 Cont ID  
Sent By hmoser Date 2014-08-12 Time 11:25 Rev Time 0.00
Received By hmoser Date 2014-08-12 Time 11:04 Sent To  
Notes
2014-08-12 11:25:32NO MECHANICAL PLANS SUBMITTED AT THIS TIME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-19 Cont ID  
Sent By skennedy Date 2014-09-19 Time 08:14 Rev Time 0.00
Received By skennedy Date 2014-09-18 Time 13:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-18 Cont ID  
Sent By eschneid Date 2014-08-18 Time 16:38 Rev Time 0.50
Received By eschneid Date 2014-08-18 Time 16:38 Sent To  
Notes
2014-07-25 10:36:507/25/14