Plan Review Details - Permit 14070641
Plan Review Stops For Permit 14070641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By dhayes Date 2014-07-26 Time 15:29 Rev Time 0.00
Received By dhayes Date 2014-07-26 Time 15:29 Sent To  
Notes
2014-07-26 15:43:45DATE: 7/23/2014
 PROJECT: SPORTS AUTHORITY
 PERMIT#: 14070641
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR GENERATOR, FIRE ALARM,
 SECURITY, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING,
 AUDIO/VIDEO, AND SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-23 Cont ID  
Sent By dhayes Date 2014-07-23 Time 12:41 Rev Time 0.00
Received By dhayes Date 2014-07-23 Time 12:41 Sent To  
Notes
2014-07-23 12:45:13DATE: 7/23/2014
 PROJECT: SPORTS AUTHORITY
 PERMIT#: 14070641
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1
  
 2) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 PLANS SUBMITTED ARE NOT LEGIBLE. PROVIDE LEGIBLE PLANS.
 FBC-B 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-26 Cont ID  
Sent By dhayes Date 2014-07-26 Time 15:29 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 17:29 Sent To  
Notes
2014-07-25 17:29:44RE-SUBMITTAL SENT TO DAVID'S DESK FOR ELECTRICAL
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-23 Cont ID  
Sent By dhayes Date 2014-07-23 Time 12:41 Rev Time 0.00
Received By dhayes Date   Time   Sent To E
Notes
***NONE***