Plan Review Details - Permit 14070599
Plan Review Stops For Permit 14070599
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-09 Cont ID  
Sent By jwitmer Date 2014-12-09 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2014-12-09 Time 16:09 Sent To  
Notes
2014-12-09 16:13:20BUILDING PROVISO:
 2010 FBC-B 1008.1.9.3 LOCKS AND LATCHES.
 APPROVED LOCKS AND LATCHES SHALL BE PERMITTED TO
 PREVENT OPERATION OF DOORS WHERE ANY OF THE FOLLOWING
 EXISTS:
 2. N BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-17 Cont ID  
Sent By jwitmer Date 2014-10-17 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2014-10-17 Time 11:12 Sent To  
Notes
2014-10-17 11:11:39BUILDING PLAN REVIEW
 REVISION: 14070599
 PERMIT: 13051012
 ADD: 290 COURTNEY LAKES
 CONT:KAST
 TEL: (561) 856-6655
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT 17/2014
 ACTION: DENIED
  
 1) MASTER # 13060771 REVSION 6 - PANIC HARDWARE REMOVED
 FROM CLUBHOUSE ENTRY DOOR. PLEASE SEE CODE SECTION 2010
 FBC-B 1008.1.9.3 & EXCEPTION # 2.
 1A) IN THE BEGINNING OF EXCEPTION # 2. THE ONLY DOORS
 THAT THIS EXCEPTION APPLIES TO IS THE MAIN EXTERIOR
 DOORS.
  
 2010 FBC-B 1008.1.9.3 & EXCEPTION # 2. IN BUILDINGS IN
 OCCUPANCY GROUP A HAVING AN OCCUPANT LOAD OF 300 OR
 LESS, GROUPS B, F, M AND S, AND IN PLACES OF RELIGIOUS
 WORSHIP, THE MAIN EXTERIOR DOOR OR DOORS ARE PERMITTED
 TO BE EQUIPPED WITH KEY-OPERATED LOCKING DEVICES FROM
 THE EGRESS SIDE PROVIDED:
  
 THE DESIGNER OF RECORD HAS NOT DESIGNATED WHICH DOOR OR
 SET OF DOORS IS TO BE CONSIDERED THE MAIN ENTRY WHERE
 THE PANIC HARDWARE CAN BE ELIMINATED. ALL OTHER
 REQUIRED EXIT DOORS WILL REQUIRE TO HAVE PANIC HARDWARE
 AS REQUIRED IN SECTION 1008.1.10. SHEET A0.05 AND THE
 DOOR SCHEDULE WILL NEED TO BE UPDATED TO REFLECT THE
 CHANGES IN HARDWARE.
  
 1B) IN SECTION: 1008.19.3 EXCEPTION # 2: SECTION 2.2. A
 READILY VISIBLE DURABLE SIGN IS POSTED ON THE EGRESS
 SIDE ON OR ADJACENT TO THE DOOR STATING: THIS DOOR TO
 REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE SIGN
 SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND;
 THIS PART OF THE REQUIRED CODE REQUIREMENT HAS NOT BEEN
 MENTION NOR DISPLAYED AS PART OF THE EXCEPTION.
  
 1C) THE MANUFACTURERS SPEC ON THE LOCK INDICATES THAT
 IT IS NOT A LOCKING TYPE AND WILL MEET THE REQUIREMENTS
 OF 2.3.
  
 PLEASE NOTE THE 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 102.4
 REFERENCED CODES AND STANDARDS. WHERE DIFFERENCES OCCUR
 BETWEEN PROVISIONS OF THIS CODE MOST STRIGENT CODE
 SHALL APPLY. THE FIRE CODES MAY HAVE BE THE MORE
 STRIGENT OF THE (2) CODES AND THEN GOVERN.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 12:15 Sent To  
Notes
2014-10-02 12:16:23THIS CODE SECTION IS NOT ELIMINATING THE REQUIREMENT
 FOR PANIC HARDWARE, IT IS ALLOWING FOR A LOCKING
 DEVICE.
  
  
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
 EXCEPTIONS:1. A MAIN EXIT OF A GROUP A OCCUPANCY IN
 COMPLIANCE WITH SECTION 1008.1.9.3, ITEM 2.
  
 1008.1.9.3 LOCKS AND LATCHES.
 APPROVED LOCKS AND LATCHES SHALL BE PERMITTED TO
 PREVENT OPERATION OF DOORS WHERE ANY OF THE FOLLOWING
 EXISTS:
  
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-01-20 Cont ID  
Sent By wjolin Date 2015-01-20 Time 08:13 Rev Time 0.00
Received By wjolin Date 2015-01-20 Time 08:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-12-12 Cont ID  
Sent By wjolin Date 2014-12-12 Time 17:06 Rev Time 0.00
Received By wjolin Date 2014-12-12 Time 16:48 Sent To  
Notes
2014-12-12 17:06:40290 COURTNEY LAKES CIRCLE
 TRACKING #14070599
 PERMIT #13060771
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE DOOR SCHEDULE OF SHEET A7.01 INDICATES THAT DOORS
 #7-101 ARE EQUIPPED WITH PANIC HARDWARE; HOWEVER, SHEET
 A0.05 INDICATES THE DOORS ARE TO BE EQUIPPED WITH AN
 ADAMSRITE LOCK INDICATOR FOR KEY OPERATED DOOR LOCKS. A
 PREVIOUSLY ISSUED PERMIT INDICATES MAGNETIC LOCKS ON
 THESE DOORS AS WELL.
  
 REPEAT COMMENT:
 FIRE INSPECTOR IN THE FIELD HAS INDICATED THAT ALL
 CLUBHOUSE EXIT DOORS ARE ALREADY EQUIPPED WITH MAGNETIC
 LOCKING DEVICES (PERMIT #14090532 SHEET LV1.01). DESIGN
 TEAM AND CONTRACTOR(S) NEED TO START COMMUNICATING AND
 COORDINATING WHAT DOOR HARDWARE IS TO BE INSTALLED ON
 ALL/EACH EXIT DOOR. IT IS VERY UNCLEAR WHAT
 LOCKS/LATCHES/HARDWARE ARE INTENDED (MAGNETIC LOCKS,
 KEY-OPERATED LOCKS, PANIC HARDWARE, ETC.).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-10-21 Cont ID  
Sent By wjolin Date 2014-10-21 Time 14:37 Rev Time 0.00
Received By wjolin Date 2014-10-21 Time 14:09 Sent To  
Notes
2014-10-21 14:37:22290 COURTNEY LAKES CIRCLE
 TRACKING #14070599
 PERMIT #13060771
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE INSPECTOR IN THE FIELD HAS INDICATED THAT ALL
 CLUBHOUSE EXIT DOORS ARE ALREADY EQUIPPED WITH MAGNETIC
 LOCKING DEVICES (PERMIT #14090532?). DESIGN TEAM AND
 CONTRACTOR(S) NEED TO START COMMUNICATING AND
 COORDINATING WHAT DOOR HARDWARE IS TO BE INSTALLED ON
 ALL/EACH EXIT DOOR. IT IS VERY UNCLEAR WHAT
 LOCKS/LATCHES/HARDWARE ARE INTENDED (MAGNETIC LOCKS,
 KEY-OPERATED LOCKS, PANIC HARDWARE, ETC.).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-23 Cont ID  
Sent By wjolin Date 2014-09-23 Time 15:02 Rev Time 0.00
Received By wjolin Date 2014-09-23 Time 14:22 Sent To  
Notes
2014-09-23 14:45:35290 COURTNEY LAKES CIRCLE
 TRACKING #14070599
 PERMIT #13060771
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE REMOVING PANIC HARDWARE FROM THE
 MAIN ENTRANCE DOUBLE DOORS; HOWEVER, THE OCCUPANT LOAD
 UTILIZING THESE DOORS APPEARS TO BE GREATER THAN 50
 PERSONS. THE TWO CONFERENCE ROOMS AND THE BREAK ROOM
 SHOULD BE CALCULATED USING AN OCCUPANT LOAD FACTOR OF
 15 SQ.FT. PER PERSON AS THESE ARE ASSEMBLY USE SPACES.
 THESE SPACES CAN BE CONSIDERED PART OF THE BUSINESS
 OCCUPANCY BECAUSE THEIR INDIVIDUAL USES ARE LESS THAN
 50 PERSONS BUT THEIR OCCUPANT LOAD FACTORS WOULD STILL
 BE 15 SQ.FT. PER PERSON. ADDING THESE INCREASED
 OCCUPANCY LOADS TO THE 30 OCCUPANTS FROM THE CLUB ROOM
 RESULTS IN AN OCCUPANT LOAD GREATER THAN 50 PERSONS AND
 WOULD REQUIRE PANIC HARDWARE ON THE MAIN ENTRY DOOR(S).
  
 THE SECONDARY EXIT FROM THE CLUB ROOM IS NOW SHOWN
 EXITING THROUGH THE PARTY/CAFE ROOM. THIS WILL RESULT
 IN A POSSIBLE OCCUPANT LOAD OF GREATER THAN 50 PERSONS
 (25+30) UTILIZING THE EXIT DOOR IN THE PARTY/CAFE ROOM
 AND THERE DOES NOT APPEAR TO BE PANIC HARDWARE ON THIS
 DOOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2015-01-30 Cont ID  
Sent By skennedy Date 2015-01-30 Time 10:47 Rev Time 0.00
Received By skennedy Date 2015-01-30 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-01-28 Cont ID  
Sent By cpuell Date 2015-01-28 Time 15:05 Rev Time 0.00
Received By cpuell Date 2014-12-19 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-15 Cont ID  
Sent By cpuell Date 2014-12-15 Time 16:07 Rev Time 0.00
Received By cpuell Date 2014-12-04 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-03 Cont ID  
Sent By cpuell Date 2014-11-03 Time 09:44 Rev Time 0.00
Received By cpuell Date 2014-10-07 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2014-09-10 Time 14:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***