| 2014-08-06 08:19:11 | DATE: 8/6/2014 |
| | PROJECT: 1701 S. FLAGLER DR. #307 |
| | PERMIT#: 14070541 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO. |
| | |
| | 1) 250.86 OTHER CONDUCTOR ENCLOSURES AND RACEWAYS. |
| | EXCEPT AS PERMITTED BY 250.112(I), METAL ENCLOSURES AND |
| | RACEWAYS FOR OTHER THAN SERVICE CONDUCTORS SHALL BE |
| | CONNECTED TO THE EQUIPMENT GROUNDING CONDUCTOR. IF NO |
| | EQUIPMENT GROUND IS AVAILABLE OR PROPOSED TO BE |
| | INSTALLED, THEN PLEASE INDICATE COMPLIANCE WITH THE |
| | FOLLOWING ARTICLE FROM THE 2008 EDITION OF THE NEC |
| | 250.96 SEE BELOW: |
| | |
| | 2) NEC 250.96 BONDING OTHER ENCLOSURES. (A) GENERAL. |
| | METAL RACEWAYS, CABLE TRAYS, CABLE ARMOR, CABLE SHEATH, |
| | ENCLOSURES, FRAMES, FITTINGS, AND OTHER METAL |
| | NON?CURRENT-CARRYING PARTS THAT ARE TO SERVE AS |
| | GROUNDING CONDUCTORS, WITH OR WITHOUT THE USE OF |
| | SUPPLEMENTARY EQUIPMENT GROUNDING CONDUCTORS, SHALL BE |
| | BONDED WHERE NECESSARY TO ENSURE ELECTRICAL CONTINUITY |
| | AND THE CAPACITY TO CONDUCT SAFELY ANY FAULT CURRENT |
| | LIKELY TO BE IMPOSED ON THEM. ANY NONCONDUCTIVE PAINT, |
| | ENAMEL, OR SIMILAR COATING SHALL BE REMOVED AT THREADS, |
| | CONTACT POINTS, AND CONTACT SURFACES OR BE CONNECTED BY |
| | MEANS OF FITTINGS DESIGNED SO AS TO MAKE SUCH REMOVAL |
| | UNNECESSARY. |
| | |
| | 3) THE PLAN INDICATES REPLACEMENT OF AN FPE LOADCENTER |
| | BUT DOESN'T INDICATE WHAT IT WILL BE REPLACED WITH. |
| | INDICATE COMPLIANCE WITH THE FOLLOWING: |
| | 408.36 OVERCURRENT PROTECTION. IN ADDITION TO THE |
| | REQUIREMENT OF 408.30, A PANELBOARD SHALL BE PROTECTED |
| | BY AN OVERCURRENT PROTECTIVE DEVICE HAVING A RATING NOT |
| | GREATER THAN THAT OF THE PANELBOARD. THIS OVERCURRENT |
| | PROTECTIVE DEVICE SHALL BE LOCATED WITHIN OR AT ANY |
| | POINT ON THE SUPPLY SIDE OF THE PANELBOARD. INDICATE |
| | THE RATING TYPE AND STYLE OF THE NEW PANELBOARD. |
| | |
| | 4) THE FBC-RESIDENTIAL STATES THE FOLLOWING: WHEN |
| | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314.3 AND |
| | 314.3.1 PLEASE INDICATE COMPLIANCE. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |