| 2014-08-01 13:42:08 | DATE: 7/24/2014 |
| | PROJECT: WASHINGTON TOWER CONDO II |
| | PERMIT#: 14070532 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE, PLUS ADDITIONAL COMMENTS. |
| | |
| | 1) PROVIDE A CUT SHEET ON THE FIXTURE. WHAT ELSE IS |
| | AFFECTED BY THE REMOVAL OF THE DRYWALL? REQUIRED SMOKE |
| | DETECTOR FOR ELEVATOR CAPTURE AT THE LOBBY? LIGHTING |
| | CONTROL? ADDITIONAL INFORMATION REQUIRED. FBC |
| | 107.3.2.1. CUT SHEET ON FIXTURE DOESN'T INDICATE |
| | COMPLIANCE WITH NEC 110.3 UL LISTING AND LABELING. |
| | |
| | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. |
| | PLANS NOT SIGNED. |
| | |
| | 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. FBC 107.2.1. PROVIDE |
| | SUFFICIENT DETAIL ON THE OVERAL SCOPE OF WORK. |
| | |
| | 4) PROVIDE CUT SHEET FROM THE MANUFACTURER ON THE "NEW" |
| | FLOOR BOX. IS THE FLOOR TO BE CORE DRILLED? WHAT FLOOR |
| | IS THIS ON? ALL FLOORS? ADDITIONAL INFORMATION |
| | REQUIRED. INDICATE A DETAIL ON THE INSTALLATION OF THE |
| | CONDUIT FO THE NEW FLOOR BOX. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |