Plan Review Details - Permit 14070493
Plan Review Stops For Permit 14070493
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-06 Cont ID  
Sent By rmcdouga Date 2015-05-06 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2015-05-06 Time 16:32 Sent To  
Notes
2015-05-06 18:09:48APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS AS REQUIRED BY DCA RULE 9N-3.
 2) SUBMIT A REVISED STORM PANEL INSTALLATION SCHEDULE
 FOR THE GLAZED DOOR. THE PANELS (NOA NO. 14-0221.04)
 CAN NOT BE MOUNTED ON THE STEEL DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2015-03-10 Time 16:08 Sent To  
Notes
2015-03-10 18:39:46PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE NON
 IMPACT RATED SINGLE HUNG WINDOWS HAS DESIGN PRESSURES
 OF =/- 50 PSF. WINDOW #1 AND #3 REQUIRE HIGHER DESIGN
 PRESSURES(-65.0 AND -51.2 PSF) BASED ON THE REQUIRED
 PRESSURES IN THE SCHEDULE ON SHEET 3.1.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD AS
 REQUIRED BY DCA RULE 9N-3 AND FBC 107.3.4.1 FOR DOOR #2
 (WITH GLASS INSERT) THAT IS LISTED IN THE DOOR SCHEDULE
 ON SHEET 3.1
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD AS
 REQUIRED BY DCA RULE 9N-3 AND FBC 107.3.4.1 FOR THE
 FIXED GLASS PICTURE WINDOW AND THE STRUCTURAL MULLIONS.
  
 4) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-14 Cont ID  
Sent By rmcdouga Date 2014-08-14 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2014-08-14 Time 18:48 Sent To  
Notes
2014-08-14 19:06:432010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS
 107.2.1
  
 2) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 NEW EXTERIOR DOORS AND WINDOWS AS REQUIRED BY DCA RULE
 9N-3.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 4) SHOW COMPLIANCE WITH FBC R301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS.
  
 5) SECTION DETAILS ON SHEET 3.2 NEED CORRECTIONS. ITEM
 13 ON DETAIL 6 IS A HEADER NOT A 2 X 6 BUCK. THE WALL
 FRAMING IS SPECIFIED AS 2 X 4. PLEASE REVIEW DETAIL 2
 AND 6 ON SHEET 3.2 FOR MISTAKES. CITY AMENDMENTS
 107.2.1
  
 6) THE ELECTRICAL NOTES ON THE UN-NUMBERED SHEET
 REFERENCES THE WRONG NFPA CODE EDITIONS. THE 2010 FBC
 REFERENCES NFPA-70 2008, NFPA-72 2007 AND NFPA-101
 2006. PLEASE CORRECT.
  
 7) ON SHEET 3.1 THE WINDLOAD PRESSURES IN THE SCHEDULE
 ARE FOR AN EFFECTIVE WIND AREA OF 10 SQFT AND THE
 SCHEDULE HAS 50 SQFT. THE CORNER DISTANCE "A" IS 4 FEET
 IN ALL CASES AND 3 FEET IS SPECIFIED ON THE SCHEDULE.
 PLEASE CORRECT. FBCR301.2.1 AND FIGURE R301.2(7)
  
 8) THE PRESSURES IN THE WINDOW AND DOOR SCHEDULE ARE
 HIGHER THAN THE WORST CASE PRESSURES THAT ARE LISTED IN
 THE WINDLOAD SCHEDULE. PLEASE CORRECT. FBCR301.2.1 AND
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2015-03-10 Time 18:43 Sent To  
Notes
2015-03-10 18:44:20RED-LINED PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-15 Cont ID  
Sent By rmcdouga Date 2014-08-15 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2014-08-15 Time 18:25 Sent To  
Notes
2014-08-15 18:25:51RED-LINED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-06 Cont ID  
Sent By rmcdouga Date 2015-05-06 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2015-04-24 Time   Sent To  
Notes
2015-04-25 09:41:48SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-10 Cont ID  
Sent By jwitmer Date 2015-03-10 Time 18:39 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2015-02-24 17:26:05SENT TO R. MCDOUGALS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By rmcdouga Date 2014-08-15 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2014-07-15 Time 12:10 Sent To  
Notes
2014-07-16 17:45:37R10
  
2014-07-15 12:11:32ROUTED TO BUILDING $5000 & UNDER

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By sgraham Date 2014-07-17 Time 11:07 Rev Time 0.00
Received By sgraham Date 2014-07-17 Time 11:07 Sent To  
Notes
***NONE***