Plan Review Details - Permit 14070487
Plan Review Stops For Permit 14070487
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-30 Cont ID  
Sent By dhayes Date 2014-07-30 Time 13:11 Rev Time 0.00
Received By dhayes Date 2014-07-30 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-22 Cont ID  
Sent By dhayes Date 2014-07-22 Time 13:10 Rev Time 0.00
Received By dhayes Date 2014-07-22 Time 12:06 Sent To  
Notes
2014-07-22 13:10:42DATE: 7/22/2014
 PROJECT: SPORTS AUTHORITY
 PERMIT#: 14070487
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FBC WPB AMENDMENTS. SECTION 109.3
 PROVIDE SUPPORTING DOCUMENTATION OF PERMIT COST
 VALUATION. COST ON APPLICATION TO INCLUDE ALL LABOR,
 MATERALS, OVERHEAD AND PROFFIT
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. THE
 PLANS SUBMITTED NEED TO BE SIGNED BY THE QUALIFYER WHO
 IS THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 3) SEPARATE PERMIT APPLICATION ACCOMPANIED BY SHOP
 DRAWINGS ARE REQUIRED FOR ADDITIONAL SCOPE OF WORK SUCH
 AS BUT NOT LIMITED TO, FIRE ALARM, SECURITY, NETWORK,
 AUDIO/VIDEO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-30 Cont ID  
Sent By dhayes Date 2014-07-30 Time 13:11 Rev Time 0.00
Received By dhayes Date 2014-07-29 Time 18:26 Sent To  
Notes
2014-07-29 18:26:13TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-22 Cont ID  
Sent By dhayes Date 2014-07-22 Time 13:11 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2014-07-15 10:26:00ROUTED TO ELECTRIC $5000 & UNDER


Account Summary | Usage Policy | Privacy Policy