Plan Review Details - Permit 14070394
Plan Review Stops For Permit 14070394
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-14 Cont ID  
Sent By jgomez Date 2014-10-14 Time 17:11 Rev Time 0.00
Received By jgomez Date 2014-10-14 Time 17:11 Sent To  
Notes
2014-10-14 17:14:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- SHEET #1:
 A) DESIGN CRITERIA: ENGINEER SPECIFIES "WIND SPEED =
 170 MPH NOMINAL 3 SEC GUST". DOOR AND WINDOW PRESSURES
 ON SHEET 4 OF 7 DON'T CORRESPOND TO 170 MPH NOMINAL
 WIND SPEED. REVISE AS REQUIRED.
 B) ALTERATION LEVEL SHOWN UNDER "BUILDING TYPE" DOESN'T
 MATCH ALTERATION LEVEL SHOWN UNDER DESIGN CRITERIA.
 REVISE AS REQUIRED.
  
 2- SHEET #5:
 A) REVISE TREAD DIMENSION OF NEW STAIR DETAIL. SEE SEC.
 R311.7.4.2.
 B) SLIDING GLASS DOORS WERE CHANGED TO FRENCH DOORS.
 NEED TO PROVIDE A LANDING IF MORE THAN 2 RISERS. SEC.
 R311.3. REVISE PLANS AS REQUIRED.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE
 9N-3) FOR:
 A) ARCHED ENTRY DOOR AS SHOWN ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-14 Cont ID  
Sent By jgomez Date 2014-08-14 Time 11:13 Rev Time 0.00
Received By jgomez Date 2014-08-14 Time 11:08 Sent To  
Notes
2014-08-14 11:18:34RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION:
 A) PLANS SUBMITTED SHOW GAS WATER HEATER NOT ELECTRIC.
 REVISE AS REQUIRED.
  
 B) THERE IS A CONFLICT ON INFORMATION GIVEN ON ITEM #8,
 ITEM #10 AND CEILING INFORMATION GIVEN ON SHEET 3 OF 5.
 NOTE: RAISED FLOOR IS NOT THE SAME AS UNDER ATTIC.
 CHECK R-INSULATION VALUE GIVEN FOR EACH AREA AND CHECK
 SQUARE FOOTAGE THAT PERTAINS TO EACH AREA AND REVISE AS
 REQUIRED.
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION ON SHEET 3 OF
 5. SEE PLANS AND REVISE AS REQUIRED.
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME AND
 JURISDICTION.
  
 E) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERV ATION.
  
 2- SHEET #1:
 A) ENGINEER OF RECORD TO REVISE TYPE OF ALTERATION.
 ACCORDING TO SCOPE OF WORK SHOWN ON PLANS THIS IS
 ALTERATION LEVEL 3, NOT LEVEL 2. SEC. 405.1 OF 2010
 FBC-EXISTING BUILDING.
  
 B) ENGINEER TO CLARIFY WHY THE DESIGN CRITERIA
 SPECIFIES "PART. OPEN STRUCTURE". SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
  
 C) ENGINEER TO CLARIFY IF THE WIND SPEED SPECIFIED IN
 THE DESIGN CRITERIA IS THE ULTIMATE OR NOMINAL WIND
 SPEED. SEC. R301.2.1.3 OF 2010 FBC-RESIDENTIAL.
  
 3- SHEET #5:
 A) NEW STAIR DETAIL. PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE RISER AND TREAD DIMENSIONS.
 SEC. R311.7.4 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE CONNECTIONS
 AT THE ENDS OF EACH NEW 3-2X10 BEAMS SHOWN ON PLANS AND
 NEW 3-2X4 STUDS. SEC. R301 OF 2010 FBC.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS.
  
 B) ENTRY DOOR.
  
 C) UTILITY ROOM EXTERIOR DOORS.
  
 D) SLIDING GLASS DOORS
  
 E) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLASS. ***NOTE: PROVIDE ALSO A
 COMPLETE SHUTTERS INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. ***NOTE: THERE ARE SOME CONNECTORS SHOWING
 THE FLORIDA PRODUCT APPROVAL # NEXT TO THE SPECIFIED
 CONNECTOR. THIS MAY BE DONE ALSO TO THE OTHER
 CONNECTORS THAT ARE MISSING THE FLORIDA PRODUCT
 APPROVAL NUMBER. OTHERWISE, PROVIDE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE CONNECTOR.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 6- SPECIFY ON PLANS "TYPE" AND "SIZE" OF EXISTING
 BEDROOM WINDOWS TO BE REPLACED TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 7- ENGINEER OF RECORD TO COORDINATE INFORMATION ON
 PLANS WITH THE INFORMATION SHOWN ON THE REVISED ENERGY
 CALCULATIONS (SEE ITEM #1 ABOVE). FOR EXAMPLE,
 COORDINATE CEILING, WALLS, CRAWL SPACE, RAISED FLOOR
 R-VALUE INSULATION, ETC. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 8- ENGINEER TO CLEARLY LABEL ALL FLOOR PLANS AND
 ELEVATIONS. CLEARLY IDENTIFY WHAT'S EXISTING AND WHAT'S
 PROPOSED. FOR EXAMPLE ON SHEET #4 FLOOR PLANS ARE NOT
 CLEAR. FLOOR PLANS ARE LABELED AS EXIST. FIRST AND
 EXIST. SECOND FLOOR PLAN. BUT, THEY ARE SHOWING THE
 PROPOSED WORK ALSO. THERE IS NOT A WALL LEGEND THAT
 IDENTIFIES, EXISTING WALLS AND PROPOSED WALLS. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 ***NOTES:
 * PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ** PLEASE REPLACE ANY REVISED DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT.
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-15 Cont ID  
Sent By dhayes Date 2014-10-15 Time 15:13 Rev Time 0.00
Received By dhayes Date 2014-10-15 Time 15:13 Sent To  
Notes
2014-10-14 19:02:04NEW PLANS SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 11:28 Rev Time 0.00
Received By dhayes Date 2014-09-08 Time 10:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2014-10-14 Cont ID  
Sent By jgomez Date 2014-10-14 Time 18:59 Rev Time 0.00
Received By jgomez Date 2014-10-14 Time 18:59 Sent To  
Notes
2014-10-14 19:01:22NO NEW GAS WORK SHOWN ON PLANS. GAS APPLIANCES CHANGED
 TO ELECTRIC. NEED GAS PERMIT TO CAP EXISTING GAS LINES.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-14 Cont ID  
Sent By jgomez Date 2014-08-14 Time 15:47 Rev Time 0.00
Received By jgomez Date 2014-08-14 Time 15:47 Sent To  
Notes
2014-08-14 15:52:45RESIDENTIAL (R3) ALTERATION, GAS REVIEW COMMENTS.
 1- PROVIDE COMPLETE INFORMATION FOR GAS REVIEW AS
 REQUIRED BY SEC. 107.3.5.3(12) OF CITY AMENDMENTS TO
 FBC. ***NOTE: SEE CITY REQUIREMENTS FOR ALL GAS
 PERMITS. VISIT THE CITY OF WEST PALM BEACH WEBSITE OR
 REQUEST A COPY OF THE REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By fmittner Date 2014-10-10 Time 12:19 Rev Time 0.00
Received By fmittner Date 2014-10-08 Time 15:49 Sent To B
Notes
2014-10-10 12:31:27SPOKE TO APPLICANT AND CLARRIFIED THAT FRONT DOOR WILL
 HAVE ARCHED TOP. PRODUCT SUBMITTALS NOT SUBMITTED FOR
 THIS YET. WINDOWS WILL BE WHITE FRAMES, CLEAR GLASS,
 EXACT OPENINGS AS EXISTING (NO SIZE CHANGES EXCEPT FOR
 FRENCH DOOR LOCATION). QUESTIONS CONTACT FRIEDERIKE
 MITTNER AT 822-1457.
2014-10-06 17:45:45NEW DRAWINGS AND PRODUCT APPROVALS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 15:02 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-15 Cont ID  
Sent By dhayes Date 2014-10-15 Time 15:13 Rev Time 0.00
Received By dhayes Date 2014-10-06 Time 17:32 Sent To  
Notes
2014-10-06 17:39:52RE-SUBMITTAL SENT TO ZONING SHELF FOR HISTORIC REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 11:29 Rev Time 0.00
Received By dhayes Date 2014-07-11 Time 13:02 Sent To  
Notes
2014-07-14 13:03:12SENT TO R5 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 09:12 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 09:12 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-15 Cont ID  
Sent By jgomez Date 2014-08-15 Time 11:09 Rev Time 0.00
Received By jgomez Date 2014-08-15 Time 11:09 Sent To  
Notes
2014-08-15 11:12:30RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS WITH THE
 EQUIPMENT MANUFACTURER AND MODEL NUMBER AS REQUIRED BY
 SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: EQUIPMENT LISTED ON THE A/C PLAN SUBMITTED TO
 MATCH EQUIPMENT SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-15 Cont ID  
Sent By jgomez Date 2014-10-15 Time 09:21 Rev Time 0.00
Received By jgomez Date 2014-10-15 Time 09:21 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-08-15 Cont ID  
Sent By jgomez Date 2014-08-15 Time 13:54 Rev Time 0.00
Received By jgomez Date 2014-08-14 Time 15:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By fmittner Date 2014-10-10 Time 12:31 Rev Time 0.00
Received By fmittner Date 2014-10-10 Time 12:31 Sent To  
Notes
2014-10-06 17:45:00NEW DRAWINGS AND PRODUCT APPROVALS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 15:02 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 15:02 Sent To  
Notes
2014-09-02 15:02:39BACK TO R 5 BOX
2014-07-25 10:32:307/25/14