| 2014-07-21 10:38:05 | DATE: 7/21/2014 |
| | PROJECT: KIKIMAZ DESIGN |
| | PERMIT#: 14070365 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 SIGN |
| | AND PRINT THE NAME OF THE DESIGNER ON THE PLANS AS |
| | INDICATED ABOVE. |
| | |
| | 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| | STRUCTURES. NEC 250.94. INDICATE AND PROVIDE THE |
| | REQUIRED INTERSYSTEM BONDING DEVICE AT THE SERVICE AS |
| | INDICATED ABOVE. |
| | |
| | 3) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 INDICATE |
| | AND PROVIDE THE REQUIRED EXIT AND EMERGENCY |
| | ILLUMINATION AS IIDICATED ABOVE. |
| | |
| | 4) AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED |
| | FOR EACH CONTROLLER AND SHALL DISCONNECT THE |
| | CONTROLLER. THE DISCONNECTING MEANS SHALL BE LOCATED IN |
| | SIGHT FROM THE CONTROLLER LOCATION. EACH DISCONNECTING |
| | MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS PURPOSE |
| | UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT. |
| | THE MARKING SHALL BE OF SUFFICIENT DURABILITY TO |
| | WITHSTAND THE ENVIRONMENT INVOLVED.NEC 430.102,110.22 |
| | (A) INDICATE AND PROVIDE DICONNECTS AS REQUIRED AND |
| | INDICATED ABOVE. |
| | |
| | 5) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN |
| | ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT |
| | SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE |
| | OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED |
| | AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. |
| | SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. NEC 600.5. INDICATE AND |
| | PROVIDE THE REQUIRED SIGN CIRCUIT AS INDICATED ABOVE. |
| | |
| | 6) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16. PROVIDE |
| | AND INSTALL THE REQUIRED EXIT AND EMERGENCY LIGHTING AS |
| | INDICATED ABOVE. |
| | |
| | 7) ILLUMINATION SHALL BE PROVIDED FOR ALL WORKING |
| | SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS, |
| | PANELBOARDS, OR MOTOR CONTROL CENTERS INSTALLED |
| | INDOORS. ADDITIONAL LIGHTING OUTLETS SHALL NOT BE |
| | REQUIRED WHERE THE WORK SPACE IS ILLUMINATED BY AN |
| | ADJACENT LIGHT SOURCE OR AS PERMITTED BY 210.70(A)(1), |
| | EXCEPTION NO. 1, FOR SWITCHED RECEPTACLES. IN |
| | ELECTRICAL EQUIPMENT ROOMS, THE ILLUMINATION SHALL NOT |
| | BE CONTROLLED BY AUTOMATIC MEANS ONLY. NEC 110.26(D) |
| | PROVIDE AND INSTALL THE REQUIRED ILLUMINATION AS |
| | INDICATED ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |