Plan Review Details - Permit 14070364
Plan Review Stops For Permit 14070364
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2014-08-30 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-29 Cont ID  
Sent By jwitmer Date 2014-07-29 Time 07:08 Rev Time 0.00
Received By jwitmer Date 2014-07-29 Time 05:50 Sent To  
Notes
2014-07-29 07:08:09 
 BUILDING PLAN REVIEW
 PERMIT: 14070364
 ADD: 401 CLEMATIS ST
 CITY HALL PARKING GARAGE/ DIESEL FUEL STORAGE
 CONT: TBD
 TEL: VIVEK 794-1061
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 29/2014
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1.02 THE HOLE CORE DRILLED THROUGH THE 2ND
 FLOOR GARAGE FLOOR SLAB FOR DETERMINING THE FLOOR FIRE
 RESISTANCE IN HOURS IS TO BE PROTECTED. THE 2010 FBC-B
 713.4.1.1. THROUGH PENETRATIONS. THIS IS BUILDING TYPE
 IIB CONSTRUCTION, FLOOR REQUIRED FIRE RATING IS 2 HRS.
 2010 FBC-B 721.2.2.1.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 09:18 Rev Time 0.00
Received By dhayes Date 2014-09-03 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-01 Cont ID  
Sent By dhayes Date 2014-08-01 Time 09:20 Rev Time 0.00
Received By dhayes Date 2014-08-01 Time 08:38 Sent To  
Notes
2014-08-01 10:29:44DATE: 8/1/2014
 PROJECT: CITY OF WPB PARKING GARAGE GENERATOR FUEL TANK
 REPLACEMENT
 PERMIT#: 14070364
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION REQUEST. PLEASE PROVIDE A
 DETAILED RESPONSE FOR THE FOLLOWING REQUESTS. FBC WPB
 AMENDMENTS 107.3.5.1
 1A.- IDENTIFY THE CLASSIFICATION OF THE ZONE.
 1B.- AN ELECTRICAL DETAIL FOR THE RELOCATION OF THE
 LIGHTING. NOTE 4. ON SHEET A-1.01 STATES TO "REMOVE ALL
 EXISTING CEILING LIGHT FIXTURES, VERIFY EXPLOSIVE
 RESISTANT AND RE-INSTALL IN SIMILAR LOCATION". PROVIDE
 A REFLECTED CEILING PLAN AND AN ELECTRICAL PLAN THAT
 INDICATES HOW AND WHERE THE LIGHTING IS TO BE
 RELOCATED, CONNECTED AND SUPPORTED. INCLUDE ALL EXIT
 AND EMERGENCY LIGHTING. IDENTIFY THE CLASSIFICATION OF
 THE ENVIRONMENT AND THE WIRING METHODS TO BE
 IMPLEMENTED AND FIRE RATING TO BE MAINTAINED.
 1C.- AN ELECTRICAL DETAIL FOR THE RELOCATION OF THE
 LIGHT SWITCH. SHEET A-1.01 INDICATES A "RELOCATED LIGHT
 SWITCH" PROVIDE AN ELECTRICAL FLOOR PLAN THAT INDICATES
 HOW AND WHERE THE SWITCH IS TO BE RELOCATED, CONNECTED
 AND SUPPORTED. IDENTIFY THE CLASSIFICATION OF THE
 ENVIRONMENT AND THE WIRING METHODS TO BE IMPLEMENTED
 AND FIRE RATING TO BE MAINTAINED.
 1D.- AN ELECTRICAL DETAIL TO INDICATE THE REMOVAL,
 RELOCATION, AND REWIRING OF THE CONTROL WORING TO THE
 FUEL TANK MONITORING SYSTEM. PROVIDE AN ELECTRICAL
 FLOOR PLAN THAT INDICATES HOW AND WHERE THE CONTROLER
 IS TO BE RELOCATED, CONNECTED AND SUPPORTED. IDENTIFY
 THE CLASSIFICATION OF THE ENVIRONMENT AND THE WIRING
 METHODS TO BE IMPLEMENTED AND FIRE RATING TO BE
 MAINTAINED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By pleduc Date 2014-07-14 Time   Rev Time 0.00
Received By pleduc Date 2014-07-14 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-03 Cont ID  
Sent By dhayes Date 2014-09-03 Time 09:18 Rev Time 0.00
Received By dhayes Date 2014-08-30 Time 14:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-01 Cont ID  
Sent By dhayes Date 2014-08-01 Time 10:29 Rev Time 0.00
Received By dhayes Date 2014-07-11 Time 07:44 Sent To  
Notes
2014-07-11 07:45:18INCOMING SENT TO B-06 . JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-29 Cont ID  
Sent By hmoser Date 2014-07-29 Time 15:24 Rev Time 0.00
Received By hmoser Date 2014-07-29 Time 10:18 Sent To  
Notes
2014-07-29 15:24:38HAVE FIRE DAMPER INSTALLATION INSTRUCTIONS ON SITE FOR
 INSPECTION
 PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
  
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-07-29 Cont ID  
Sent By jwitmer Date 2014-07-29 Time 07:08 Rev Time 0.00
Received By jwitmer Date 2014-07-29 Time 05:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2014-07-18 Cont ID  
Sent By aaponte Date 2014-07-18 Time 15:58 Rev Time 0.00
Received By aaponte Date 2014-07-18 Time 15:58 Sent To  
Notes
2014-07-29 07:07:23BUILDING PLAN REVIEW
 PERMIT: 14070364
 ADD: 401 CLEMATIS ST
 CITY HALL PARKING GARAGE/ DIESEL FUEL STORAGE
 CONT: TBD
 TEL: VIVEK 794-1061
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 29/2014
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1.02 THE HOLE CORE DRILLED THROUGH THE 2ND
 FLOOR GARAGE FLOOR SLAB FOR DETERMINING THE FLOOR FIRE
 RESISTANCE IN HOURS IS TO BE PROTECTED. THE 2010 FBC-B
 713.4.1.1. THROUGH PENETRATIONS. THIS IS BUILDING TYPE
 IIB CONSTRUCTION, FLOOR REQUIRED FIRE RATING IS 2 HRS.
 2010 FBC-B 721.2.2.1.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  