| Plan Review Stops For Permit 14070321 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2015-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-11 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-11 |
Time |
08:35 |
Sent To |
Z |
|
| Notes |
| 2015-05-11 18:50:46 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES | | | THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY | | | WITH FBC-R302.5.1 | | | | | | 2) THE PRODUCT APPROVAL REQUIRES THE RAS 117 | | | CALCULATIONS TO BE SIGNED AND SEALED BY A FLORIDA | | | LICENSED ENGINEER, ARCHITECT OR CERTIFIED ROOFING | | | CONSULTANT. SPECIFY WHICH ONE OF THE APPROVED ROOFING | | | ASSEMBLIES LISTED IN THE PRODUCT APPROVAL FOR GAF | | | MODIFIED ROOFING SYSTEM (NOA NO. 14-0102.12) WILL BE | | | INSTALLED. IDENTIFY THE ANCHORING AND DESIGN PRESSURES | | | FOR THE SELECTED ASSEMBLY. SUBMIT TWO SETS OF SIGNED | | | AND SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | | IF THE DESIGN PRESSURES ARE LESS THAN REQUIRED. | | | | | | 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND | | | INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION | | | DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED | | | SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3 | | | AND FBC 107.2.1 | | | | | | 4) THE PRODUCT APPROVAL SUBMITTED FOR THE LARGE MISSILE | | | IMPACT RATED SINGLE HUNG WINDOWS HAS INSTALLATION | | | DRAWINGS FOR WINDOWS WITH NO IMPACT RATING. THE FL | | | NUMBER WRITTEN ON THE SUBMITTAL IS INCORRECT. IT IS | | | MISSING A NUMBER AND SHOULD BE FL 14462. PLEASE | | | CORRECT. | | | | | | 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE | | | STEEL STORM PANELS HAS THE GLASS SEPARATION INCORRECTLY | | | SPECIFIED AS 3". SEE TABLE 2 ON SHEET 4 OF 4. FOR | | | SYSTEM 3 WITH A PANEL LENGTH OF UP TO 8'-8" AND A | | | POSITIVE PRESSURE OF UP TO 50 PSF, THE MINIMUM GLASS | | | SEPARATION IS 3.5". PLEASE CORRECT. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-16 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-13 |
Time |
08:12 |
Sent To |
Z |
|
| Notes |
| 2015-03-16 12:08:16 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS THAT WERE SUBMITTED HAVE AN ENGINEER'S | | | SEAL AND A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE | | | ONLY VALID FOR ELECTRONICALLY TRANSMITTED PLANS. PLANS | | | THAT ARE SUBMITTED ON PAPER ARE REQUIRED TO HAVE THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THEM IN | | | ADDITION TO THEIR SEAL. FS 471 | | | | | | 2) THE TYPE OF CONSTRUCTION AND THE TYPE OF OCCUPANCY | | | SPECIFIED ON THE COVER SHEET ARE INCORRECT. THE | | | CONSTRUCTION TYPE SHOULD BE V-B AND THE OCCUPANCY TYPE | | | IS R-3. | | | FBC 601 AND 301 | | | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. THE ENGINEER, MANUEL MARTINEZ, IS | | | THE DESIGNER OF RECORD FOR THIS PROJECT. THE PRODUCT | | | APPROVALS WERE NOT APPROVED BY ENGINEER. | | | | | | 4) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES | | | THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY | | | WITH FBC-R302.5.1 | | | | | | 5) SPECIFY WHICH ONE OF THE APPROVED ROOFING ASSEMBLIES | | | LISTED IN THE PRODUCT APPROVAL FOR GAF MODIFIED ROOFING | | | SYSTEM (NOA NO. 14-0102.12) WILL BE INSTALLED. IDENTIFY | | | THE ANCHORING AND DESIGN PRESSURES FOR THE SELECTED | | | ASSEMBLY. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING IF THE DESIGN | | | PRESSURES ARE LESS THAN REQUIRED. | | | | | | 6) THE PRODUCT APPROVALS FOR THE OUT-SWING FRENCH DOORS | | | ( NOA NO. 08-0312.09 ) EXPIRED IN MAY 2011. SUBMIT | | | CURRENT PRODUCT APPROVALS. DCA RULE 9N-3 | | | | | | 7) SUBMIT PRODUCT APPROVALS FOR THE STUCTURAL MULLIONS | | | THAT WILL BE REQUIRED BETWEEN THE FRENCH DOORS AND THE | | | FIXED WINDOWS OR SUBMIT PRODUCT APPROVALS FOR FRENCH | | | DOORS WITH SIDELIGHTS. DCA RULE 9N-3 | | | | | | 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND | | | INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION | | | DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED | | | SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3 | | | AND FBC 107.2.1 | | | | | | 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | SECTIONAL GARAGE DOOR HAS A DESIGN PRESSURE OF -52.0 | | | PSF AND THE PLANS SEPCIFY THAT -53.2 PSF IS REQUIRED. | | | FBC 107.2.1 | | | | | | 10) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND THE | | | PRODUCT APPROVAL SUBMITTED IS FOR DOUBLE HUNG WINDOWS. | | | PLEASE CLARIFY. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-20 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-13 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2014-08-15 17:02:17 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENGINEER IS REQUIRED TO SIGN AND SEAL ALL PLAN | | | SHEETS THAT ARE RELATED TO STRUCTURAL DESIGN. SHEETS | | | 3.0 AND 4.0 CONTAIN OPENING PRESSURES AND THE COVER | | | SHEET CONTAINS THE DESIGN COMPLIANCE STATEMENT. CITY | | | AMENDMENTS 107.1 | | | | | | 2) THE OTHER PLAN SHEETS ARE REQUIRED TO HAVE THE NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | CITY AMENDMENTS 107.2.1 | | | | | | 3) SPECIFY THE TYPE OF CONSTRUCTION AND TYPE OF | | | OCCUPANCY ON THE PLANS. FBC 602 AND 302 | | | | | | 4)THE DESIGN CRITERIA ON SHEETS 7.0 & 8.0 IS INCORRECT. | | | THE WIND SPEED IS 170 MPH, THE APPLICABLE CODE IS THE | | | 2010 FBC AND ASCE 7 - 10. | | | | | | 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 107.3.4.1 | | | | | | 6) THE WINDOW IN THE SECOND FLOOR BATHROOM MARKED (6) | | | IS NOT LISTED IN THE WINDOW SCHEDULE ON SHEET 3.0. CITY | | | AMENDMENTS 107.2.1 | | | | | | 7) THE BATHROOMS ARE REQUIRED TO COMPLY WITH FBCR 303.3 | | | FOR NATURAL OR MECHANICAL VENTILATION. | | | | | | 8) THE DOORS FROM THE GARAGE TO THE OFFICE (#5) AND | | | GAME ROOM (#6) ARE REQUIRED TO COMPLY WITH FBCR302.5.1 | | | OPENING PROTECTION. | | | | | | 9) NEITHER THE OFFICE NOR THE GAME ROOM CAN BE USED AS | | | A SLEEPING ROOM AND SHALL BE SO LABELED ON THE PLANS. | | | FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE | | | DIRECTLY INTO A SLEEPING ROOM. | | | | | | 10) THE SCOPE OF WORK ON THE COVER SHEET SPECIFIES A | | | NEW BEDROOM AND FAMILY ROOM ABOVE THE GARAGE. THE | | | BEDROOM AND FAMILY ROOM ARE NOT LABELED ON THE FLOOR | | | PLAN. THE ENTIRE SECOND FLOOR IS LABELED GAME ROOM. | | | PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | | | 11) FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE | | | DIRECTLY INTO A SLEEPING ROOM. SHOW THAT THE SECOND | | | FLOOR BEDROOM WILL COMPLY. | | | | | | 12) SHOW COMPLIANCE WITH FBCR FOR COMPLIANCE WITH FBCR | | | 314 SMOKE ALARMS AND 315 CARBON MONOXIDE ALARMS. | | | | | | 13) SUBMIT TWO SETS OF ENERGY CALCULATIONS. FBC ENERGY | | | CONSERVATION 103.2.1.1 | | | | | | 14) SHOW COMPLIANCE WITH FBCR 806.1 ATTIC VENTILATION. | | | | | | 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | EXTERIOR DOORS, SLIDING GLASS DOOR, SECTIONAL GARAGE | | | DOOR, WINDOWS, ROOF COVERING, BALCONY WATER PROOFING | | | AND SIMPSON CONNECTORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 16) THE VALUATION FOR THE PROJECT IS LOW. THE ICC | | | VALUATION IS $155,932.00 FOR A SINGLE FAMILY DWELLING | | | AND GARAGE. BECAUSE THERE IS NOT A KITCHEN THIS CAN BE | | | REDUCED TO $135,932.00. CITY AMENDMENTS 109.3 | | | | | | 17) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE PLAN REVIEW | | | ITEMS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-11 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-11 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2015-05-11 18:55:17 | APPROVED WITH EXCEPTION | | | MAKE CORRECTIONS REDLINED ON PLANS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-03-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-13 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-13 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2015-03-13 14:53:12 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-20 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-15 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2014-08-20 09:06:08 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY | | | AMENDMENTS 107.2.1 | | | | | | 2) SHOW COMPLIANCE WITH FBCR 314 FOR SMOKE ALARMS AND | | | 315 FOR CARBON MONOXIDE ALARMS. | | | | | | 3) ALL RECEPTACLE OUTLETS IN THE GARAGE ARE REQUIRED TO | | | BE GFCI PROTECTED. THIS INCLUDES THE ONE FOR THE GARAGE | | | DOOR OPENER. NEC 210.8 | | | | | | 4) EXTERIOR RECEPTCAL OUTLETS ARE REQUIRED TO BE | | | WEATHER-PROOF. NEC 406.8 (B) | | | | | | 5) THE WIRING FROM THE SWITCHES CONTROLLING THE | | | EXTERIOR SPOT LIGHTS AND SOME OF THE OTHER EXTERIOR | | | LIGHTING OUTLETS ARE NOT INDICATED ON THE PLANS. CITY | | | AMENDMENTS 107.2.1 | | | | | | 6) A RECEPTACLE OUTLET IS REQUIRED AT THE FRONT OF THE | | | DWELLING. NEC210.52 (E) (1) | | | | | | 7) AN APPARENT PRINTING ERROR SHOWS A RECEPTACLE OUTLET | | | LOCATED ON THE OVERHEAD GARAGE DOOR. PLEASE CALARIFY. | | | CITY AMENDMENTS 107.2.1 | | | | | | 8) UPDATE THE NFPA CODE EDITIONS SPECIFIED IN THE | | | ELECTRICAL NOTES TO THE STANDARDS THAT ARE REFERENCED | | | IN CHAPTER 43 OF THE 2010 FBCR. | | | | | | 9) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM | | | BONDING. | | | | | | 10) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION. | | | | | | 11) SHOW COMPLIANCE WITH NEC 406.11 FOR | | | TAMPER-RESISTANT RECEPTACLES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-05-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-05-19 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-04-22 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-03-16 |
|
|
Cont ID |
|
| Sent By |
R McDoug |
Date |
2015-03-16 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-02-23 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-20 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-11 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2015-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-11 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-11 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2015-05-11 15:17:23 | BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE PLANS MUST BE | | | STAMPED AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE | | | APPLICATION. 233-5025 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-08-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-11 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-11 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2014-08-11 09:44:16 | BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE PLANS MUST BE | | | STAMPED AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE | | | APPLICATION. 233-5025 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2015-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-11 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-11 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-03-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-13 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-13 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2015-03-13 10:38:37 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND | | | COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS | | | CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS AND | | | THE ENERGY COMPLIANCE FORM. PROVIDE THE MODEL NUMBERS | | | FOR THE AIR HANDLER AND CONDENSING UNIT. CITY | | | AMENDMENTS 107.2.1.3 AND 107.3.5.3 (REPEAT COMMENT) | | | | | | 2) THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IS | | | REQUIRED ON THE PAPER PLANS THAT WERE SUBMITTED. | | | DIGITAL SIGNATURES ARE FOR USE ON ELECTRONICALLY | | | TRANSMITTED PLANS. | | | SEE FS 471 & FS 668 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-13 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-13 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2014-08-13 09:01:32 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC ENERGY CONSERVATION SECTION 103.2.1.1 THE | | | PREPARER AND THE OWNER/AGENT IS REQUIRED TO SIGN THE | | | FORMS. | | | | | | 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE MECHANICAL DESIGN IS REQUIRED ON THE PLANS. CITY | | | AMENDMENTS 107.2.1 | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND | | | COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS | | | CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS. | | | PROVIDE THE MODEL NUMBERS FOR THE AIR HANDLER AND | | | CONDENSING UNIT. CITY AMENDMENTS 107.2.1.3 AND | | | 107.3.5.3 | | | | | | 5) SHOW THE RETURN AIR DUCTWORK FROM THE FIRST FLOOR | | | OFFICE TO THE A/H LOCATED ON THE SECOND FLOOR. SPECIFY | | | THE GRILL SIZE AND DUCT SIZE. CITY AMENDMENTS 107.3.5.3 | | | AND FBCR M1602 | | | | | | 6) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE HALF BATH | | | ON THE FIRST FLOOR. CITY AMENDMENTS 107.3.5.3 | | | | | | 7) IF THE A/H IS TO BE LOCATED IN A CLOSET, SHOW HOW | | | THE RETURN AIR WILL GET TO THE A/H. SPECIFY RETURN | | | GRILL SIZE. DUCT SIZES, LOUVERED DOOR, ETC. CITY | | | AMENDMENTS 107.3.5.3 AND FBCR M1602 | | | | | | 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-11 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-11 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2015-05-11 17:07:44 | APPROVED WITH EXCEPTIONS THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | | | | 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY | | | VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE | | | THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE | | | LAVATORY DRAIN CONNECTION. | | | | | | 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE | | | INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE | | | THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE | | | IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY | | | AMENDMENTS 107.2.1 AND FBCR P3201.7 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-03-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-13 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-13 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-13 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-13 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2014-08-13 08:10:23 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY | | | VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE | | | THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE | | | LAVATORY DRAIN CONNECTION. | | | | | | 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE | | | INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE | | | THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE | | | IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY | | | AMENDMENTS 107.2.1 AND FBCR P3201.7 | | | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE PLUMBING DESIGN IS REQUIRED ON THE PLANS. CITY | | | AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-08-19 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-08-19 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2015-08-19 16:26:11 | 8/19/15 ZONING FAILED 4TH REVIEW | | | 1. SUBMIT TWO CERIFIED SURVEYS | | | 2. AN ACCESSORY STRUCTURE CAN NOT BE BUILT ON A VACANT | | | LOT, PRIMARY STRUCTURE MUST BE BUILT FIRST | | | 3. SUBMIT DRAWING FOR THE SINGLE FAMILY HOUSE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2015-05-18 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-05-18 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-05-18 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2015-05-18 13:59:42 | 5/18/15 ZONING FAILED 3RD CHECKLIST | | | | | | 1. SUBMIT TWO SEAL AND SIGNED UP TO DATE SURVEYS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-03-16 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-03-16 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-03-16 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2015-03-16 16:04:12 | 3/16/15 ZONING FAILED AGAIN | | | | | | 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-08-11 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-07-17 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-17 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2014-07-17 15:31:25 | 7/17/14 ZONING FAILED | | | 1. PROVIDE TWO UP TO DATE SURVEYS. |
|
|