Plan Review Details - Permit 14070321
Plan Review Stops For Permit 14070321
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-11 Cont ID  
Sent By rmcdouga Date 2015-05-11 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2015-05-11 Time 08:35 Sent To Z
Notes
2015-05-11 18:50:46PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES
 THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY
 WITH FBC-R302.5.1
  
 2) THE PRODUCT APPROVAL REQUIRES THE RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER, ARCHITECT OR CERTIFIED ROOFING
 CONSULTANT. SPECIFY WHICH ONE OF THE APPROVED ROOFING
 ASSEMBLIES LISTED IN THE PRODUCT APPROVAL FOR GAF
 MODIFIED ROOFING SYSTEM (NOA NO. 14-0102.12) WILL BE
 INSTALLED. IDENTIFY THE ANCHORING AND DESIGN PRESSURES
 FOR THE SELECTED ASSEMBLY. SUBMIT TWO SETS OF SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 IF THE DESIGN PRESSURES ARE LESS THAN REQUIRED.
  
 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND
 INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION
 DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED
 SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3
 AND FBC 107.2.1
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR THE LARGE MISSILE
 IMPACT RATED SINGLE HUNG WINDOWS HAS INSTALLATION
 DRAWINGS FOR WINDOWS WITH NO IMPACT RATING. THE FL
 NUMBER WRITTEN ON THE SUBMITTAL IS INCORRECT. IT IS
 MISSING A NUMBER AND SHOULD BE FL 14462. PLEASE
 CORRECT.
  
 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE
 STEEL STORM PANELS HAS THE GLASS SEPARATION INCORRECTLY
 SPECIFIED AS 3". SEE TABLE 2 ON SHEET 4 OF 4. FOR
 SYSTEM 3 WITH A PANEL LENGTH OF UP TO 8'-8" AND A
 POSITIVE PRESSURE OF UP TO 50 PSF, THE MINIMUM GLASS
 SEPARATION IS 3.5". PLEASE CORRECT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-16 Cont ID  
Sent By rmcdouga Date 2015-03-16 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2015-03-13 Time 08:12 Sent To Z
Notes
2015-03-16 12:08:16PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS THAT WERE SUBMITTED HAVE AN ENGINEER'S
 SEAL AND A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE
 ONLY VALID FOR ELECTRONICALLY TRANSMITTED PLANS. PLANS
 THAT ARE SUBMITTED ON PAPER ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THEM IN
 ADDITION TO THEIR SEAL. FS 471
  
 2) THE TYPE OF CONSTRUCTION AND THE TYPE OF OCCUPANCY
 SPECIFIED ON THE COVER SHEET ARE INCORRECT. THE
 CONSTRUCTION TYPE SHOULD BE V-B AND THE OCCUPANCY TYPE
 IS R-3.
 FBC 601 AND 301
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. THE ENGINEER, MANUEL MARTINEZ, IS
 THE DESIGNER OF RECORD FOR THIS PROJECT. THE PRODUCT
 APPROVALS WERE NOT APPROVED BY ENGINEER.
  
 4) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES
 THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY
 WITH FBC-R302.5.1
  
 5) SPECIFY WHICH ONE OF THE APPROVED ROOFING ASSEMBLIES
 LISTED IN THE PRODUCT APPROVAL FOR GAF MODIFIED ROOFING
 SYSTEM (NOA NO. 14-0102.12) WILL BE INSTALLED. IDENTIFY
 THE ANCHORING AND DESIGN PRESSURES FOR THE SELECTED
 ASSEMBLY. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING IF THE DESIGN
 PRESSURES ARE LESS THAN REQUIRED.
  
 6) THE PRODUCT APPROVALS FOR THE OUT-SWING FRENCH DOORS
 ( NOA NO. 08-0312.09 ) EXPIRED IN MAY 2011. SUBMIT
 CURRENT PRODUCT APPROVALS. DCA RULE 9N-3
  
 7) SUBMIT PRODUCT APPROVALS FOR THE STUCTURAL MULLIONS
 THAT WILL BE REQUIRED BETWEEN THE FRENCH DOORS AND THE
 FIXED WINDOWS OR SUBMIT PRODUCT APPROVALS FOR FRENCH
 DOORS WITH SIDELIGHTS. DCA RULE 9N-3
  
 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND
 INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION
 DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED
 SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3
 AND FBC 107.2.1
  
 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SECTIONAL GARAGE DOOR HAS A DESIGN PRESSURE OF -52.0
 PSF AND THE PLANS SEPCIFY THAT -53.2 PSF IS REQUIRED.
 FBC 107.2.1
  
 10) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND THE
 PRODUCT APPROVAL SUBMITTED IS FOR DOUBLE HUNG WINDOWS.
 PLEASE CLARIFY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-20 Cont ID  
Sent By rmcdouga Date 2014-08-20 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2014-08-13 Time 09:37 Sent To  
Notes
2014-08-15 17:02:172010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEER IS REQUIRED TO SIGN AND SEAL ALL PLAN
 SHEETS THAT ARE RELATED TO STRUCTURAL DESIGN. SHEETS
 3.0 AND 4.0 CONTAIN OPENING PRESSURES AND THE COVER
 SHEET CONTAINS THE DESIGN COMPLIANCE STATEMENT. CITY
 AMENDMENTS 107.1
  
 2) THE OTHER PLAN SHEETS ARE REQUIRED TO HAVE THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 107.2.1
  
 3) SPECIFY THE TYPE OF CONSTRUCTION AND TYPE OF
 OCCUPANCY ON THE PLANS. FBC 602 AND 302
  
 4)THE DESIGN CRITERIA ON SHEETS 7.0 & 8.0 IS INCORRECT.
 THE WIND SPEED IS 170 MPH, THE APPLICABLE CODE IS THE
 2010 FBC AND ASCE 7 - 10.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 6) THE WINDOW IN THE SECOND FLOOR BATHROOM MARKED (6)
 IS NOT LISTED IN THE WINDOW SCHEDULE ON SHEET 3.0. CITY
 AMENDMENTS 107.2.1
  
 7) THE BATHROOMS ARE REQUIRED TO COMPLY WITH FBCR 303.3
 FOR NATURAL OR MECHANICAL VENTILATION.
  
 8) THE DOORS FROM THE GARAGE TO THE OFFICE (#5) AND
 GAME ROOM (#6) ARE REQUIRED TO COMPLY WITH FBCR302.5.1
 OPENING PROTECTION.
  
 9) NEITHER THE OFFICE NOR THE GAME ROOM CAN BE USED AS
 A SLEEPING ROOM AND SHALL BE SO LABELED ON THE PLANS.
 FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE
 DIRECTLY INTO A SLEEPING ROOM.
  
 10) THE SCOPE OF WORK ON THE COVER SHEET SPECIFIES A
 NEW BEDROOM AND FAMILY ROOM ABOVE THE GARAGE. THE
 BEDROOM AND FAMILY ROOM ARE NOT LABELED ON THE FLOOR
 PLAN. THE ENTIRE SECOND FLOOR IS LABELED GAME ROOM.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 11) FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE
 DIRECTLY INTO A SLEEPING ROOM. SHOW THAT THE SECOND
 FLOOR BEDROOM WILL COMPLY.
  
 12) SHOW COMPLIANCE WITH FBCR FOR COMPLIANCE WITH FBCR
 314 SMOKE ALARMS AND 315 CARBON MONOXIDE ALARMS.
  
 13) SUBMIT TWO SETS OF ENERGY CALCULATIONS. FBC ENERGY
 CONSERVATION 103.2.1.1
  
 14) SHOW COMPLIANCE WITH FBCR 806.1 ATTIC VENTILATION.
  
 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, SLIDING GLASS DOOR, SECTIONAL GARAGE
 DOOR, WINDOWS, ROOF COVERING, BALCONY WATER PROOFING
 AND SIMPSON CONNECTORS AS REQUIRED BY DCA RULE 9N-3.
  
 16) THE VALUATION FOR THE PROJECT IS LOW. THE ICC
 VALUATION IS $155,932.00 FOR A SINGLE FAMILY DWELLING
 AND GARAGE. BECAUSE THERE IS NOT A KITCHEN THIS CAN BE
 REDUCED TO $135,932.00. CITY AMENDMENTS 109.3
  
 17) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE PLAN REVIEW
 ITEMS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-07 Cont ID  
Sent By rmcdouga Date 2015-05-11 Time 18:51 Rev Time 0.00
Received By rmcdouga Date 2015-05-11 Time 18:51 Sent To  
Notes
2015-05-11 18:55:17APPROVED WITH EXCEPTION
 MAKE CORRECTIONS REDLINED ON PLANS

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By rmcdouga Date 2015-03-13 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2015-03-13 Time 09:00 Sent To  
Notes
2015-03-13 14:53:12APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-20 Cont ID  
Sent By rmcdouga Date 2014-08-20 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2014-08-15 Time 16:41 Sent To  
Notes
2014-08-20 09:06:082010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 2) SHOW COMPLIANCE WITH FBCR 314 FOR SMOKE ALARMS AND
 315 FOR CARBON MONOXIDE ALARMS.
  
 3) ALL RECEPTACLE OUTLETS IN THE GARAGE ARE REQUIRED TO
 BE GFCI PROTECTED. THIS INCLUDES THE ONE FOR THE GARAGE
 DOOR OPENER. NEC 210.8
  
 4) EXTERIOR RECEPTCAL OUTLETS ARE REQUIRED TO BE
 WEATHER-PROOF. NEC 406.8 (B)
  
 5) THE WIRING FROM THE SWITCHES CONTROLLING THE
 EXTERIOR SPOT LIGHTS AND SOME OF THE OTHER EXTERIOR
 LIGHTING OUTLETS ARE NOT INDICATED ON THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 6) A RECEPTACLE OUTLET IS REQUIRED AT THE FRONT OF THE
 DWELLING. NEC210.52 (E) (1)
  
 7) AN APPARENT PRINTING ERROR SHOWS A RECEPTACLE OUTLET
 LOCATED ON THE OVERHEAD GARAGE DOOR. PLEASE CALARIFY.
 CITY AMENDMENTS 107.2.1
  
 8) UPDATE THE NFPA CODE EDITIONS SPECIFIED IN THE
 ELECTRICAL NOTES TO THE STANDARDS THAT ARE REFERENCED
 IN CHAPTER 43 OF THE 2010 FBCR.
  
 9) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM
 BONDING.
  
 10) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION.
  
 11) SHOW COMPLIANCE WITH NEC 406.11 FOR
 TAMPER-RESISTANT RECEPTACLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-19 Cont ID  
Sent By lmarchan Date 2015-05-19 Time 14:45 Rev Time 0.00
Received By lmarchan Date 2015-04-22 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-16 Cont ID  
Sent By R McDoug Date 2015-03-16 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2015-02-23 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-20 Cont ID  
Sent By rmcdouga Date 2014-08-20 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2014-07-11 Time 07:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-05-11 Cont ID  
Sent By rmcdouga Date 2015-05-11 Time 15:17 Rev Time 0.00
Received By rmcdouga Date 2015-05-11 Time 15:17 Sent To  
Notes
2015-05-11 15:17:23BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-08-11 Cont ID  
Sent By rmcdouga Date 2014-08-11 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2014-08-11 Time 09:43 Sent To  
Notes
2014-08-11 09:44:16BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-05-11 Cont ID  
Sent By rmcdouga Date 2015-05-11 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2015-05-11 Time 08:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-03-13 Cont ID  
Sent By rmcdouga Date 2015-03-13 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2015-03-13 Time 08:59 Sent To  
Notes
2015-03-13 10:38:37PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND
 COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS
 CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS AND
 THE ENERGY COMPLIANCE FORM. PROVIDE THE MODEL NUMBERS
 FOR THE AIR HANDLER AND CONDENSING UNIT. CITY
 AMENDMENTS 107.2.1.3 AND 107.3.5.3 (REPEAT COMMENT)
  
 2) THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IS
 REQUIRED ON THE PAPER PLANS THAT WERE SUBMITTED.
 DIGITAL SIGNATURES ARE FOR USE ON ELECTRONICALLY
 TRANSMITTED PLANS.
 SEE FS 471 & FS 668
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By rmcdouga Date 2014-08-13 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2014-08-13 Time 08:10 Sent To  
Notes
2014-08-13 09:01:322010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 103.2.1.1 THE
 PREPARER AND THE OWNER/AGENT IS REQUIRED TO SIGN THE
 FORMS.
  
 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE MECHANICAL DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND
 COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS
 CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS.
 PROVIDE THE MODEL NUMBERS FOR THE AIR HANDLER AND
 CONDENSING UNIT. CITY AMENDMENTS 107.2.1.3 AND
 107.3.5.3
  
 5) SHOW THE RETURN AIR DUCTWORK FROM THE FIRST FLOOR
 OFFICE TO THE A/H LOCATED ON THE SECOND FLOOR. SPECIFY
 THE GRILL SIZE AND DUCT SIZE. CITY AMENDMENTS 107.3.5.3
 AND FBCR M1602
  
 6) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE HALF BATH
 ON THE FIRST FLOOR. CITY AMENDMENTS 107.3.5.3
  
 7) IF THE A/H IS TO BE LOCATED IN A CLOSET, SHOW HOW
 THE RETURN AIR WILL GET TO THE A/H. SPECIFY RETURN
 GRILL SIZE. DUCT SIZES, LOUVERED DOOR, ETC. CITY
 AMENDMENTS 107.3.5.3 AND FBCR M1602
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-08-07 Cont ID  
Sent By rmcdouga Date 2015-05-11 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2015-05-11 Time 16:32 Sent To  
Notes
2015-05-11 17:07:44APPROVED WITH EXCEPTIONS THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY
 VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE
 THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE
 LAVATORY DRAIN CONNECTION.
  
 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE
 INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE
 THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE
 IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1 AND FBCR P3201.7
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By rmcdouga Date 2015-03-13 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2015-03-13 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By rmcdouga Date 2014-08-13 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2014-08-13 Time 07:27 Sent To  
Notes
2014-08-13 08:10:232010 FBC
  
 DENIED BY PLUMBING
  
 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY
 VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE
 THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE
 LAVATORY DRAIN CONNECTION.
  
 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE
 INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE
 THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE
 IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1 AND FBCR P3201.7
  
 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE PLUMBING DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2015-08-19 Cont ID  
Sent By sgraham Date 2015-08-19 Time 16:23 Rev Time 0.00
Received By sgraham Date 2015-08-19 Time 16:23 Sent To  
Notes
2015-08-19 16:26:118/19/15 ZONING FAILED 4TH REVIEW
 1. SUBMIT TWO CERIFIED SURVEYS
 2. AN ACCESSORY STRUCTURE CAN NOT BE BUILT ON A VACANT
 LOT, PRIMARY STRUCTURE MUST BE BUILT FIRST
 3. SUBMIT DRAWING FOR THE SINGLE FAMILY HOUSE.

Review Stop Z ZONING
Rev No 3 Status F Date 2015-05-18 Cont ID  
Sent By sgraham Date 2015-05-18 Time 13:58 Rev Time 0.00
Received By sgraham Date 2015-05-18 Time 13:58 Sent To  
Notes
2015-05-18 13:59:425/18/15 ZONING FAILED 3RD CHECKLIST
  
 1. SUBMIT TWO SEAL AND SIGNED UP TO DATE SURVEYS

Review Stop Z ZONING
Rev No 2 Status F Date 2015-03-16 Cont ID  
Sent By sgraham Date 2015-03-16 Time 16:03 Rev Time 0.00
Received By sgraham Date 2015-03-16 Time 16:03 Sent To  
Notes
2015-03-16 16:04:123/16/15 ZONING FAILED AGAIN
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-11 Cont ID  
Sent By sgraham Date 2014-07-17 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2014-07-17 Time 09:41 Sent To  
Notes
2014-07-17 15:31:257/17/14 ZONING FAILED
 1. PROVIDE TWO UP TO DATE SURVEYS.