Plan Review Details - Permit 14070263
Plan Review Stops For Permit 14070263
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-16 Cont ID  
Sent By jwitmer Date 2014-07-16 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2014-07-16 Time 07:06 Sent To  
Notes
2014-07-16 07:52:48BUILDING PLAN REVIEW
 PERMIT: 14070263
 ADD: 1016 CLARE AVE. BUILDING # 5, 2ND FL SUITE # 4
 BUILDING # 5, 3RD FL SUITE # ??? 900 SQ FT
 CONT: TBD
 TEL: (561) 223-2042 / BORIS JOFRE
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 16/ 2014
 ACTION: DENIED
  
 1)THIS REVIEW WILL BE CONSIDERED A CHANGE OF OCCUPANCY
 FROM STORAGE TO A4 ASSEMBLY OCCUPANCY PLAYING FIELDS
 WITH SPECTATOR SEATING &
 NEW OFFICE ALSO CHANGE OF OCCUPANCY TO BUSINESS
 OCCUPANCY.
  
 THE PLANS ARE DEFICIENT IN THE REQUIREMENTS FOR MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD PLAYING FIELDS @50 / SQ FT , SPECTATOR
 SEATING @ 15 SQ FT APPROX 373 OCC LOAD
 GROSS
 NET
 MEANS OF EGRESS:
 EXIT ACCESS OCCUPANT LOADS FOR THE WHOLE FLOOR AND LIFE
 SAFETY PLAN FOR EXITING
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS FOR EXTERIOR STAIRS, LANDINGS HANDRAIL/
 GUARDRAIL SYSTEM PLANS ARE DESIGNED TO THE 2007 FBC
 CURRENT CODE 2010 FBC-B.
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3) : WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. THE SUBMITTED PLANS ARE MORE OF A
 PICTORIAL OR CONCEPT DRAWING THERE IS NO DETAILS FOR
 EITHER OF THE OCCUPANCY GROUPS DEPICTED INTHE PLANS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 13:22 Rev Time 0.00
Received By dhayes Date 2014-09-04 Time 13:16 Sent To  
Notes
2014-09-04 13:36:55DATE: 9/4/2014
 PROJECT: CITY SOCCER
 PERMIT#: 14070263
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO THE FBC
 107.2.1. THERE IS NO ELECTRICAL INFORMATION ON THE
 SUBMITTAL TO REVIEW. SEE BELOW FOR THE MINIMUM PLAN
 REVIEW CRITERIA FOR ELECTRICAL WORK REVISE PLANS TO
 INCLUDE THE FOLOLOWING::
 A.) 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, SECTION 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.107.3.5.1.2 ELECTRICAL
 1. ELECTRICAL: WIRING, SERVICES, FEEDERS AND BRANCH
 CIRCUITS, OVERCURRENT PROTECTION, GROUNDING, WIRING
 METHODS AND MATERIALS, GFCI'S
 2. EQUIPMENT
 3. SPECIAL OCCUPANCIES
 4. EMERGENCY SYSTEMS
 5. COMMUNICATION SYSTEMS
 6. LOW VOLTAGE
 7. LOAD CALCULATIONS
 8. DESIGN FLOOD ELEVATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-07-10 Cont ID  
Sent By pleduc Date 2014-07-10 Time   Rev Time 0.00
Received By pleduc Date 2014-07-10 Time 09:40 Sent To  
Notes
2014-07-10 11:14:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. LIFE SAFETY PLAN TO THE OFFICE SPACE NOT PROVIDED.
  
 2. DIMENSIONS AND OCCUPANY LOAD NOT PROVIDED.
  
 3. EXISTING/PROPOSED FIRE ALARM DEVICES NOT PROVIDED.
  
 4. EXISTING/PROPOSED FIRE SPRINKLER NOT PROVIDED.
  
 5. STAIR DETAIL NOT PROVIDED.
  
 6. EXIT SIGNAGE AND EMERGENCY LIGHTING NOT PROVIDED.
  
 7. FIRE EXTINGUISHER LOCATIONS NOT PROVIDED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 13:36 Rev Time 0.00
Received By dhayes Date 2014-07-09 Time 17:54 Sent To  
Notes
2014-07-09 17:55:52B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-16 Cont ID  
Sent By jwitmer Date 2014-07-16 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2014-07-16 Time 07:57 Sent To  
Notes
2014-07-16 07:57:51BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-23 Cont ID  
Sent By jsaez Date 2014-07-23 Time 11:13 Rev Time 0.00
Received By jsaez Date 2014-07-23 Time 11:12 Sent To  
Notes
2014-07-23 11:14:591. NO MECHANICAL PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-16 Cont ID  
Sent By jwitmer Date 2014-07-16 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2014-07-16 Time 07:53 Sent To  
Notes
2014-07-16 07:53:34PLUMBING PLAN REVIEW
 PERMIT: 14070263
 ADD: 1016 CLARE AVE. BUILDING # 5, 2ND FL SUITE # 4
 BUILDING # 5, 3RD FL SUITE # ??? 900 SQ FT
 CONT: TBD
 TEL: (561) 223-2042 / BORIS JOFRE
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 16/ 2014
 ACTION: DENIED
  
 1)THIS REVIEW WILL BE CONSIDERED A CHANGE OF OCCUPANCY
 FROM STORAGE TO A4 ASSEMBLY OCCUPANCY PLAYING FIELDS
 WITH SPECTATOR SEATING &
 NEW OFFICE ALSO CHANGE OF OCCUPANCY TO BUSINESS
 OCCUPANCY.
  
 THE PLANS ARE DEFICIENT IN THE REQUIREMENTS FOR MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3PLUMBING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. PLUMBING RISER
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  