Plan Review Details - Permit 14070255
Plan Review Stops For Permit 14070255
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-02-03 Cont ID  
Sent By jgomez Date 2015-02-03 Time 16:01 Rev Time 0.00
Received By jgomez Date 2015-02-03 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 07:18 Rev Time 0.00
Received By jgomez Date 2014-11-05 Time 07:18 Sent To E
Notes
2014-11-05 07:43:3311/5/14 TALKED TO MR. DEXTER. HE SAID HE WILL PROVIDE
 THE FOLLOWING BEFORE ISSUING THE PERMIT. (ALSO: ADDED
 $6000 VALUATION FOR WORK IN REAR STUDIO).
  
 1- REVISE ENERGY CALCULATIONS:
 A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH.
 ACCORDING TO THE PROPERTY APPRAISAL AERIAL VIEW, THERE
 NO OVERHANGS EXCEPT FOR THE MANSARD IN THE FRONT
 ELEVATION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) REVISE THE TYPE OF ROOF ON PAGE 2 OF 5. COORDINATE
 WITH ITEM #1 A ABOVE. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS U-FACTOR
 AND SHGC FACTOR SPECIFIED IN THE ENERGY CALCULATIONS ON
 ITEM #7. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 JULIO GOMEZ
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 10:53 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 10:49 Sent To  
Notes
2014-07-31 11:01:26RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- SHEET A-1:
 A) ENGINEER TO REVISE THE BUILDING EXPOSURE. ACCORDING
 TO SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL , THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS
 REQUIRED.
  
 B) ENGINEER TO ELECT THE TYPE OF ALTERATION LEVEL AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL11120-R7 SUBMITTED WAS REVISED. NEED TO SUBMIT
 CURRENT REVISED FLORIDA PRODUCT APPROVAL FL11120-R10.
  
 B) WINDOW MULLIONS. FLORIDA PRODUCT APPROVAL FL11870-R2
 SUBMITTED WAS REVISED. NEED TO SUBMIT CURRENT REVISED
 FLORIDA PRODUCT APPROVAL FL11870-R3.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVED ABOVE
 PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 107.3.4.1 OF
 CITY AMENDMENTS TO FBC.
  
 5- SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604 OF 2010 FBC-EXISTING BUILDING.
  
 6- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
 ***NOTE: ACCORDING TO PROPERTY APPRAISAL INFORMATION
 THERE WAS AN ENTRY PORCH IN THE MAIN HOUSE. AND, THERE
 WAS AN STORAGE AREA IN THE REAR STRUCTURE. ALL AREAS
 WERE CONVERTED TO LIVING AREA. PALM BEACH COUNTY TO
 DETERMINE IF FEES ARE DUE OR NOT.
  
 7- SPECIFY CARBON MONOXIDE ALARMS IN PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 *** PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** CONTRACTOR TO REPLACE ANY REVISED SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-05 Time 11:41 Rev Time 0.00
Received By dhayes Date 2014-11-06 Time 15:22 Sent To  
Notes
2014-11-05 11:18:07NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 14:06 Rev Time 0.00
Received By dhayes Date 2014-09-04 Time 13:56 Sent To  
Notes
2014-09-04 14:56:42DATE: 9/4/2014
 PROJECT: ACKER
 PERMIT#: 14070255
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR
 STRUCTURE, A METAL PIPING SYSTEM(S), INCLUDING GAS
 PIPING SHALL BE BONDED. .250.104(3)(B) OTHER METAL
 PIPING.
  
 2) PROVIDE A LIGHTING OUTLET AND SWITCH AT THE ATTIC
 ACCESS. 210.70(A)(3)
  
 3) CEILING FAN BOXES SHALL COMPLY WITH THE PROVISIONS
 OF NEC 314.27(D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 11:15 Rev Time 0.00
Received By jgomez Date 2014-11-05 Time 11:15 Sent To  
Notes
2014-11-05 11:15:58NO GAS WORK EXCEPT FOR CAPPING OF THE LINES. NEED GAS
 PERMIT. JG.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-01 Cont ID  
Sent By jgomez Date 2014-08-01 Time 11:58 Rev Time 0.00
Received By jgomez Date 2014-08-01 Time 11:58 Sent To  
Notes
2014-08-01 12:21:06RESIDENTIAL (R3) ALTERATION, GAS REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO REVISE THE GAS ISOMETRIC:
 A) CLARIFY/REVISE SIZE OF PIPE AT THE POINT OF DELIVERY
 (METER). ISOMETRIC CALLS FOR 1/2", WHILE FLOOR PLANS
 SHOWS 3/4". REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) GAS ISOMETRIC SHOWN IS BASED ON TABLE 402.4(20).
 THIS TABLE IS FOR POLYETHYLENE PLASTIC PIPE WITH AN
 INLET PRESSURE OF 2.0 PSI. GAS ISOMETRIC TO SHOW
 PRESSURE REGULATORS FOR ALL THE APPLIANCES AS REQUIRED
 BY SEC. G2421.1(410.1) OF 2010 FBC-RESIDENTIAL. LINE
 PRESSURE REGULATOR SHALL BE INSTALLED WHERE THE
 APPLIANCE IS DESIGNED TO OPERATE AT A LOWER PRESSURE
 THAN THE SUPPLY PRESSURE.
  
 ***NOTE: SEPARATE GAS PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-03 Cont ID  
Sent By jgomez Date 2015-02-03 Time 17:06 Rev Time 0.00
Received By jgomez Date 2015-01-26 Time 11:13 Sent To  
Notes
2015-01-27 11:14:14RE-SUBMITTAL SENT TO JULIO GOMEZ FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-06 Cont ID  
Sent By dhayes Date 2014-11-06 Time 15:22 Rev Time 0.00
Received By dhayes Date 2014-10-22 Time 17:20 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 15:04 Rev Time 0.00
Received By dhayes Date 2014-07-09 Time 18:05 Sent To  
Notes
2014-07-09 18:05:11R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 11:16 Rev Time 0.00
Received By jgomez Date 2014-11-05 Time 11:16 Sent To  
Notes
2014-11-05 11:17:07NO FEES DUE. MU-2014-21152. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 11:23 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 11:23 Sent To  
Notes
2014-07-31 11:24:431-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-02-03 Cont ID  
Sent By jgomez Date 2015-02-03 Time 16:52 Rev Time 0.00
Received By jgomez Date 2015-02-03 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 14:27 Rev Time 0.00
Received By jgomez Date 2014-11-05 Time 14:27 Sent To  
Notes
2014-11-05 14:34:56RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT LISTED ON DRAWING P/M SUBMITTED DOESN'T
 MATCH EQUIPMENT LISTED IN THE EQUIPMENTS SIZING SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2
 OF 2010 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-01 Cont ID  
Sent By jgomez Date 2014-08-01 Time 08:24 Rev Time 0.00
Received By jgomez Date 2014-08-01 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By jgomez Date 2015-02-03 Time 17:06 Rev Time 0.00
Received By jgomez Date 2015-02-03 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 16:37 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-28 Cont ID  
Sent By dhayes Date 2014-11-06 Time 15:22 Rev Time 0.00
Received By llouie Date 2014-10-28 Time 15:45 Sent To B
Notes
2014-10-28 15:49:37NOTES:
 - PROPERTY IS ZONED SF7; HOWEVER, TWO (2) UNITS ARE
 VESTED ON THE PROPERTY PER GREEN CARD #214-146 (PRIMARY
 STRUCTURE AND REAR ACCESSORY STRUCTURE).
 - INTERIOR MODIFICATIONS ONLY; NO CHANGE TO BUILDING
 FOOTPRINTS.
 - LANDSCAPE PERMIT REFERENCE: PERMIT #14100890.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-15 Cont ID  
Sent By llouie Date 2014-07-15 Time 14:33 Rev Time 0.00
Received By llouie Date 2014-07-15 Time 14:33 Sent To  
Notes
2014-07-15 14:34:26** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($50,000) EXCEEDS 50
 PERCENT OF THE STRUCTURE'S VALUE ($56,168) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT
 SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE
 INTO CONFORMITY.
  
 2.) A NEW A/C UNIT IS PROPOSED IN THE SCOPE OF WORK.
 PROVIDE A SURVEY SHOWING THE LOCATION OF THE EXISTING
 BUILDINGS AND THE LOCATION OF THE A/C UNIT IN
 RELATIONSHIP TO THE PROPERTY LINES.
  
 3.) CLARIFICATION NEEDS TO BE PROVIDED IN THE WORK
 DESCRIPTION IN THE PERMIT APPLICATION AND THE SCOPE OF
 WORK PROVIDED IN THE PLANS. THE PERMIT APPLICATION
 SPECIFIES THAT WORK WILL ONLY BE COMPLETED IN THE
 PRIMARY STRUCTURE; HOWEVER, THE PLANS INDICATE THAT
 IMPROVEMENTS WILL BE DONE ON THE REAR ACCESSORY
 STRUCTURE. PLEASE CONTACT ONE OF THE PERMITTING CLERKS
 AT (561) 805-6700 TO MAKE ANY NECESSARY CORRECTIONS.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
2014-07-11 15:21:457/11/14