| 2014-08-12 16:40:29 | DATE: 8/12/2014 |
| | PROJECT: JEFFERSON AT PALM BEACH LAKES |
| | PERMIT#: 14070236 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | SHEET E1.61 |
| | 1) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT |
| | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL |
| | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND |
| | BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC |
| | 700.12(F) THE CIRCUITING FOR EGRESS ILLUMINATION SHALL |
| | BE INCLUDED ON THE PLANS. |
| | |
| | 2) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| | LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| | SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| | CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| | KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| | DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. NEC314.27(D) INDICATE A NOTE ON THE PLAN FOR |
| | CEILING FAN BOX SUPPORT. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |