Plan Review Details - Permit 14070166
Plan Review Stops For Permit 14070166
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-22 Cont ID  
Sent By dhayes Date 2014-07-22 Time 07:14 Rev Time 0.00
Received By dhayes Date 2014-07-22 Time 07:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-18 Cont ID  
Sent By dhayes Date 2014-07-18 Time 11:42 Rev Time 0.00
Received By dhayes Date 2014-07-18 Time 11:42 Sent To  
Notes
2014-07-18 12:14:29DATE: 7/18/2014
 PROJECT: FIRE ALARM FOR NEW BUILDOUT 400 N. CONGRESS.
 PERMIT#: 14070166
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE NAC POWER SUPPLY CALCULATIONS INDICATING
 CAPACITY TO SUPPORT THE ADDITIONAL LOAD. SHOW THE
 EXISTING DEVICE LOAD AND THE NEW LOAD ADDED FROM THE
 NEW DEVICES.
  
 2) REVISE THE RISER TO MATCH THE NAC POWER SUPPLY
 CALCULATIONS AND THE FLOOR PLAN. THE FLOOR PLAN
 CURRENTLY INDICATES 7 NEW NAC DEVICES AND ONE
 INITIATING DEVICE. THE RISER INDICATESA TOTAL OF 14 NEW
 DEVICES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-11 Cont ID  
Sent By pleduc Date 2014-07-11 Time 12:08 Rev Time 0.00
Received By pleduc Date 2014-07-11 Time 12:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-22 Cont ID  
Sent By dhayes Date 2014-07-22 Time 07:14 Rev Time 0.00
Received By dhayes Date 2014-07-21 Time 16:46 Sent To  
Notes
2014-07-21 16:46:40RE-SUBMITTAL SENT TO DAVID HAYES' DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-18 Cont ID  
Sent By dhayes Date 2014-07-18 Time 12:14 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2014-07-11 10:58:03ROUTED TO FIRE