Plan Review Details - Permit 14070148
Plan Review Stops For Permit 14070148
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 14:05 Rev Time 0.00
Received By dhayes Date 2014-07-08 Time 14:05 Sent To  
Notes
2014-07-08 14:21:21DATE: 7/8/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 2) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 3) VERIFY THE EXISTING HOME ALSO HAS SMOKE DETECTORS
 AND CARBON MONOXIDE DETECTORS. REMODELING OF AN
 EXISTING STRUCTURE IS REQUIRED TO INCLUDE
 INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND OUTSIDE
 EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 5) ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 14:05 Rev Time 0.00
Received By dhayes Date 2014-07-07 Time 13:07 Sent To  
Notes
2014-07-07 13:08:10ROUTED TO ELECTRICAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved