| 2014-07-05 11:59:09 | BUILDING PLAN REVIEW |
| | PERMIT: 14070081 |
| | ADD: 316 ELLAMAR RD. |
| | CONT: VERSATILE BUILDERS |
| | TEL: (561)845-9421 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 05/2014 |
| | ACTION: DENIED |
| | |
| | 1) . SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. |
| | |
| | 2). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| | 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | THE TABLE SUBMITTED IS NOT A CURRENT TABLE FROM EITHER |
| | THE 2010 FLORIDA RESIDENTUAL OR BUILDING - FUEL-GAS |
| | CODES. |
| | |
| | 3). SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 4). SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 THE SUBMITTED CUR SHEET |
| | LIST RHEEM, PALOMA/ WAI WELA, RUUD, RICHMOND AS |
| | PRODUCTS ALL COVERED UNDER THIS SPEC SHEET, WHICH |
| | MANUFACTURER IS IT. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |