Plan Review Details - Permit 14070063
Plan Review Stops For Permit 14070063
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 11:13 Rev Time 0.00
Received By jgomez Date 2014-09-16 Time 11:13 Sent To  
Notes
2014-09-16 11:15:49BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOORS AS SHOWN ON PLANS.
 B) CABANA EXTERIOR DOOR AS SHOWN ON PLANS.
 C) ARCHED FIXED WINDOW 5'-0" X 6'-6" IN GARAGE AS SHOWN
 ON PLANS.
 D) SLIDING GLASS DOORS. NOA 11-1018.14 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 E) 9'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
 NOA SUBMITTED IS FOR 16'-2" DOORS.
 F) ROOF TILE. PROVIDE CURRENT REVISED FLORIDA PRODUCT
 APPROVAL FL3505-R6 AND REVISED ESR 1775. ONE SUBMITTED
 IS FL3506-R5.
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
 3- A) WINDOWS FOR BEDROOM #3 AND #4 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #3 AND
 #4 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE
 MINIMUM OPENINGS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL (NEED TO VERIFY MIN. CLEAR WIDTH, MIN.
 CLEAR HEIGHT AND TOTAL MIN. CLEAR AREA).
 4- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS
 SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL.
 5- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR
 #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010
 FBC-RESIDENTIAL.
 6- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION):
 A) REVISE DOORS INFORMATION ON PAGE 3 OF 6. SEE PLANS
 AND PRODUCT APPROVALS SUBMITTED. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION TO SEE HOW TO CALCULATED
 DOOR WITH GLAZING.
 B) COORDINATE COOLING AND HEATING INFORMATION WITH THE
 A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO,
 INCLUDE THE UNIT LOCATED IN THE GARAGE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-15 Cont ID  
Sent By jgomez Date 2014-09-12 Time 14:21 Rev Time 0.00
Received By jgomez Date 2014-09-12 Time 14:21 Sent To  
Notes
2014-09-12 14:35:33NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOORS AS SHOWN ON PLANS.
  
 B) CABANA EXTERIOR DOOR AS SHOWN ON PLANS.
  
 C) ARCHED FIXED WINDOW 5'-0" X 6'-6" IN GARAGE AS SHOWN
 ON PLANS.
  
 D) SLIDING GLASS DOORS. NOA 11-1018.14 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
  
 E) 9'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
 NOA SUBMITTED IS FOR 16'-2" DOORS.
  
 F) ROOF TILE. PROVIDE CURRENT REVISED FLORIDA PRODUCT
 APPROVAL FL3505-R6 AND REVISED ESR 1775. ONE SUBMITTED
 IS FL3506-R5.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 3- A) WINDOWS FOR BEDROOM #3 AND #4 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #3 AND
 #4 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE
 MINIMUM OPENINGS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL (NEED TO VERIFY MIN. CLEAR WIDTH, MIN.
 CLEAR HEIGHT AND TOTAL MIN. CLEAR AREA).
  
 4- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS
 SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL.
  
 5- CLARIFY BLOCKED DIAPHRAGM ROOF ON SHEET S203. IT'S
 NOT CLEAR IS USING RING SHANK NAILS OR NOT. SEC.
 R803.2.3.1 REQUIRES RING SHANK NAILS.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR
 #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010
 FBC-RESIDENTIAL.
  
 7- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION):
 A) PROVIDE THE JURISDICTION NUMBER ON TOP OF FORM
 B) REVISE DOORS INFORMATION ON PAGE 3 OF 6. SEE PLANS
 AND PRODUCT APPROVALS SUBMITTED. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION TO SEE HOW TO CALCULATED
 DOOR WITH GLAZING.
 C) COORDINATE COOLING AND HEATING INFORMATION WITH THE
 A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO,
 INCLUDE THE UNIT LOCATED IN THE GARAGE.
  
 *****NOTES:
 * PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ** PLEASE REPLACE EACH REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By jgomez Date 2014-07-29 Time 14:33 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 14:33 Sent To  
Notes
2014-07-29 14:34:07NEW SINGLE FAMILY RESIDENCE(R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL EXTERIOR DOORS, INCLUDING THE ARCHED ENTRY DOOR
 WITH SIZE AS SHOWN ON PLANS.
 B) ALL WINDOW TYPES SHOWN ON PLANS.
 C) WINDOW AND DOOR MULLIONS. *****NOTE: CLEARLY SPECIFY
 MULLION SIZE AND FASTENING TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES.
 D) ROOF TILE.
 E) ROOF TILE ADHESIVE (IF SPECIFIED BY THE DESIGNER OF
 RECORD). COORDINATE WITH ADHESIVES LISTED IN TILE
 PRODUCT APPROVAL.
 F) FLAT ROOF. IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE RAS 117 CALCULATIONS IF REQUIRED.
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 H) GARAGE DOORS.
 I) PRECAST LINTELS AS SPECIFIED ON PLANS.
 J) "PHANTOM SCREEN" SHOWN ON FLOOR PLAN AND BUILDING
 SECTION A-A. ***NOTE: PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 4- A) WINDOWS FOR BEDROOM #2 AND #3 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #2
 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE MINIMUM
 OPENINGS REQUIRED BY SEC. R310 OF 2010 FBC-RESIDENTIAL
 (NEED TO VERIFY MIN. CLEAR WIDTH, MIN. CLEAR HEIGHT AND
 TOTAL MIN. CLEAR AREA).
  
 5- ALL DRAWINGS NEED TO HAVE THE ARCHITECT'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES.
 SIGNATURE STAMP IS NOT ALLOWED.
  
 6- PROVIDE MANUFACTURER'S SPECS FOR BBQ GRILL DESIGNED
 TO BE INSTALLED IN PORCH AS SHOWN ON PLANS. SEC.
 G2408.1 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION FOR THE NEW BUILDING WAS UPDATED TO
 $627,910 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS TO
 FBC. THE PERMIT FEE BALANCE IS $10,797.14.
  
 10- SHEET A201: SPECIFY ATTIC ACCESS SIZE FOR ATTIC
 ACCESS SHOWN IN GARAGE. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE 48" H. METAL DEC. FINIAL SHOWN ON
 THE ELEVATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 12- DESIGNER OF RECORD TO PROVIDE COMPLETE ROOF TILE
 FASTENING SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC. IF USING NAILS OR SCREWS, THEN
 SPECIFY SIZE AND NUMBER OF NAILS/SCREWS PER TILE.
 COORDINATE INFORMATION WITH WALL SECTION IN SHEET A801.
  
 13- WALL SECTION ON SHEET A801: COORDINATE INFORMATION
 SHOWN ON PLANS WITH INFORMATION SHOWN ON THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. FOR EXAMPLE CHECK ROOF TYPE OF INSULATION
 (BATT INSULATION OR ICYNENE INSULATION), VENTED OR
 UNVENTED ATTIC, ETC. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
 ***NOTE: CHECK ICYNENE ICC REPORT FOR LIMITATIONS ON
 MAX. THICKNESSS AND R-VALUE.
  
 14- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS
 SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: CLARIFY IF USING WOOD OUTRIGGERS OR FOAM
 OUTRIGGERS KEY NOTES ON SHEET A301 CALLS FOR WOOD,
 WHILE ELEVATIONS AND WALL SECTION CALL FOR FOAM. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 15- PROVIDE EVALUATION REPORT FOR THE ICYNENE
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL. ***NOTE: SEE LIMITATIONS FOR MAXIMUM
 THICKNES AND R-VALUE. COORDINATE WITH ENERGY
 CALCULATIONS.
  
 16- SHEET A801: REVISE ALL THE WINDOWS AND DOORS
 STRUCTURAL BUCK DETAILS. BUCK NEEDS TO PROVIDE FULL
 SUPPORT TO THE DOOR AND WINDOW FRAME AS REQUIRED BY
 SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 17- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PROVIDE PLANS SHOWING NUMBER OF CEILING FANS
 AND SIZES IN ALL ROOMS AS REQUIRED BY SEC. 405.6.6 AND
 TABLE 405.6.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 18- SHEET S203: REVISE THE "BLOCKED DIAPHRAGM ROOF".
 NEED TO SPECIFY RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ALSO, SPECIFY ROOF
 NAILING SPACING FOR ROOF ZONE #3. OTHERWISE, PROVIDE
 CALCULATIONS SHOWING THAT THE SPECIFIED NAILS WILL HAVE
 THE SAME OR BETTER VALUE THAN THE RING SHANK NAILS.
 SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 19- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR
 #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010
 FBC-RESIDENTIAL.
  
 20- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION):
 A) NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS.
 B) REVISE NAME OF BUILDER AND PROVIDE THE JURISDICTION
 NUMBER ON TOP OF FORM
 C) CLARIFY IF VENTED OR UNVENTED ATTIC. SEE PLANS.
 D) CLARIFY DOORS INFORMATION ON PAGE 3 OF 6: WHERE ARE
 THE INSULATED AND WOOD DOORS LOCATED ON PLANS? ALSO,
 COORDINATE WITH THE PRODUCT APPROVALS. CLARIFY DOOR
 WIDTH, DOOR HEIGHT AND DOOR AREA SHOWN.
 E) CLARIFY WINDOWS INFORMATION ON PAGE 4 OF 6: CLARIFY
 THE OVERHANG SEPARATION SHOWN . SEE PLANS.
 F) COORDINATE COOLING AND HEATING INFORMATION WITH THE
 A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO,
 INCLUDE THE UNIT LOCATED IN THE GARAGE.
  
 21- SHEET A901:
 A) REVISE ALL WINDOWS AND DOORS BUCK DETAILS. SEC.
 R612.10.2 OF 2010 FBC-RESIDENTIAL. COORDINATE WITH ITEM
 #16 ABOVE.
 B) UPDATE THE EXTERIOR WINDOW & DOOR GENERAL NOTES:
 (1)REVISE THE WIND LOAD. SPECIFY THE ULTIMATE AND
 NOMINAL WIND LOADS. SEC. R301.2.1.3 OF 2010
 FBC-RESIDENTIAL. (2)UPDATE BUILDING CODE CITED.
  
 *****NOTES:
 * PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ** PLEASE REPLACE EACH REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-14 Cont ID  
Sent By rlecky Date 2014-08-14 Time 12:25 Rev Time 0.00
Received By rlecky Date 2014-08-14 Time 11:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-09-15 Cont ID  
Sent By jgomez Date 2014-09-15 Time 13:54 Rev Time 0.00
Received By jgomez Date 2014-09-15 Time 13:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-07-31 Cont ID  
Sent By jgomez Date 2014-07-31 Time 08:26 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 08:26 Sent To  
Notes
2014-07-31 09:00:14NEW SINGLE FAMILY RESIDENCE (R3) GAS REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO PROVIDE ORIGINAL SIGNATURE ON PLANS AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 ***NOTE: GAS PERMIT IS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 11:12 Rev Time 0.00
Received By jgomez Date 2014-09-16 Time 11:12 Sent To  
Notes
2014-09-16 11:12:58MET WITH MR. SHELDON. HE WANTS PERMIT WITH PROVISO:

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-15 Cont ID  
Sent By jgomez Date 2014-09-15 Time 13:54 Rev Time 0.00
Received By jgomez Date 2014-09-04 Time 15:20 Sent To  
Notes
2014-09-04 15:20:38SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-19 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 10:01 Sent To  
Notes
2014-07-03 10:01:22INCOMING SENT TO R04 . JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By jgomez Date 2014-09-12 Time 14:35 Rev Time 0.00
Received By jgomez Date 2014-09-12 Time 14:35 Sent To  
Notes
2014-09-12 14:36:56MU-2014-20093. $9,904.34 PAID.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 14:37 Rev Time 0.00
Received By jgomez Date 2014-07-29 Time 14:34 Sent To  
Notes
2014-07-29 14:39:071- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-09-16 Cont ID  
Sent By jgomez Date 2014-09-16 Time 11:22 Rev Time 0.00
Received By jgomez Date 2014-09-16 Time 11:22 Sent To  
Notes
2014-09-16 11:24:11MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) NEED TO COORDINATE THE EQUIPMENT SIZING CALCULATIONS
 WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED TO MATCH THE WINDOWS/DOORS U-FACTOR
 AND SHGC FACTOR, THE CEILING INSULATION R-VALUE, ETC.
  
 B) CALCULATIONS ARE TAKING INTO CONSIDERATION 62
 PEOPLE. THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE
 NOT 62 PEOPLE TO BE CONSIDERED FOR EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) THE LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE
 LESS THAN THE CALCULATED LATENT LOAD. REVISE EQUIPMENT
 FOR SYSTEM 1 AS REQUIRED. SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- A/C PLAN SUBMITTED:
 A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. THE GARAGE EQUIPMENT SHOWN ON A/C PLAN
 DOESN'T MATCH THE ONE SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS.
  
 B) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR
 UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL AND REVISE ORIGINAL NOTE AS REQUIRED.
  
 C) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. REVISE ORIGINAL
 DRAWING TO INCLUDE THE RETURN AIR GRILL.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-09-15 Cont ID  
Sent By jgomez Date 2014-09-15 Time 11:49 Rev Time 0.00
Received By jgomez Date 2014-09-15 Time 11:49 Sent To  
Notes
2014-09-15 12:43:09NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST
 CODE: 2010 FBC.
  
  
 1-EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) NEED TO COORDINATE THE EQUIPMENT SIZING CALCULATIONS
 WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED TO MATCH THE WINDOWS/DOORS U-FACTOR
 AND SHGC FACTOR, THE CEILING INSULATION R-VALUE, ETC.
  
 B) CALCULATIONS ARE TAKING INTO CONSIDERATION 62
 PEOPLE. THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE
 NOT 62 PEOPLE TO BE CONSIDERED FOR EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) THE LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE
 LESS THAN THE CALCULATED LATENT LOAD. REVISE EQUIPMENT
 FOR SYSTEM 1 AS REQUIRED. SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- A/C PLAN SUBMITTED:
 A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. THE GARAGE EQUIPMENT SHOWN ON A/C PLAN
 DOESN'T MATCH THE ONE SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS.
  
 B) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR
 UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL AND REVISE ORIGINAL NOTE AS REQUIRED.
  
 C) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. REVISE ORIGINAL
 DRAWING TO INCLUDE THE RETURN AIR GRILL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By jgomez Date 2014-07-30 Time 10:54 Rev Time 0.00
Received By jgomez Date 2014-07-30 Time 10:54 Sent To  
Notes
2014-07-30 10:56:02NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC.
 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 2- EQUIPMENT CALCULATIONS SUBMITTED: SELECTED EQUIPMENT
 FOR SYSTEM #1 AND SYSTEM #2 DON'T COMPLY WITH SEC.
 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. SELECTED
 EQUIPMENT EXCEEDS THE 1.15 TIMES GREATER THAN THE TOTAL
 LOAD CALCULATED. REVISE AS REQUIRED.
  
 3- A/C PLAN SUBMITTED:
 A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) GARAGE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE EQUIPMENT SIZING CALCULATIONS.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR
 UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 D) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected].
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-15 Cont ID  
Sent By jgomez Date 2014-09-15 Time 13:36 Rev Time 0.00
Received By jgomez Date 2014-09-15 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-30 Cont ID  
Sent By jgomez Date 2014-07-30 Time 17:14 Rev Time 0.00
Received By jgomez Date 2014-07-30 Time 17:14 Sent To  
Notes
2014-07-30 17:23:15NEW SINGLE FAMILY RESIDENCE (R3) PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO PROVIDE ORIGINAL SIGNATURE ON PLANS AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-08 Cont ID  
Sent By dkittred Date 2014-09-08 Time 08:40 Rev Time 0.00
Received By dkittred Date 2014-09-05 Time 14:50 Sent To  
Notes
2014-09-08 08:42:309/8/14 - SENT TO JG. DK

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By dkittred Date 2014-07-09 Time 10:59 Rev Time 0.00
Received By dkittred Date 2014-07-08 Time 10:02 Sent To  
Notes
2014-07-09 10:58:59PLANNING AND ZONING COMMENTS: UPDATE
  
 7/10/14
  
 APPLICANT HAS SUFFICIENTLY REVISED PLANS IN ACCORDANCE
 WITH COMMENT #1 BELOW AND WILL RESUBMIT TO ADDRESS THE
 COMMENTS. ADDITIONALLY, THE APPLICANT HAS COMPLETED A
 LANDSCAPING CONDITIONAL APPROVAL FORM IN ACCORDANCE
 WITH COMMENT #2. DK
  
  
 PLANNING AND ZONING COMMENTS: ***FAILED***
  
 7/9/14
  
 COMMENT(S) TO BE ADDRESSED:
  
 1. THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE
 FRONT YARD AREA SHALL BE IMPERVIOUS AREA [ZLDR SEC.
 94-482(A)]. THE FRONT SETBACK FOR THIS PROPERTY IS 10
 FEET AND SHOULD BE UTILIZED FOR THIS CALCULATION.
 PLEASE PROVIDE CALCULATION AND DEMONSTRATE COMPLIANCE.
 THIS ITEM IS BEING REVIEWED BECAUSE THE PERMIT
 APPLICATION INDICATES INSTALLATION OF THE PAVER
 DRIVEWAY. IF THESE PAVERS WILL BE INSTALLED UNDER A
 SEPARATE PERMIT, PLEASE NOTIFY ME SO THE COMMENT CAN BE
 ADJUSTED.
  
 2. STAFF IS WAITING ON SUBMITTAL AND APPROVAL OF
 CONDITIONAL APPROVAL FORM FOR LANDSCAPING.
  
 GENERAL COMMENT(S):
  
 3. MECHANICAL EQUIPMENT CANNOT ENCROACH INTO A REQUIRED
 SETBACK MORE THAN 4 FEET [ZLDR SEC. 94-305(B)(4)]. A
 NOTATION HAS BEEN ADDED TO THE PLANS.
  
 4. SEPARATE PERMITS WILL BE REQUIRED FOR THE POOL AND
 POOL EQUIPMENT, GENERATOR, AND LANDSCAPING. PLEASE NOTE
 THAT AT THE TIME OF SUBMITTAL OF THE LANDSCAPE PERMIT,
 PLANTING OF TREES IN THE UTILITY EASEMENT WILL NOT BE
 PERMITTED UNLESS AN EASEMENT CONSENT FORM HAS BEEN
 COMPLETED AND APPROPRIATE APPROVALS RECEIVED.
 ADDITIONALLY, THE LANDSCAPE PERMIT WILL NEED TO INCLUDE
 PROPER SCREENING OF MECHANICAL EQUIPMENT ON THE PLAN.
  