| 2014-07-24 09:15:22 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ARCHITECT TO REVISE DESIGN CRITERIA ON SHEET A-10: |
| | A) CLARIFY WHY THE WIND NET UPLIFT IS ONLY FOR ZONES 1 |
| | AND 2?. NEED WIND LOADS FOR ALL ZONES. SEC. R301 OF |
| | 2010 FBC-RESIDENTIAL. |
| | B) REVISE THE BASIC WIND VELOCITY. SPECIFY THE ULTIMATE |
| | WIND LOAD AND THE NOMINAL WIND LOAD AS REQUIRED BY SEC. |
| | R301.2.1.3 OF 2010 FBC-RESIDENTIAL. (NOTE: ULTIMATE |
| | WIND SPEED FOR CITY OF WEST PALM BEACH IS 170MPH). |
| | C) REVISE OCCUPANCY. THIS IS NOT 1. THIS IS A SINGLE |
| | FAMILY RESIDENCE (R3). |
| | |
| | 2- ARCHITECT TO REVISE ALL THE WINDOWS AND DOORS DESIGN |
| | PRESSURES SHOWN ON THE EXTERIOR ELEVATIONS. THEY DO NOT |
| | CORRESPOND TO EXPOSURE "C" ACCORDING TO HEIGHT AND |
| | OPENING LOCATION (INTERIOR OR END LOCATION). OR PROVIDE |
| | COMPLETE CALCULATIONS SHOWING HOW THE DESIGN PRESSURES |
| | SHOWN WERE CALCULATED. SEC. R301.2.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF COVER. NONE SUBMITTED. GENERAL NOTES ON COVER |
| | SHEET INDICATES NEW ROOF AS PART OF THE SCOPE OF WORK. |
| | ***NOTE: A ROOFING SUB-PERMIT IS REQUIRED ALSO. |
| | B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS, DETAILS AND SPECIFICATIONS. |
| | C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE |
| | DOWNLOAD CURRENT NOA AND RE-SUBMIT. PROVIDE 2 COPIES |
| | ONLY ONE SUBMITTED. |
| | D) FRENCH DOORS NOA 11-1013.24. ONLY ONE COPY |
| | SUBMITTED. PROVIDE ANOTHER COPY. |
| | E) CASEMENT WINDOWS NOA 11-1006.05. ONLY ONE COPY |
| | SUBMITTED. PROVIDE ANOTHER COPY. |
| | F) FIXED WINDOWS NOA 11-1021.17. ONLY ONE COPY |
| | SUBMITTED. PROVIDE ANOTHER COPY. |
| | G) ROUND CASEMENT WINDOW AS SHOWN ON ELEVATIOINS. |
| | |
| | 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 5- ARCHITECT TO REVISE WINDOW AND DOOR SCHEDULES TO |
| | MATCH PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE FRENCH |
| | DOORS PRODUCT APPROVAL SUBMITTED IS FOR ALUMINUM DOORS |
| | NOT WOOD. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 6- SHEET A-2: |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | INTERIOR HANDRAIL TO BE REPLACED TO VERIFY COMPLIANCE |
| | WITH TABLE R301.5 AND SEC. R311.7.7 OF 2010 |
| | FBC-RESIDENTIAL. |
| | B) POWDER ROOM #105. EXISTING WINDOW IS GOING TO BE |
| | BLOCKED. PROVIDE SPECIFICATIONS FOR VENTILATION. SEC. |
| | R303.3 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- A) WINDOW SCHEDULE ON SHEET A-5 IS MISSING WINDOW |
| | "N". PROVIDE INFORMATION FOR WINDOW "N" TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 604.1 |
| | OF 2010 FBC-EXISTING BUILDING. |
| | B) CLARIFY WINDOW "B". IS IT A CASEMENT OR FIXED |
| | WINDOW?. IS IT ROUND OR SQUARE TOP?. EXTERIOR ELEVATION |
| | SHOWS ROUND TOP. CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 8- SHEET A-4: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY TO |
| | VERIFY COMPLIANCE WITH TABLE R301.5 AND SEC. R312 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON |
| | FIRST FLOOR. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 10- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK |
| | DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR |
| | FRAME AS REQUIRED BY SEC. R612.10.2.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |