Plan Review Details - Permit 14070011
Plan Review Stops For Permit 14070011
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-05 Cont ID  
Sent By dhayes Date 2014-08-05 Time 11:27 Rev Time 0.00
Received By dhayes Date 2014-08-05 Time 09:41 Sent To  
Notes
2014-08-05 11:27:12DATE: 8/5/2014
 PROJECT: TENANT IMPROVEMENT SUITE 115, 116
 PERMIT#: 14070011
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ONLY A PORTION OF THIS RENOVATION PROJECT HAS BEEN
 INDICATED TO HAVE AUTOMATIC LIGHTING SHUT OFF. IN THE
 AREAS OF THE PROJECT MARKED WITH A NOTE 2 STATING
 "EXISTING WIRING TO REMAIN AS IS" SHALL BE EQUIPPED
 WITH AUTOMATIC LIGHTING CONTROLS AS WELL. SEE THE FBC
 SECTION BELOW THAT REQUIRES AUTOMATIC LIGHTING CONTROL.
  
 2) A SIGN CIRCUIT IS REQUIRED AT EACH TENANT SPACE
 ACCESSIBLE BY PEDESTRIANS. SEE THE NEC CODE ARTICLE
 BELOW THAT REQUIRES A SIGN CIRCUIT AND THE FBC-ENERGY
 THAT REQUIRES AUTOMATIC CONTROL OF THAT CIRCUIT.
  
 3) REVISE THE PANEL SCHEDULE AND LOAD CALCULATION TO
 REFLECT THE REQUIRED SIGN CIRCUIT.
  
 CODE REFERENCES
 FBC-ENERGY
 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS
 LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS.
  
 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 NEC 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED
 AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-03 Cont ID  
Sent By pleduc Date 2014-07-03 Time   Rev Time 0.00
Received By pleduc Date 2014-07-03 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-05 Cont ID  
Sent By dhayes Date 2014-08-05 Time 11:58 Rev Time 0.00
Received By dhayes Date 2014-07-01 Time 06:51 Sent To  
Notes
2014-07-02 06:51:05B29

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By hmoser Date 2014-07-17 Time 14:55 Rev Time 0.00
Received By hmoser Date 2014-07-17 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 08:28 Sent To  
Notes
***NONE***