| 2014-07-02 18:17:05 | 2010 FBC |
| | |
| | REVISION IS DENIED |
| | |
| | 1) BECAUSE THE REVISED PAGE IS NOT REPLACING SHEET S.01 |
| | OF THE APPROVED STRUCTURAL PLANS, IT SHOULD NOT BE |
| | NUMBERED AS S-1. PLEASE USE A NUMBER FOR THE REVISED |
| | PLAN THAT WILL NOT BE CONFUSED WITH SHEETS S.01 OR S.02 |
| | OF THE APPROVED PLANS. CITY AMENDMENTS 107.2.1.4 AND FS |
| | 471 |
| | |
| | 2) THE DESIGNER OF RECORD FOR THIS PROJECT IS A FLORIDA |
| | LICENSED ARCHITECT, STEPHEN MICHAEL ROY. THE REVISED |
| | PLANS ARE SIGNED AND SEALED BY A FLORIDA LICENSED |
| | ENGINEER, JOHN HOLT. THERE IS NO STRUCTURAL OR |
| | CONSULTING ENGINEER SPECIFIED ON THE APPROVED PLANS. IN |
| | ORDER FOR THE REVISED PLANS TO BE ACCEPTED, THE |
| | DESIGNER OF RECORD WILL HAVE TO SUBMIT A LETTER STATING |
| | THAT THE ENGINEER IS RESPONSIBLE FOR THE STRUCTURAL |
| | WORK SHOWN ON HIS NEW PLANS OR THE REVISED PLANS WILL |
| | NEED TO BE STAMPED WITH THE ARCHITECT'S SHOP DRAWING |
| | REVIEW STAMP AND MARKED AS ACCEPTED. FS 471 AND 481 |
| | |
| | 3) THE EXPOSURE CATEGORY ON THE REVISED STRUCTURAL |
| | DRAWING IS INCORRECT. THE STRUCTURE IS LOCATED IN |
| | EXPOSURE CATEGORY 'D' . PLEASE CORRECT. FBCR |
| | 301.2.1.4.3 |
| | |
| | 4) DETAIL B ON S-1, SPECIFIES (2) 5/8" DIA. X 12" LONG |
| | THRU BOLTS TO THE MASONRY WALL WITH 8 " EMBED, BUT DOES |
| | NOT SPECIFY THE EPOXY THAT WILL BE USED TO ANCHOR IT |
| | AND THE DRAWING DOES NOT SHOW THE BOLT EXTENDING INTO |
| | THE FILLED CONCRETE BLOCK CELL. PLEASE CORRECT CITY |
| | AMENDMENTS 107.2.1 AND FBCR 301.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |