Plan Review Details - Permit 14061335
Plan Review Stops For Permit 14061335
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-30 Cont ID  
Sent By shill Date 2014-09-30 Time 14:34 Rev Time 0.00
Received By shill Date 2014-09-30 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-15 Cont ID  
Sent By shill Date 2014-08-15 Time 12:10 Rev Time 0.00
Received By shill Date 2014-08-15 Time 12:10 Sent To  
Notes
2014-08-15 12:16:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. I BELIEVE THAT THIS MAY A REPEAT COMMENT FOR
 THIS FIRM AND/OR ENGINEER. A SET HAS BEEN RETAINED.
  
 2. THE STRUCTURAL ANALYSIS LETTER AND THE PLANS DO NOT
 INCLUDE WIND DESIGN CRITERIA AS REQUIRED BY FBC
 1603.4.1. REVISE PLANS AND LETTER.
  
 3. METHOD OF MOUNTING IS CONFUSING. SHEET E1 GROUNDING
 PLAN REFERS TO RF DATA SHEET AND ALSO TO SHEET A11
 (WHICH DOES NOT EXIST IN THIS SET OF PLANS), NEITHER
 WHICH SPECIFIES FASTENERS. THIS APPEARS TO BE DONE IN
 THE LETTER. REVISE THE PLANS TO INCLUDE THE
 SPECIFICATION OR REMOVE/REVISE THE ERRONEOUS
 INFORMATION AND MAKE REFERENCE TO THE SPECIFIC LETTER
 INCLUDING DATE. VERIFY THAT ALL DETAILS WHICH REFERENCE
 OTHER SHEETS AND DETAILS ARE CORRECT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 16:29 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 16:29 Sent To  
Notes
2014-09-22 16:30:12TO MISC. 2
  
  
2014-09-08 18:23:53NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-15 Cont ID  
Sent By dhayes Date 2014-07-15 Time 08:51 Rev Time 0.00
Received By dhayes Date 2014-07-15 Time 08:51 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-30 Cont ID  
Sent By shill Date 2014-09-30 Time 14:34 Rev Time 0.00
Received By shill Date 2014-09-08 Time 18:22 Sent To  
Notes
2014-09-08 18:23:26RE-SUBMITTAL SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By shill Date 2014-08-15 Time 12:16 Rev Time 0.00
Received By shill Date 2014-06-30 Time 17:52 Sent To  
Notes
2014-06-30 17:52:09TO ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-22 Cont ID  
Sent By dkittred Date 2014-09-22 Time 08:45 Rev Time 0.00
Received By dkittred Date 2014-09-19 Time 12:57 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-10 Cont ID  
Sent By dkittred Date 2014-07-10 Time 09:33 Rev Time 0.00
Received By dkittred Date 2014-07-10 Time 08:55 Sent To E
Notes
2014-07-10 09:31:52PLANNING AND ZONING COMMENTS: ***FAILED***
  
 7/10/14
  
 1. SUBMITTAL AND APPROVAL OF A WIRELESS COMMUNICATION
 APPLICATION THROUGH THE PLANNING AND ZONING DIVISION IS
 REQUIRED. THIS REVIEW IS REQUIRED PRIOR TO ISSUANCE OF
 A BUILDING PERMIT FOR THE PROPOSED ROOFTOP ANTENNA
 MODIFICATIONS. THE APPLICATION CAN BE FOUND AT THE
 FOLLOWING LINK: HTTP://WPB.ORG/PLANNING/WP-CONTENT/UPLO
 ADS/SITES/37/2013/04/2014-WIRELESS-DEVELOPMENT-APPLICAT
 ION-REVISED-01.31.2014.PDF (NOTE: FOR THE ROOFTOP
 FACILITY THE TOTAL PLANNING AND ZONING APPLICATION FEE
 IS $1,550 WHICH INCLUDE $300 CITY FEE PLUS $1,250
 WIRELESS CONSULTANT FEE.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-07-01 12:52:537/1/14 ZONING SENT TO JR. SG