Plan Review Details - Permit 14061197
Plan Review Stops For Permit 14061197
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 12:42 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 11:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 06:00 Sent To  
Notes
2014-07-17 07:29:37BUILDING PLAN REVIEW
 REVISION: 14061197
 PERMIT: 14030368
 ADD: 3673 HISTORIC LN.
 CONT: L& H HOMEBUILDERS
 TEL: (561) 436-0668
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 17/2014
 ACTION: DENIED
  
 1) THE REVISION INDICATES THERE IS NO INCREASE IN THE
 VALUE OF THE WORK AND LIST THE REVISION AS CHANGE TO
 MASTER BEDROOM SUITES. THE ELECTRICAL SHEETS CLEARLY
 SHOW THE OPTION FOR A ELEVATOR HAS BEEN TAKEN. PLEASE
 INCREASE THE VALUE OF THE SCOPE OF WORK TO INCLUDE THE
 ELEVATOR AS WELL AS THE MOVING OF THE POWDER ROOM ON
 THE 1ST FLOOR. REMOVAL OF EXISTING CONCRETE FLOOR,
 EXISTING INGROUND WASTE, RE-PIPING OF WASTE AND THE
 REPOURING OF THE 1ST FLOOR SLAB. 108.3* BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE PROVIDE THE MANUFACTER'S SPECIFICATIONS FOR
 THE NEWLY PROPOSED RESIDENTIAL ELEVATOR. PLEASE INCLUDE
 IN THIS INFORMATION HARDWARE ON OPENING PROTECTIVES
 SHALL BE OF AN APPROVED TYPE INSTALLED AS TESTED,
 EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL LOCKS AND
 ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC CONTACTS AND
 DOOR-OPERATING MECHANISMS SHALL BE EXEMPT FROM THE FIRE
 TEST REQUIREMENTS. 3002.1.2.
  
 3) THE PLANS SHOW ON THE 1ST FLOOR THE WATER CLOSET
 BACKED UP UNDER THE STAIRS, PLEASE PROVIDE COMPLLIANCE
 WITH 2010 FBC-B 1208.2 MINIMUM CEILING HEIGHT FOR
 SLOPED CEILINGS. THIS INFORMATION IS NOT PROVIDED ON
 SHEET A.1. IN THE UNITS WITH THISTYPE OF CONDITION
 ADDITIONAL INFORMATION IS PROVIDED ON SHEET A2.1 THAT
 DEALS WITH SLOPED CEILINGS AND WATER CLOSETS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 06:00 Sent To  
Notes
2014-07-17 07:34:35ELECTRICAL PLAN REVIEW
 REVISION: 14061197
 PERMIT: 14030368
 ADD: 3673 HISTORIC LN.
 CONT: L& H HOMEBUILDERS
 TEL: (561) 436-0668
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 2008 NEC
  
 1ST REVIEW
 DATE: THURS. JULY 17/2014
 ACTION: DENIED
  
 1) THE REVISION INDICATES THERE IS NO INCREASE IN THE
 VALUE OF THE WORK AND LIST THE REVISION AS CHANGE TO
 MASTER BEDROOM SUITES. THE ELECTRICAL SHEETS CLEARLY
 SHOW THE OPTION FOR A ELEVATOR HAS BEEN TAKEN. PLEASE
 INCREASE THE VALUE OF THE SCOPE OF WORK TO INCLUDE THE
 ELEVATOR AS WELL AS THE MOVING OF THE POWDER ROOM ON
 THE 1ST FLOOR. REMOVAL OF EXISTING CONCRETE FLOOR,
 EXISTING INGROUND WASTE, RE-PIPING OF WASTE AND THE
 REPOURING OF THE 1ST FLOOR SLAB. 108.3* BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE PROVIDE THE MANUFACTER'S SPECIFICATIONS FOR
 THE NEWLY PROPOSED RESIDENTIAL ELEVATOR. PLEASE INCLUDE
 IN THIS INFORMATION HARDWARE ON OPENING PROTECTIVES
 SHALL BE OF AN APPROVED TYPE INSTALLED AS TESTED,
 EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL LOCKS AND
 ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC CONTACTS AND
 DOOR-OPERATING MECHANISMS SHALL BE EXEMPT FROM THE FIRE
 TEST REQUIREMENTS. 3002.1.2.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2014-08-06 Time   Sent To  
Notes
2014-08-06 18:23:57SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2014-06-26 Time 15:12 Sent To  
Notes
2014-06-27 15:12:59REVISION SENT TO JIM WITMER'S DESK FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 06:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 06:00 Sent To  
Notes
***NONE***