Plan Review Details - Permit 14061187
| Plan Review Stops For Permit 14061187 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-22 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-20 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2014-08-22 09:09:03 | BUILDING PLAN REVIEW | | | PERMIT: 14061187 | | | ADD: 900 FLORIDA AVE | | | CONT: COASTAL CONSTRUCTION | | | TEL: (561)630-3770 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | 2ND REVIEW | | | DATE: FRI. AUGUST 22/ 2014 | | | ACTION: BUILDING PROVISO | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | 1 THE OWNERS OF THE PROJECT ARE GOING TO THE STATE FOR | | | A WAIVER TO THE VERTICAL ACCESSIBILITY REQUIREMENTS. | | | NOTE 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS | | | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR | | | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY | | | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE | | | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE OR FACILITY. FL S 553.509 VERTICAL | | | ACCESSIBILITY. (1) THIS PART AND THE AMERICANS WITH | | | DISABILITIES ACT STANDARDS FOR ACCESSIBLE DESIGN DO NOT | | | RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE, OR | | | FACILITY GOVERNED BY THIS PART FROM THE DUTY TO PROVIDE | | | VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW | | | THE OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE, OR FACILITY. | | | IF THE WAIVER IS DENIED THEN THE OWNERS WILL BE | | | REQUIRED TO SUPPLY VERTICAL ACCESSIBILITY TO THE 2ND | | | FLOOR LEVEL. | | | | | | 2) REVISION REQUIRED, SPOKE WITH THE DESIGNER OF | | | RECORD. SHEET GA2.00 CONSTRUCTION TYPE LISTED AS IB | | | CONFLICT WITH 2010 FBC-B 3102.6 MIXED CONSTRUCTION. | | | 2010 FBC-B 406.3.6 OPEN PARKING GARAGES LESS THAN 75 | | | FT. IN HEIGHT UNLIMITED AREA WHEN THE TOTAL AREA OF | | | OPENINGS ALONG THE SIDE SHALL NOT BE LESS THAN 50 | | | PERCENT OF THE INTERIOR AREA OF THE SIDE AT EACH TIER | | | AND SUCH OPENINGS SHALL BE EQUALLY DISTRIBUTED ALONG | | | THE LENGTH OF THE TIER. ALL PORTIONS OF TIERS SHALL BE | | | WITHIN 200 FEET (60 960 MM) HORIZONTALLY FROM SUCH | | | OPENINGS OR OTHER NATURAL VENTILATION OPENINGS AS | | | DEFINED IN SECTION 406.3.3.1. THESE OPENINGS SHALL BE | | | PERMITTED TO BE PROVIDED IN COURTS WITH A MINIMUM | | | DIMENSION OF 20 FEET (6096 MM) FOR THE FULL WIDTH OF | | | THE OPENINGS. | | | THIS WILL ALLOW FOR THE MEMBRANE CANOPY ON A IIB | | | BUILDING AND CODE COMPLIANCE. | | | | | | 3) DEFERRED SUBMITTAL 107.3.4.2. SHEET GA8.00 NOTE # 27 | | | FIXED CANVAS CANOPY, THERE IS NO WIND DESIGN CRITERIA | | | FOR THIS PRODUCT NOR IS THERE . 2010 FBC-B 3102.7 | | | ENGINEERING DESIGN. THE STRUCTURE SHALL BE DESIGNED AND | | | CONSTRUCTED TO SUSTAIN DEAD LOADS; LOADS DUE TO TENSION | | | OR INFLATION; AND LIVE LOADS INCLUDING WIND LOADS AND | | | FLOOD IN ACCORDANCE WITH CHAPTER 16. | | | | | | 4) DEFERRED SUBMITTAL 107.3.4.2. PLEASE PROVIDE | | | COMPLIANCE WITH 2010 FBC-B 1607.7.3 VEHICLE BARRIER | | | SYSTEMS FOR THE 2ND FLOOR PERIMETER BARRIER AND RAMP. | | | VEHICLE BARRIER SYSTEMS FOR PASSENGER VEHICLES SHALL BE | | | DESIGNED TO RESIST A SINGLE LOAD OF 6,000 POUNDS (26.70 | | | KN) APPLIED HORIZONTALLY IN ANY DIRECTION TO THE | | | BARRIER SYSTEM AND SHALL HAVE ANCHORAGE OR ATTACHMENT | | | CAPABLE OF TRANSMITTING THIS LOAD TO THE STRUCTURE. | | | | | | 5A) DEFERRED SUBMITTAL 107.3.4.2.. SHEET GA8.00 NOTE # | | | 31 CABLE GUARDRAIL, GUARDRAILS ALSO INDICATE A FABRIC | | | SCREEN TO BE ATTACHED TO THE GUARDRAIL SYSTEM, PLEASE | | | PROVIDE INFORMATION ON FABRIC, COMPLIANCE WITH FIRE | | | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701. | | | | | | 5B) DEFERRED SUBMITTAL 107.3.4.2. SHEET GA8.00 NOTE # | | | 31 CABLE GUARDRAIL, GUARDRAILS ALSO INDICATE A FABRIC | | | SCREEN TO BE ATTACHED TO THE GUARDRAIL SYSTEM, SHOW | | | COMPLIANCE WITH : 3102.7 ENGINEERING DESIGN. THE | | | STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO SUSTAIN | | | DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; AND LIVE | | | LOADS INCLUDING WIND LOADS IN ACCORDANCE WITH CHAPTER | | | 16. | | | | | | 7) ROOF CANOPY IS TO BE UNDER A SEPARATE PERMIT. NOTE | | | CONTRACTOR CONTINUES AT OWN RISK. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-09 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-08 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2014-07-09 15:17:01 | BUILDING PLAN REVIEW | | | PERMIT: 14061187 | | | ADD: 900 FLORIDA AVE | | | CONT: COASTAL CONSTRUCTION | | | TEL: (561)630-3770 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: WED. JULY 09/2014 | | | ACTION: DENIED | | | | | | 1) 0110 GA2.00 NOTES FOR FIRE PROTECTION ARE CONFUSING, | | | IS OR IS NOT THIS STRUCTURE FIRE SPRINKLERED? | | | TABLE 1016.1 300' FOR OPEN PARKING GARAGES | | | NON-SPRINKLERED | | | 1018.4 DEAD END EXC # 2 50 FT W/ FIRE SPRINKLERS | | | 1014.3 COMMON PATH OF TRAVEL 50'-0" EXC # 8 PARKING | | | GAGARES | | | GFP1, GFP2 & GFP3 ONLY SHOW A DRY STAND PIPE SYSTEM. | | | GFA-2 INDICATES THE INSTALATION OF A TAMPER & FLOW | | | SWITCH. | | | | | | 2) 0150 GS0.00 INDICATES A GEOTECHNICAL SOILS | | | ENGINEERING REPORT WAS COMPLETED ON 6/05/13. 2010 FBC-B | | | 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION | | | SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS | | | OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR | | | OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE | | | LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS | | | NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, | | | POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT | | | OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, | | | COMPRESSIBILITY, | | | LIQUEFACTION AND EXPANSIVENESS. | | | | | | 3) THE PLANS SHOW STAIRS TO THE 2ND LEVEL BUT NO | | | ELEVATOR. PLEASE SHOW COMPLIANCE WITH VERTICAL | | | ACCESSIBILITY. 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS | | | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR | | | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY | | | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE | | | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE OR FACILITY. | | | 553.509?VERTICAL ACCESSIBILITY.? | | | (1)?THIS PART AND THE AMERICANS WITH DISABILITIES ACT | | | STANDARDS FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE | | | OWNER OF ANY BUILDING, STRUCTURE, OR FACILITY GOVERNED | | | BY THIS PART FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE, OR FACILITY, EXCEPT FOR: | | | (A)?ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL | | | ROOMS, PIPING OR EQUIPMENT CATWALKS, AND AUTOMOBILE | | | LUBRICATION AND MAINTENANCE PITS AND PLATFORMS. | | | (B)?UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED | | | SPACES, AND STORAGE SPACES THAT ARE NOT DESIGNED FOR | | | HUMAN OCCUPANCY, FOR PUBLIC ACCOMMODATIONS, OR FOR WORK | | | AREAS. | | | (C)?OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO | | | THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, | | | INCLUDING, BUT NOT LIMITED TO, EQUIPMENT CONTROL ROOMS | | | AND PROJECTION BOOTHS. | | | (D)?THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER | | | LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR | | | TIERED SEATING IF SS. 221 AND 802 OF THE STANDARDS ARE | | | MET. | | | (E)?ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS | | | OF CHAPTER 10 OF THE STANDARDS ARE MET. | | | (F)?ALL EMPLOYEE AREAS AS EXEMPTED IN S. 203.9 OF THE | | | STANDARDS. | | | (G)?FACILITIES, SITES, AND SPACES EXEMPTED BY S. 203 OF | | | THE STANDARDS. | | | (2)?HOWEVER, BUILDINGS, STRUCTURES, AND FACILITIES | | | MUST, AS A MINIMUM, COMPLY WITH THE AMERICANS WITH | | | DISABILITIES ACT STANDARDS FOR ACCESSIBLE DESIGN. | | | | | | 4A) SHEET GA8.00 NOTE # 27 FIXED CANVAS CANOPY, THERE | | | IS NO WIND DESIGN CRITERIA FOR THIS PRODUCT NOR IS | | | THERE . 2010 FBC-B 3102.7 ENGINEERING DESIGN. THE | | | STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO SUSTAIN | | | DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; AND LIVE | | | LOADS INCLUDING WIND LOADS AND FLOOD IN ACCORDANCE WITH | | | CHAPTER 16. | | | | | | 4B) THE FIXED CANVAS CANOPY IS ONTOP OF A BUILDING TYPE | | | I-B PLEASE INDICATE HOW COMPLIANCE WITH THE FOLLOWING: | | | 2010 FBC-B 3102.6 MIXED CONSTRUCTION. | | | MEMBRANE STRUCTURES SHALL BE PERMITTED TO BE UTILIZED | | | AS SPECIFIED IN THIS SECTION AS A PORTION OF BUILDINGS | | | OF OTHER TYPES OF CONSTRUCTION. HEIGHT AND AREA LIMITS | | | SHALL BE AS SPECIFIED FOR THE TYPE OF CONSTRUCTION AND | | | OCCUPANCY OF THE BUILDING. | | | | | | 3102.6.1 NONCOMBUSTIBLE MEMBRANE. | | | A NONCOMBUSTIBLE MEMBRANE SHALL BE PERMITTED FOR USE AS | | | THE ROOF OR AS A SKYLIGHT OF ANY BUILDING OR ATRIUM OF | | | A BUILDING OF ANY TYPE OF CONSTRUCTION PROVIDED IT IS | | | AT LEAST 20 FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR | | | GALLERY. | | | | | | 3102.6.1.1 MEMBRANE. | | | A MEMBRANE MEETING THE FIRE PROPAGATION PERFORMANCE | | | CRITERIA OF NFPA 701 SHALL BE PERMITTED TO BE USED AS | | | THE ROOF OR AS A SKYLIGHT ON BUILDINGS OF TYPES IIB, | | | III, IV AND V CONSTRUCTION, PROVIDED IT IS AT LEAST 20 | | | FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR GALLERY. | | | | | | 4C) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, GUARDRAILS | | | TO REJECT A 4 INCH SPHERE. PLEASE PROVIDE AT WHAT | | | CENTERS THE CABLE WILL NEED TO BE, CENTER TO CENTER ON | | | POST AND AT WHAT TENSION IT WILL TAKE TO KEEP THE | | | SPHERE FROM GOING THROUGH THE SPACING OF THE CABLES. | | | 2010 FBC-B 1013.3. | | | | | | 4D)(1) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, | | | GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED | | | TO THE GUARDRAIL SYSTEM, PLEASE PROVIDE INFORMATION ON | | | FABRIC, COMPLIANCE WITH FIRE PROPAGATION PERFORMANCE | | | CRITERIA OF NFPA 701. | | | | | | 4D)(2) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, | | | GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED | | | TO THE GUARDRAIL SYSTEM, | | | SHOW COMPLIANCE WITH : 3102.7 ENGINEERING DESIGN. | | | THE STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO | | | SUSTAIN DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; | | | AND LIVE LOADS INCLUDING WIND LOADS IN ACCORDANCE WITH | | | CHAPTER 16. | | | | | | 4E) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1607.7.3 | | | VEHICLE BARRIER SYSTEMS FOR THE 2ND FLOOR AND RAMP. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION | | | | | | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-08-21 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-08-21 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-08-20 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2014-08-21 07:15:11 | DATE: 8/21/2014 | | | PROJECT: 900 FLORIDA AVENUE PARKING GARAGE | | | PERMIT: 14061187 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) SHEET T2.01,T9.11 | | | A. THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE | | | RACEWAY SHALL BE LISTED ACCORDINGLY. | | | B. SUITABILITY FOR INSTALLATION AND USE SHALL BE IN | | | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC | | | 110.3(A)(1 THRU 8) | | | | | | 2) GENERAL NOTE: | | | A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR GENERATOR, FIRE ALARM, SECURITY, CCTV, | | | DATA/COM, NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND | | | SIGNAGE. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-08-16 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-08-16 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-08-16 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2014-08-16 16:28:00 | DATE: 8/16/2014 | | | PROJECT: 900 FLORIDA AVENUE PARKING GARAGE | | | PERMIT: 14061187 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | SHEET GE.0 | | | 1) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | 2) SHEET GE.1 | | | PROVIDE PROTECTIVE BOLLARDS FOR ELECTRICAL SWITCH GEAR | | | AND FACP BUT MAINTAIN CLEARANCES PER NEC 110.26 AND | | | 110.27 | | | ALL LIGHTING TO BE IDENTIFIED ?SUITABLE FOR DAMP | | | LOCATION?. NEC 110.3, AND 410.10 | | | | | | 3) SHEET T2.01,T9.11 | | | A. THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE | | | RACEWAY SHALL BE LISTED ACCORDINGLY. | | | B. SUITABILITY FOR INSTALLATION AND USE SHALL BE IN | | | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC | | | 110.3(A)(1 THRU 8) | | | | | | 4) GENERAL NOTE: | | | A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR GENERATOR, FIRE ALARM, SECURITY, CCTV, | | | DATA/COM, NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND | | | SIGNAGE. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2014-08-22 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2014-08-22 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2014-08-22 16:22:14 | NO OBJECTIONS |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2014-08-18 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2014-08-18 |
Time |
|
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
2014-08-18 |
Time |
|
Sent To |
I |
|
| Notes |
| 2014-08-18 08:20:04 | ENGINEERING COMMENTS: (PLEASE RESPOND IN WRITING, CC | | | [email protected]) | | | | | | 1. SIDEWALK ACCESS AROUND THE PARKING STRUCTURE MUST | | | COMPLY WITH ADA. ALTHOUGH SIDEWALKS MAY ME PRIVATE OR | | | LIE INSIDE THE PROPERTY IN SIDEWALK EASEMENTS | | | THEY MUST COMPLY WITH MINIMUM ADA. | | | | | | 2. THERE IS A CONCERN AS TO THE LENGTH OF THE PROPOSED | | | SIDEWALKS AND ESTABLISHING PASSING ZONES FOR ADA. | | | PLEASE RESPOND IF YOUR SITE MEETS U.S. ACCESS BOARD | | | GUIDELINES. | | | | | | 3. TRUNCATED DOMES MUST ALSO BE PLACED AT ALL RAMPS AND | | | CROSSWALKS AS PER FDOT STANDARD. MINIMUM 5' LENGTH X 2' | | | WIDE AREAS. | | | | | | 4. PLEASE ADDRESS ALL PLANNING AND ZONING COMMENTS. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-08-29 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-08-28 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-08-28 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2014-08-28 17:42:06 | 900 FLORIDA AVENUE | | | PERMIT #14061187 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ***OWNER IS PROCEEDING CONSTRUCTION AT RISK - THE | | | FOLLOWING FIRE CODE DEFICIENCIES WILL NEED TO BE | | | ADDRESSED PRIOR TO ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY (CO)*** | | | | | | | | | REPEAT COMMENT - SHEET GA2.00 SECTION HEADING "FIRE | | | PROTECTION" INDICATES A COMPLETE AUTOMATIC SPRINKLER | | | SYSTEM IS PROVIDED FOR THE ROOF LEVEL CANOPY | | | PROTECTION; HOWEVER, SHEET GFP-2 DOES NOT INDICATE ANY | | | AUTOMATIC SPRINKLER SYSTEM PROTECTION. | | | | | | SAFRSHADE CANOPY: SUBMIT PRODUCT INFORMATION AND | | | INDICATE COMPLIANCE WITH NFPA 701. | | | | | | SAFRSHADE CANOPY: PER NFPA 101 THE LIFE SAFETY CODE, | | | SECTION 11.9.1.2 "USE OF MEMBRANE ROOFS. MEMBRANE ROOFS | | | SHALL BE USED IN ACCORDANCE WITH THE FOLLOWING: | | | (1) MEMBRANE MATERIALS SHALL NOT BE USED WHERE FIRE | | | RESISTANCE RATINGS ARE REQUIRED FOR WALLS OR ROOFS. | | | (2) WHERE EVERY PART OF THE ROOF, INCLUDING THE ROOF | | | MEMBRANE, IS NOT LESS THAN 20 FEET ABOVE ANY FLOOR, | | | BALCONY, OR GALLERY, A NONCOMBUSTIBLE OR | | | LIMITED-COMBUSTIBLE MEMBRANE SHALL BE PERMITTED TO BE | | | USED AS THE ROOF IN ANY CONSTRUCTION TYPE. | | | (3) WITH APPROVAL OF THE AUTHORITY HAVING JURISDICTION, | | | MEMBRANE MATERIALS SHALL BE PERMITTED TO BE USED WHERE | | | EVERY PART OF THE ROOF MEMBRANE IS SUFFICIENTLY ABOVE | | | EVERY SIGNIFICANT FIRE POTENTIAL, SUCH THAT THE IMPOSED | | | TEMPERATURE CANNOT EXCEED THE CAPABILITY OF THE | | | MEMBRANE, INCLUDING SEAMS, TO MAINTAIN ITS STRUCTURAL | | | INTEGRITY. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-07-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-07-08 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-07-08 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2014-07-08 16:58:40 | 900 FLORIDA AVENUE | | | PERMIT #14061187 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET GA2.00 SECTION HEADING "FIRE PROTECTION" | | | INDICATES A COMPLETE AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED FOR THE ROOF LEVEL CANOPY PROTECTION; HOWEVER, | | | SHEET GFP-2 DOES NOT INDICATE ANY AUTOMATIC SPRINKLER | | | SYSTEM PROTECTION. ADDITIONALLY, SHEET GFA-2 INDICATES | | | THE INSTALLATION OF TAMPER AND FLOW SWITCHES (EQUIPMENT | | | ASSOCIATED WITH AUTOMATIC SPRINKLER SYSTEMS). | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-08-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2014-08-29 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-08-20 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-08-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2014-08-18 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-06-30 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-20 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-20 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2014-08-20 16:52:38 | WILLIE SCOOPE SIGNATURE ON PLANS NO FEES DUE GA3.00 , | | | DATED 8/15/2014. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-07-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-08 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-08 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2014-07-08 14:45:28 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2014-07-22 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-07-22 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-07-22 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2014-07-22 14:10:11 | NO MECHANICAL AT THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-22 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-20 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2014-08-22 08:16:25 | PLUMBING PLAN REVIEW | | | PERMIT: 14061187 | | | ADD: 900 FLORIDA AVE | | | CONT:COASTAL CONSTRUCTION | | | TEL: (561)630-3770 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: FRI. AUG. 22/2014 | | | ACTION: PROVISO | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | NOTE:!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES | | | STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF | | | FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | | REJECTED OR MORE TIMES FOR REPEATED FAILURE TO CORRECT | | | A CODE VIOLATION. | | | | | | 1) SHEET 0200 GP-1 THIS SHEET NOR ANY SUBMITTED | | | PLUMBING SHEET SHOWS HOW THE STORM DRAINAGE PLANS WAS | | | DERIVED. PLEASE PROVIDE CALCULATIONS FOR THE NOT 2ND | | | STORY SLAB BUT THE ROOF AREA OF THE CANOPY, THE AREA OF | | | THE CANOPY IS A LARGER SQ. FT .SURFACE AREA. PLEASE | | | DESIGN TO THE 2010 FBC-PLUMBING 106.1 GENERAL. | | | THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS, | | | BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY | | | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE | | | BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN | | | FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED | | | FROM APPROVED LOCAL WEATHER DATA. PROVIDE THE SQUARE | | | FOOT AREA OF THE ROOFING MEMBRANE AND HOW THE DRAINAGE | | | IS SIZED FOR THIS CANOPY AND HOW THE RAIN WATER WILL | | | FLOW TO THE DECK DRAINS SINCE THE PLANS DO NOT INDICATE | | | ROOF DRAINS IN THE ROOF TOP CANOPY, NOR REIN LITTERS OR | | | CONDUCTORS TO THE ROOF DRAINS IN THE 2ND FLOOR DECK. | | | | | | 2) PLEASE SHOW COMPLIANCE WITH FBC-P TABLE 403.1 FOR S2 | | | OCCUPANCY AND IF THE RESTROOMS WITHIN THE HOTEL ARE | | | LOCATED OVER 500 FT AWAY, SEE FBC-P 403.3.2. | | | | | | 3) DO NOT INSTALL ANY STORM WATER BUILDING DRAIN PIPING | | | (UNDER THE FOOTPRINT OF THE BUILDING) IDENTIFYING THE | | | TYPE OF MATERIALS TO BE USED IN THIS INSTALLATION UNTIL | | | A REVISION HAS BEEN SUBMITTED AND APPROVED THROUGH THE | | | BUILDING DEPARTMENT. | | | | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-09 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-08 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2014-07-09 15:34:34 | PLUMBING PLAN REVIEW | | | PERMIT: 14061187 | | | ADD: 900 FLORIDA AVE | | | CONT: | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: WED. JULY 09/2014 | | | ACTION: DENIED | | | | | | 1) SHEET 0200 GP-1 THIS SHEET NOR ANY SUBMITTED | | | PLUMBING SHEET SHOWS HOW THE STORM DRAINAGE PLANS WAS | | | DERIVED. PLEASE PROVIDE CALCULATIONS FOR THE NOT 2ND | | | STORY SLAB BUT THE ROOF AREA OF THE CANOPY, PLEASE | | | DESIGN TO THE 2010 FBC-PLUMBING 106.1 GENERAL. | | | THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS, | | | BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY | | | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE | | | BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN | | | FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED | | | FROM APPROVED LOCAL WEATHER DATA. PROVIDE THE SQUARE | | | FOOT AREA OF THE ROOFING MEMBRANE AND HOW THE DRAINAGE | | | IS SIZED FOR THIS CANOPY AND LOCATION OF ROOF DRAINS IN | | | THE DECK. | | | | | | 2) PLEASE SHOW COMPLIANCE WITH FBC-P TABLE 403.1 FOR S2 | | | OCCUPANCY AND IF THE RESTROOMS WITHIN THE HOTEL ARE | | | LOCATED OVER 500 FT AWAY, SEE FBC-P 403.3.2. | | | | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-08-22 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-08-22 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-08-20 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2014-08-22 09:36:01 | 1ST REVIEW; FBC 2010: | | | | | | PEDDS SUBMITTAL IS INCOMPLETE: AT LEAST THE FOLLOWING | | | SHEETS ARE NOT LISTED ON ANY SIGNATURE REPORT:: | | | 0000, 0001, 50, 52, 54, 56, 60, 62, 70,72, 74,80. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-08-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-08-25 |
Time |
14:42 |
Rev Time |
4.00 |
| Received By |
eschneid |
Date |
2014-08-25 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2014-08-25 15:15:06 | PASSED W/PROVISOS | | | | | | 1) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION | | | NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE | | | FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION; | | | HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY | | | SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT | | | HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE | | | ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF | | | OCCUPANCY. | | | | | | A.PROVISO: RECORD EASEMENTS IN FAVOR OF THE CITY FOR | | | ANY PUBLIC SIDEWALKS OR UTILITIES ON THE HOTEL OR | | | PARKING STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS | | | WILL BE BASED ON THE AS BUILT SURVEY OF THE SITE.**** | | | | | | B. PROVISO: SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY | | | FOR THE RECONFIGURATION OF THE MEDIANS AND INSTALLATION | | | OF LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE | | | RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE | | | MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE | | | SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN | | | CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE | | | LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL | | | DEVICES (MUTCD). ****THE ENGINEERING SERVICES | | | DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO | | | ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL | | | RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE | | | CONSTRUCTION IS FURTHER ALONG.**** | | | | | | C. PROVISO: SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY | | | FOR THE INSTALLATION OF LANDSCAPE MATERIAL WITHIN THE | | | ALABAMA AVENUE RIGHT-OF-WAY. ****THE ENGINEERING | | | SERVICES DEPARTMENT HAS DETERMINED THAT IT IS TOO | | | PREMATURE TO ISSUE A RIGHT-OF-WAY PERMIT SINCE THE | | | ACTUAL RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE | | | CONSTRUCTION IS FURTHER ALONG.**** | | | | | | 2) PROVISO: THE IMPROVEMENTS AND LANDSCAPING SHOWN | | | OUTSIDE OF THE PARCEL BOUNDARIES REQUIRE A RIGHT-OF-WAY | | | PERMIT PRIOR TO THE FINAL INSPECTION (104) APPROVAL FOR | | | THE GARAGE. | | | | | | 3) PROVISO: STAFF ONLY COUNTS 83 NOT 85 COMPACT PARKING | | | SPACES AS LISTED ON THE PARKING TABLE ON SHEET GA0.01. | | | PRIOR TO THE FINAL ZONING INSPECTION OF THE GARAGE, | | | THIS SHEET SHALL ACCURATELY REFLECT THE NUMBER OF | | | REGULAR, ADA AND COMPACT SPACES PROVIDED IN THE GARAGE. | | | | | | 4) PROVISO: INSUFFICIENT INFORMATION WAS PROVIDED ON | | | THE PROPOSED CABLE GUARDRAILS WITH FABRIC SCREEN. THESE | | | ELEMENTS ARE NOT APPROVED AS PART OF THE ZONING | | | APPROVAL. AT THE CURRENT TIME ZONING IS ONLY APPROVING | | | THE USE OF A SOLID WALL IN ACCORDANCE WITH THE CITY | | | COMMISSION APPROVAL. NO PHOTOS WERE PROVIDED AS | | | REQUIRED ON THE PREVIOUS PERMIT REVIEW AS TO THE | | | AESTHETICS OF THE PROPOSED SCREENING, NOR WAS | | | INFORMATION PROVIDED AS TO THE ABILITY TO BLOCK | | | HEADLIGHT GLARE AS REQUIRED BY THE MINOR AMENDMENT | | | COMMENTS. THE FINAL CONDITION OF THE SECOND FLOOR WALL | | | SHALL BE RESOLVED ON REVISED PLANS PRIOR TO THE FIRST | | | INSPECTION FOR THE GARAGE. | | | | | | 5) PROVISO: SHEET GA12.01 SHALL BE REVISED PRIOR TO THE | | | FINAL PARKING INSPECTION TO INCLUDE WHEEL STOPS AT THE | | | HEAD OF ALL SPACES WHICH HAVE A WALL, COLUMN OR OTHER | | | STRUCTURAL ELEMENT IN FRONT OF IT (EXCLUDING THE PIPES | | | PROTECTED BY BOLLARDS) AND DETAILS FOR THE COMPACT | | | PARKING SPACES. | | | | | | 6) PROVISO: ZONING HAS NOT APPROVED THE SPECIFIC LIGHT | | | FIXTURES AND THEIR LOCATION UNDER THE CANOPIES. THE | | | LIGHT FIXTURES REQUIRE APPROVAL AS A REVISION TO THIS | | | PERMIT PRIOR TO INSTALLATION. | | | | | | 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. ROOF CANOPIES | | | B. SITE LIGHTING | | | C. LANDSCAPE | | | D. BICYCLE RACKS | | | E. IRRIGATION | | | | | | 8) THE WORK RELATING TO THE PRIVATE DRIVE REQUIRES A | | | SEPARATE DRIVEWAY PERMIT, WITH PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-07-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-07-22 |
Time |
09:24 |
Rev Time |
4.00 |
| Received By |
eschneid |
Date |
2014-07-22 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2014-07-22 10:56:30 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) THE FOLLOWING CONDITION FROM RESOLUTION NO. 329-13 | | | SHALL BE SATISFIED PRIOR TO THE ISSUANCE OF THE FIRST | | | BUILDING PERMIT FOR VERTICAL CONSTRUCTION - THE | | | APPLICANT SHALL: | | | | | | A. SUBMIT A MINOR AMENDMENT SHOWING THE LOCATIONS OF | | | THE STREET LIGHTS AND THE PEDESTRIAN SCALE LIGHTING. | | | THE MINOR AMENDMENT SHALL SHOW THAT THE STREET LIGHTS | | | MEET THE DOWNTOWN MASTER PLAN SPECIFICATIONS AND SHALL | | | SPECIFY AND PROVIDE DETAILS OF THE LIGHTING FIXTURES | | | USED FOR THE PEDESTRIAN SCALE LIGHTING. NO LIGHTING | | | SHALL CONFLICT WITH PROPOSED LANDSCAPE. | | | | | | B. THE LANDSCAPE PLANS SHALL BE SUBMITTED AS A | | | LANDSCAPE PERMIT AND INCLUDE THE NOTATION AND DETAILS | | | THAT ROOT BARRIERS AND STRUCTURAL SOILS SHALL BE USED | | | FOR ALL THE OAK TREE PLANTINGS IN SIDEWALK CUTOUTS OR | | | WITHIN CLOSE PROXIMITY TO SIDEWALKS TO ENSURE PROPER | | | ROOT GROWTH WHILE LIMITING THE POTENTIAL FOR ROOT | | | DAMAGE. | | | | | | 2) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION | | | NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE | | | FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION; | | | HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY | | | SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT | | | HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE | | | ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF | | | OCCUPANCY. | | | | | | A. RECORD EASEMENTS IN FAVOR OF THE CITY FOR ANY PUBLIC | | | SIDEWALKS OR UTILITIES ON THE HOTEL OR PARKING | | | STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS WILL BE | | | BASED ON THE AS BUILT SURVEY OF THE SITE.**** | | | | | | B. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE | | | RECONFIGURATION OF THE MEDIANS AND INSTALLATION OF | | | LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE | | | RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE | | | MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE | | | SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN | | | CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE | | | LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL | | | DEVICES (MUTCD). ****THE ENGINEERING SERVICES | | | DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO | | | ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL | | | RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE | | | CONSTRUCTION IS FURTHER ALONG.**** | | | | | | C. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE | | | INSTALLATION OF LANDSCAPE MATERIAL WITHIN THE ALABAMA | | | AVENUE RIGHT-OF-WAY. ****THE ENGINEERING SERVICES | | | DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO | | | ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL | | | RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE | | | CONSTRUCTION IS FURTHER ALONG.**** | | | | | | 3) THE GARAGE ELEVATION AND FLOOR PLAN HAS CHANGED, | | | WHICH REQUIRE THE APPROVAL OF A MINOR PLANNED | | | DEVELOPMENT AMENDMENT. YOU MAY INCLUDE THIS WITH THE | | | MINOR AMENDMENT TO THE HOTEL. | | | | | | 4) THE IMPROVEMENTS AND LANDSCAPING SHOWN OUTSIDE OF | | | THE PARCEL BOUNDARIES REQUIRE A RIGHT-OF-WAY PERMIT. | | | | | | 5) REMOVE THE NOTE REFERENCING THE BUS AND TROLLEY STOP | | | FROM SHEET GA1.01. | | | | | | 6) VERIFY THAT THE GATES ARE CONFIGURED TO OPERATE FROM | | | BOTH DIRECTIONS IN ACCORDANCE WITH THE CITY COMMISSION | | | APPROVAL. THE GATE PLACEMENT IN RELATIONSHIP TO THE RF | | | ID READERS DO NOT LOOK LIKE THEY ALLOW REVERSE TRAFFIC | | | FLOW. | | | | | | 7) INCLUDE THE NUMBER OF COMPACT SPACES ON THE PARKING | | | TABLE ON SHEET GA0.01. | | | | | | 8) SHEET GA3.00 SHOWS A CIRCULAR OBJECT IN SPACES 20, | | | 188 & 193, 197. WHAT IS THIS (SIMILAR FEATURES ARE | | | LABELED AS F.D., FLOOR DRAINS BUT THESE APPEAR | | | DIFFERENT ON PLUMBING PLAN)? IF IT IS AN ABOVE GROUND | | | OBJECT, IT BLOCKS THE ABILITY OF THE CAR TO USE THE | | | FULL SPACE, RESULTING IN A SUBSTANDARD DEPTH PARKING | | | SPACE. | | | | | | 9) THE PLAN NOTES STATE THAT PLUMBING WILL BE PROTECTED | | | BY BOLLARDS. STAFF WAS UNABLE TO DISCERN WHERE THIS | | | OCCUSR. BOLLARDS SHALL BE SHOWN. ANY PARKING SPACES | | | RENDERED SUBSTANDARD DUE TO THE PLACEMENT OF BOLLARDS | | | SHALL BE DELETED FROM THE PLANS. | | | | | | 10) A SIGN SHALL BE INSTALLED AT THE RAMP UP TO THE | | | SECOND LEVEL TO NOTIFY HC DRIVERS THAT NO ADA PARKING | | | IS AVAILABLE PAST THAT POINT. | | | | | | 11) THE NORTH AND EAST ELEVATIONS SHOW A LOW WALL IN | | | FRONT OF THE EASTERNMOST ADA ENTRY TO THE GARAGE THAT | | | IS NOT SHOWN ON THE SITE PLAN, THE CIVIL PLAN, THE | | | LANDSCAPE PLAN OR THE HARDSCAPE PLAN. WHY IS THE WALL | | | HERE? IT APPEARS TO BE IN THE LANDSCAPE BUFFER AND | | | SERVING NO PURPOSE. AS SHOWN, THIS PRESENTS AN AREA | | | THAT DOES NOT HAVE NATURAL SURVEILLANCE. | | | | | | 12) PLEASE EXPLAIN AND PROVIDE A PHOTOGRAPH OF THE | | | CABLE GUARDRAILS WITH FABRIC SCREEN (NORTH AND SOUTH | | | ELEVATIONS). | | | | | | 13) PROVIDE THE DIMENSION OF THE EXPANDED SIDEWALK AREA | | | ON THE EAST SIDE OF THE GARAGE (SEE LOCATION ON SHEET | | | C4). | | | | | | 14) PROVIDE PHOTOMETRIC PLANS WHICH SHOW THE LIGHT | | | LEVELS ON FLORIDA AVENUE, M STREET, ALABAMA AVENUE AND | | | THE NORTHERN ACCESS DRIVE CAUSED BY THE GARAGE LIGHTS. | | | PER CODE THEY SHOULD NOT PROVIDE GLARE INTO THE | | | RIGHT-OF-WAY OR INTO THE RESIDENCES NORTH AND SOUTH OF | | | THE GARAGE. | | | | | | 15) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. ROOF CANOPIES | | | B. SITE LIGHTING | | | C. LANDSCAPE | | | D. BICYCLE RACKS | | | E. IRRIGATION | | | | | | 16) THE WORK RELATING TO THE PRIVATE DRIVE REQUIRES A | | | SEPARATE DRIVEWAY PERMIT, WITH PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2014-07-01 16:32:55 | 7-1-14 |
|
|
|