| 2014-06-26 13:21:45 | DATE: 6/26/2014 |
| | PROJECT: FLAGLER RESIDENCE ELECTRICAL AS BUILTS-SHEET |
| | E-03 |
| | PERMIT#: 13070545 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | NOTE: |
| | PLAN REVEIW APPROVED FOR SHEETS E-01 AND E-02 ONLY. |
| | SHEET E-03 TO BE SUBMITTED AT A LATER DATE. TAKE THE |
| | FOLLOWING INTP ACCOUNT WHEN RESUBMITTING SHEET E-03 |
| | |
| | 1) RISER DIAGRAM NEEDS TO BE REVISED TO INDICATE THE |
| | FOLLOWING: |
| | A) CORRECT CONDUIT LAYOUT FOR FUTURE GENERATOR. I |
| | BELIEVE THE INTENT WAS TO HAVE TWO SETS OF CONDUITS |
| | FROM THE FUTURE GENERATOR. ONE SET TO EACH OF THE TWO |
| | ATS'S |
| | B) CORRECT GROUNDING DETAIL. CURRENTLY SHOWS UFER |
| | GROUND ONLY. |
| | |
| | 2) THE FEEDER SCHEDULE IS UNCLEAR AND CONFLICTS WITH |
| | THE RISER DIAGRAM. I SUGGEST USING EITHER A FEEDER |
| | SCHEDULE OR CALL OUT EACH CONDUIT AND WIRE DETAIL ON |
| | THE RISER DIAGRAM ITSELF. NOT BOTH. IF BOTH ARE USED |
| | THEY NEED TO MATCH AND BE CLEAR AS TO WHICH CONDUIT |
| | LOCATION IS REPRESENTED BY THE "TYPE" |
| | |
| | 3) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE |
| | RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "A" |
| | FEEDS PANEL "F" BUT IS NOT INDICATED IN THE PANEL "A" |
| | SCHEDULE. |
| | |
| | 4) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE |
| | RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "B" |
| | FEEDS PANEL "E" BUT IS NOT INDICATED IN THE PANEL "B" |
| | SCHEDULE. |
| | |
| | 5) THE RISER DIAGRAM INDICATES FOUR PANELS LOCATED IN |
| | THE GARAGE. THE FLOOR PLAN INDICATES ONLY THREE. |
| | CORRECT ONE OR THE OTHER. |
| | |
| | 6) LOAD CALCULATIONS SHALL BE INCLUDED FOR EACH PANEL |
| | TO INDICATE THE PANEL PROPOSED IS ADEQUATE TO SUPPORT |
| | THE LOAD. |
| | |
| | 7) AT LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHT FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 404.1. |
| | PROVIDE FIXTURE SCHEDULE. |
| | |
| | 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. |
| | FBC-R402.4.5. PROVIDE FIXTURE SCHEDULE. |
| | |
| | 9) THE GROUNDING ELECTRODE SYSTEM SHALL BE INDICATED ON |
| | THE RISER AS IT WILL BE INSTALLED AND AS DESCRIBED IN |
| | SECTION III OF THE NEC 250 |
| | |
| | 10) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE |
| | BUILDING NEAREST THE POINT OF SERVICE ENTRANCE IN |
| | ACCORDANCE WITH NEC 230.70. PLEASE INDICATE THE |
| | LOCATION OF THE ELECTRICAL SERVICE ENTRANCE AND |
| | DISCONNECTING MEANS. |
| | |
| | 11) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE |
| | MAIN SERVICE GROUND. NEC 250.94 |
| | |
| | 12) THE INSTALLATION OF ELECTRICAL WIRING FOR, AND |
| | EQUIPMENT IN AND ADJACENT TO, NATURAL OR ARTIFICIALLY |
| | MADE BODIES OF WATER NOT COVERED BY OTHER ARTICLES IN |
| | THIS CODE SHALL COMPLY WITH THE PROVISIONS OF THE NEC |
| | 682. |
| | |
| | NOTE: A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE |
| | SUBMITTED INCLUDING ALL DETAILED PLANS, SHOP DRAWINGS, |
| | EQUIPMENT SUBMITTALS, PRODUCT APPROVALS, ETC? IS |
| | REQUIRED FOR ALL OF THE FOLLOWING: SWIMMING POOL, DOCK, |
| | GENERATOR, AUDIO, VIDEO, NETWORK, SECURITY, CCTV. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |
| | |