Plan Review Details - Permit 14061136
Plan Review Stops For Permit 14061136
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-31 Cont ID  
Sent By shill Date 2014-07-31 Time 13:45 Rev Time 0.00
Received By shill Date 2014-07-31 Time 13:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-16 Cont ID  
Sent By shill Date 2014-07-16 Time 17:00 Rev Time 0.00
Received By shill Date 2014-07-16 Time 17:00 Sent To  
Notes
2014-07-16 17:22:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE OPENING #1. SPAN IS SHOWN AS 108" (9'). SEE
 SHEET 10. CONCRETE SUBSTRATE ON THE TOP, CONNECTION
 TYPE C3, ELCO ULTRACON, 9' SPAN, 62PSF, CANNOT BE USED
 (BOX IS HATCHED).
  
 CONTRACTOR HAS HIGHLIGHTED THE ROW FOR 48PSF, BUT
 DESIGN PRESSURE PROPOSED FOR THIS OPENING IS 49.4, SO
 THE NEXT ROW (62PSF) MUST BE USED.
  
 2. SEE OPENING #1, BOTTOM AND CHART ON SHEET 11. FOR
 CONCRETE BLOCK, ULTRACON, CONNECTION TYPE C3, IS
 HATCHED (CANNOT BE USED) FOR 62 PSF.
  
 3. REVISE INSTALLATION SCHEDULE TO BE MORE SPECIFIC
 REGARDING THE FASTENER. THERE ARE DIFFERENT DIAMETER OF
 ELCO ULTRACON.
  
 CHECK ALL OPENINGS AS THE ONE GIVEN IS ONLY ONE
 EXAMPLE. THE OTHER OPENINGS HAVE THE SAME ISSUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-05 Cont ID  
Sent By shill Date 2014-07-05 Time 14:58 Rev Time 0.00
Received By shill Date 2014-07-05 Time 14:58 Sent To  
Notes
2014-07-05 14:59:39****CORRECTIONS****
 ****REVISED 7/8/14****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 2. INFORMATIONAL ONLY - FS471, CONTRACTOR IS NOT TO USE
 THE WORD "ENGINEERING" IN HIS COMPANY NAME UNLESS AN
 ENGINEER QUALIFIES THE COMPANY. PER CONVERSATION WITH
 CONTRACTOR'S REPRESENTATIVE, CONTRACTOR WILL RESOLVE
 THIS ISSUE BUT THIS PERMIT WILL BE ISSUED UNDER THE
 CURRENT NAME AFTER ITEM #1 IS ADDRESSED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-31 Cont ID  
Sent By shill Date 2014-07-31 Time 13:45 Rev Time 0.00
Received By shill Date 2014-07-18 Time 11:26 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-16 Cont ID  
Sent By shill Date 2014-07-16 Time 17:22 Rev Time 0.00
Received By shill Date 2014-07-11 Time 11:22 Sent To  
Notes
2014-07-11 11:23:06RE-SUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-05 Cont ID  
Sent By shill Date 2014-07-05 Time 14:59 Rev Time 0.00
Received By shill Date 2014-06-25 Time 09:07 Sent To  
Notes
2014-06-25 09:07:22MISC 1
  