Plan Review Details - Permit 14061120
Plan Review Stops For Permit 14061120
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 07:21 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-20 Cont ID  
Sent By rmcdouga Date 2014-11-20 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2014-11-17 Time 06:46 Sent To E
Notes
2014-11-20 16:32:12PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) PLAN SHEETS A.03 AND A.05 ARE MISSING FROM ONE SET
 OF THE PLANS. SUBMIT ADDITIONAL SHEETS A.03 AND A.05.
 FBC 107.1
  
 2) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THE
 GAF MODIFIED ROOF SYSTEM, NOA NO. 13-0424.14 ARE NOT
 ACCEPTABLE. THERE ARE THREE DIFFERENT FASTENING OPTIONS
 WITH A MAXIMUM DESIGN PRESSURE OF -60 PSF. SPECIFY THE
 FASTENER AS WELL AS THE LAP AND FIELD SPACING FOR THE
 ANCHOR SHEET. THE NOTE ON PAGE 8 STATE THAT THE
 INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT
 ASPHALT. SHOW ALL OF THE RAS 117 CALCULATIONS THAT WERE
 USED TO DETERMINE THE ENHANCED FASTENER SPACING. IT IS
 UNCLEAR WHY THE NUMBER OF INSULATION BOARD FASTENERS
 WAS PROVIDED. FBC 107.2.1.4
  
 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-15 Cont ID  
Sent By rmcdouga Date 2014-07-15 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 08:59 Sent To E
Notes
2014-07-14 18:21:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND DESIGN DATA IN THE WIND PRESSURE SCHEDULE
 ON SHEET A.07 IS INCORRECTLY SPECIFIED AS 140 MPH AND
 THE PRESSURES ARE INCORRECT. THE WINDSPEED FOR THIS
 PROJECT IS 170 MPH AND THE EXPOSURE CATEGORY IS C. THE
 WIND SPEED IS SPECIFIED AS 170 MPH AND EXPOSURE D ON
 SEVERAL OF THE PLAN SHEETS. PLEASE CORRECT AND SPECIFY
 THE WIND PRESSURES FOR THE CORRESPONDING WINDSPEED,
 ROOF HEIGHT AND EXPOSURE CATEGORY. FBCR 301.2.1
  
 2) THE APPLICABLE EDITION OF THE NATIONAL ELECTRICAL
 CODE ( NEC) IS THE 2008. THE APPLICABLE EDITION OF THE
 FLORIDA FIRE PREVENTION CODE IS THE 2010 EDITION. THIS
 IS LISTED ON SEVERAL OF THE PLAN SHEETS. IT IS CORRECT
 ON SOME AND NOT ON OTHERS. PLEASE CORRECT.
  
 3) SUBMIT TWO SETS OF ENERGY COMPLIANCE DOCUMENTS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION 103.
  
 4) THERE ARE CONFLICTING NOTES REGARDING THE ATTIC
 INSULATION. WALL SECTION C ON A.07 HAS A NOTE
 SPECIFYING R-30 INSULATION WITH AN ARROW POINTING TO
 THE BOTTOM CORD OF THE TRUSS, HOWEVER, THE INSULATION
 IS SHOWN ON THE TOP CORD. A NOTE ON SHEET A.04
 SPECIFIES SPRAY FOAM INSULATION ON THE TOP CORD. THERE
 ARE ROOF VENT CALCULATIONS AND OFF RIDGE ROOF VENTS
 SHOWN ON SHEET A.06. THE SPRAY FOAM ON THE UNDER SIDE
 OF THE ROOF DECK IS TYPICALLY USED WITH UN-VENTED
 ATTICS, AS THE ATTIC IS CONSIDERED CONDITIONED SPACE
 WITH THIS APPLICATION. PLEASE CLARIFY AND COORDINATE
 THE INFORMATION ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316.
  
 6) ON SHEET A.07 THE DETAILS FOR THE EXTERIOR WINDOW
 HEAD, SILL AND JAMB SHOW LATH AND PLASTER (STUCCO) AND
 NOT THE CEMENTITIOUS SIDING THAT IS SPECIFIED ON THE
 OTHER PLAN SHEETS. PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 7) ON SHEET A.08, SOME OF THE ID TAGS ON THE FOUNDATION
 PLAN DO NOT MATCH THE DETAILS OR THE DETAILS ARE
 MISSING. THERE ARE TWO DIFFERENT DETAILS NUMBERED 2 AND
 TWO MORE NUMBERED 6. THERE WERE ALSO TWO PLAN SHEETS
 NUMBERED A.08 IN BOTH OF THE PLAN SETS THAT WERE
 SUBMITTED. PLEASE REVIEW PLANS FOR ACCURACY AND
 CONSISTENCY, THEN MAKE CORRECTIONS. CITY AMENDMENTS
 107.2.1
  
 8) ON SHEET A.08, THE ELEVATION FOR THE TOP OF THE SLAB
 AT THE LOGGIA INDICATES THAT IT IS 4" HIGHER THAN THE
 HOUSE SLAB. THERE IS A NOTE THAT INDICATES THERE IS A
 6" STEP DOWN. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 9) THERE IS A 6" STEP DOWN AND A 6" WHEEL STOP SHOWN IN
 THE GARAGE ON SHEET A.04. THE FOUNDATION PLAN ON A.08,
 DOES NOT SHOW THE 6" INCH WHEEL STOP. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 10) PROVIDE A STRUCTURAL DETAIL VIEW OF THE 4 X 6 WOOD
 POSTS' TOP AND BOTTOM CONNECTIONS. FBCR 301.1
  
 11) SUBMIT THE MANUFACTURER'S INSTALLATION GUIDE AND
 SPAN TABLES FOR THE LAMINATED VENEER LUMBER BEAMS. FBCR
 301.1 & R602.1.1.2
  
 12) THE DESIGN PRESSURES FOR THE CLOPAY OVERHEAD GARAGE
 DOOR, FL 15279 ARE LOWER THAN THE REQUIRED WIND LOAD
 PRESSURES FOR THE END ZONE OF A TWO STORY STRUCTURE
 LOCATED IN EXPOSURE D OR C WITH A 170 MPH VULT WIND
 SPEED.
  
 13) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR CEMENTITIOUS SIDING AND THE STRUCTURAL
 MULLIONS AS REQUIRED BY DCA RULE 9N-3.
  
 14) SPECIFY THE APPROVED SYSTEM AND THE FASTENING
 OPTION THAT WILL BE USED FOR THE GAF RUBEROID MODIFIED
 BITUMEN SYSTEM, NOA NO. 13-0424.14. SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #7 OF THE NOA. CITY AMENDMENTS 107.2.1 &
 FBCR 301.2.1
  
 15) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW ITEMS
 HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 07:22 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 07:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 14:13 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 14:13 Sent To  
Notes
2014-11-21 14:25:1711/21/2014
 PROJECT: VALLY FORGE RESIDENCE
 PERMIT#: 14061120
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INCLUDE THE FEED TO THE
 PANEL IN THE GARAGEANY POWER IN THE SHED BUILDING AND
 TO INDICATE THE NEW PANEL IS NEMA 3R APPROVED FOR USE
 OUTDOORS.
  
 2) PROVIDE ELECTRICAL PANEL SCHEDULE FOR BOTH
 ELECTRICAL PANELS.
  
 3) VERIFY THE EXISTANCE OR THE INSTALLATION OF SMOKE/CO
 DETECTORS IN COMPLIANCE WITH THE FBC -R 314, 315
  
 4) PROVIDE CIRCUITING ON THE FLOOR PLAN THAT COINCIDES
 WITH THE PANEL SCHEDULES TO BE PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-18 Cont ID  
Sent By dhayes Date 2014-07-18 Time 13:23 Rev Time 0.00
Received By dhayes Date 2014-07-18 Time 13:23 Sent To  
Notes
2014-07-18 13:30:07DATE: 7/18/2014
 PROJECT: PINSKY ADDITION
 PERMIT#: 14061120
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 CLARIFICATION REQUIRED. SITE PLAN INDICATE THE EXISTING
 ELECTRICAL METER AT A SHED IN THE BACK YARD. THE
 ELECTRICAL PLAN INDICATES A NEW SERVICE BUT THE
 LOCATION OF THE SERVICE IS NOT IDENTIFIED. FBC WPB
 AMENDMENTS. 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-07-14 Cont ID  
Sent By rmcdouga Date 2014-07-14 Time 14:17 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 14:17 Sent To  
Notes
2014-07-14 14:25:27A SEPARATE GAS PERMIT, APPLICATION AND REVIEW IS
 REQUIRED. NO APPLICATION OR PLANS FOR GAS WERE
 SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 07:26 Rev Time 0.00
Received By skennedy Date 2015-05-20 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 14:25 Rev Time 0.00
Received By dhayes Date 2014-10-23 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-18 Cont ID  
Sent By dhayes Date 2014-07-18 Time 13:30 Rev Time 0.00
Received By dhayes Date 2014-06-24 Time 17:25 Sent To  
Notes
2014-06-24 17:27:11R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 07:21 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 07:21 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-11-19 Cont ID  
Sent By rmcdouga Date 2014-11-19 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2014-11-17 Time 06:47 Sent To  
Notes
2014-11-19 16:20:58BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-14 Cont ID  
Sent By rmcdouga Date 2014-07-14 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 13:37 Sent To  
Notes
2014-07-14 13:38:59IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. 233-5025

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 07:24 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 07:22 Sent To  
Notes
2015-06-04 07:25:58A MECHANICAL APPLICATION IS ATTACHED, BUT THERE IS
 MECHANICAL DESIGN SUBMITTED. THIS APPLICATION SHOULD BE
 WITHDRAWN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-11-17 Cont ID  
Sent By rmcdouga Date 2014-11-17 Time 08:12 Rev Time 0.00
Received By rmcdouga Date 2014-11-17 Time 06:47 Sent To  
Notes
2014-11-17 08:18:37A SEPARATE MECHANICAL PERMIT, APPLICATION AND REVIEW IS
 REQUIRED. NO APPLICATION OR PLANS FOR MECHANICAL WORK
 WERE SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-14 Cont ID  
Sent By rmcdouga Date 2014-07-14 Time 15:15 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 15:15 Sent To  
Notes
2014-07-14 15:37:272010 FBC
  
 DENIED BY MECHANICAL
  
 1) NO MECHANICAL PLANS WERE SUBMITTED. SUBMIT TWO SETS
 OF MECHANICAL PLANS. SPECIFY THE DUCT SIZES AND
 LOCATIONS. SPECIFY THE GRILL LOCATIONS, SIZES AND CFMS
 AT EACH OUTLET. CITY AMENDMENTS 107.3.5.3
  
 2) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 3) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS.
 CITY AMENDMENTS 107.2.1
  
 5) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS
 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-19 Cont ID  
Sent By rmcdouga Date 2014-11-19 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2014-11-19 Time 16:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By rmcdouga Date 2014-07-14 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 11:45 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By rmcdouga Date 2014-07-14 Time 15:15 Rev Time 0.00
Received By rmcdouga Date 2014-07-14 Time 15:15 Sent To  
Notes
2014-07-14 15:15:22ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED.
  
 1) GAF ASPHALT SHINGLES - FL #10124
  
 2) GAF RUBEROID MODIFIED BITUMEN - NOA NO. 13-0424.14
 (REQUIRES RAS 117 CALCULATIONS)

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By dkittred Date 2014-10-27 Time 08:20 Rev Time 0.00
Received By dkittred Date 2014-10-24 Time 16:11 Sent To  
Notes
2014-10-27 08:20:4010/27/14
  
 1. APPLICANT SUBMITTED LANDSCAPE SKETCH DEMONSTRATING
 COMPLIANCE WITH MINIMUM LANDSCAPING REQUIREMENTS. NO
 ADDITION PLANTINGS REQUIRED.
  
 2. SITE PLAN SHOWS 'TREE TO BE REMOVED' WHICH DOES NOT
 EXIST AND NOTATION ADDED TO PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-30 Cont ID  
Sent By dkittred Date 2014-06-30 Time 14:25 Rev Time 0.00
Received By dkittred Date 2014-06-30 Time 10:21 Sent To  
Notes
2014-06-30 14:25:22PLANNING AND ZONING COMMENTS: ***FAILED***
  
 6/30/14
  
 1. NEW AC UNIT CANNOT PROJECT MORE THAN FOUR (4) FEET
 INTO A REQUIRED SETBACK. PROVISO WILL BE ADDED TO THE
 PLANS.
  
 2. THE VALUE OF THE CONSTRUCTION ($50,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($86,809) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR SEC.
 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 3. TREE ALTERATION PERMIT THROUGH THE PLANNING DEPT. IS
 REQUIRED FOR THE REMOVAL OR RELOCATION OF ANY TREES
 REQUIRED FOR THE NEW CONSTRUCTION. HTTP://WPB.ORG/PLANN
 ING/WP-CONTENT/UPLOADS/SITES/37/2013/04/TREEALTERATIONP
 ERMITREVISED03-12-09.PDF
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-06-25 11:52:136/25/14