| Plan Review Stops For Permit 14061120 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-04 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-04 |
Time |
07:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-20 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-17 |
Time |
06:46 |
Sent To |
E |
|
| Notes |
| 2014-11-20 16:32:12 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) PLAN SHEETS A.03 AND A.05 ARE MISSING FROM ONE SET | | | OF THE PLANS. SUBMIT ADDITIONAL SHEETS A.03 AND A.05. | | | FBC 107.1 | | | | | | 2) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THE | | | GAF MODIFIED ROOF SYSTEM, NOA NO. 13-0424.14 ARE NOT | | | ACCEPTABLE. THERE ARE THREE DIFFERENT FASTENING OPTIONS | | | WITH A MAXIMUM DESIGN PRESSURE OF -60 PSF. SPECIFY THE | | | FASTENER AS WELL AS THE LAP AND FIELD SPACING FOR THE | | | ANCHOR SHEET. THE NOTE ON PAGE 8 STATE THAT THE | | | INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT | | | ASPHALT. SHOW ALL OF THE RAS 117 CALCULATIONS THAT WERE | | | USED TO DETERMINE THE ENHANCED FASTENER SPACING. IT IS | | | UNCLEAR WHY THE NUMBER OF INSULATION BOARD FASTENERS | | | WAS PROVIDED. FBC 107.2.1.4 | | | | | | 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION | | | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-15 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
08:59 |
Sent To |
E |
|
| Notes |
| 2014-07-14 18:21:49 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE WIND DESIGN DATA IN THE WIND PRESSURE SCHEDULE | | | ON SHEET A.07 IS INCORRECTLY SPECIFIED AS 140 MPH AND | | | THE PRESSURES ARE INCORRECT. THE WINDSPEED FOR THIS | | | PROJECT IS 170 MPH AND THE EXPOSURE CATEGORY IS C. THE | | | WIND SPEED IS SPECIFIED AS 170 MPH AND EXPOSURE D ON | | | SEVERAL OF THE PLAN SHEETS. PLEASE CORRECT AND SPECIFY | | | THE WIND PRESSURES FOR THE CORRESPONDING WINDSPEED, | | | ROOF HEIGHT AND EXPOSURE CATEGORY. FBCR 301.2.1 | | | | | | 2) THE APPLICABLE EDITION OF THE NATIONAL ELECTRICAL | | | CODE ( NEC) IS THE 2008. THE APPLICABLE EDITION OF THE | | | FLORIDA FIRE PREVENTION CODE IS THE 2010 EDITION. THIS | | | IS LISTED ON SEVERAL OF THE PLAN SHEETS. IT IS CORRECT | | | ON SOME AND NOT ON OTHERS. PLEASE CORRECT. | | | | | | 3) SUBMIT TWO SETS OF ENERGY COMPLIANCE DOCUMENTS AS | | | REQUIRED BY FBC ENERGY CONSERVATION SECTION 103. | | | | | | 4) THERE ARE CONFLICTING NOTES REGARDING THE ATTIC | | | INSULATION. WALL SECTION C ON A.07 HAS A NOTE | | | SPECIFYING R-30 INSULATION WITH AN ARROW POINTING TO | | | THE BOTTOM CORD OF THE TRUSS, HOWEVER, THE INSULATION | | | IS SHOWN ON THE TOP CORD. A NOTE ON SHEET A.04 | | | SPECIFIES SPRAY FOAM INSULATION ON THE TOP CORD. THERE | | | ARE ROOF VENT CALCULATIONS AND OFF RIDGE ROOF VENTS | | | SHOWN ON SHEET A.06. THE SPRAY FOAM ON THE UNDER SIDE | | | OF THE ROOF DECK IS TYPICALLY USED WITH UN-VENTED | | | ATTICS, AS THE ATTIC IS CONSIDERED CONDITIONED SPACE | | | WITH THIS APPLICATION. PLEASE CLARIFY AND COORDINATE | | | THE INFORMATION ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | | | 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE | | | SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316. | | | | | | 6) ON SHEET A.07 THE DETAILS FOR THE EXTERIOR WINDOW | | | HEAD, SILL AND JAMB SHOW LATH AND PLASTER (STUCCO) AND | | | NOT THE CEMENTITIOUS SIDING THAT IS SPECIFIED ON THE | | | OTHER PLAN SHEETS. PLEASE CORRECT. CITY AMENDMENTS | | | 107.2.1 | | | | | | 7) ON SHEET A.08, SOME OF THE ID TAGS ON THE FOUNDATION | | | PLAN DO NOT MATCH THE DETAILS OR THE DETAILS ARE | | | MISSING. THERE ARE TWO DIFFERENT DETAILS NUMBERED 2 AND | | | TWO MORE NUMBERED 6. THERE WERE ALSO TWO PLAN SHEETS | | | NUMBERED A.08 IN BOTH OF THE PLAN SETS THAT WERE | | | SUBMITTED. PLEASE REVIEW PLANS FOR ACCURACY AND | | | CONSISTENCY, THEN MAKE CORRECTIONS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 8) ON SHEET A.08, THE ELEVATION FOR THE TOP OF THE SLAB | | | AT THE LOGGIA INDICATES THAT IT IS 4" HIGHER THAN THE | | | HOUSE SLAB. THERE IS A NOTE THAT INDICATES THERE IS A | | | 6" STEP DOWN. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | | | 9) THERE IS A 6" STEP DOWN AND A 6" WHEEL STOP SHOWN IN | | | THE GARAGE ON SHEET A.04. THE FOUNDATION PLAN ON A.08, | | | DOES NOT SHOW THE 6" INCH WHEEL STOP. PLEASE CLARIFY. | | | CITY AMENDMENTS 107.2.1 | | | | | | 10) PROVIDE A STRUCTURAL DETAIL VIEW OF THE 4 X 6 WOOD | | | POSTS' TOP AND BOTTOM CONNECTIONS. FBCR 301.1 | | | | | | 11) SUBMIT THE MANUFACTURER'S INSTALLATION GUIDE AND | | | SPAN TABLES FOR THE LAMINATED VENEER LUMBER BEAMS. FBCR | | | 301.1 & R602.1.1.2 | | | | | | 12) THE DESIGN PRESSURES FOR THE CLOPAY OVERHEAD GARAGE | | | DOOR, FL 15279 ARE LOWER THAN THE REQUIRED WIND LOAD | | | PRESSURES FOR THE END ZONE OF A TWO STORY STRUCTURE | | | LOCATED IN EXPOSURE D OR C WITH A 170 MPH VULT WIND | | | SPEED. | | | | | | 13) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | EXTERIOR CEMENTITIOUS SIDING AND THE STRUCTURAL | | | MULLIONS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 14) SPECIFY THE APPROVED SYSTEM AND THE FASTENING | | | OPTION THAT WILL BE USED FOR THE GAF RUBEROID MODIFIED | | | BITUMEN SYSTEM, NOA NO. 13-0424.14. SUBMIT TWO SETS OF | | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED | | | FASTENING AT THE PERIMETER AND CORNER AREAS AS REQUIRED | | | BY LIMITATION #7 OF THE NOA. CITY AMENDMENTS 107.2.1 & | | | FBCR 301.2.1 | | | | | | 15) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW ITEMS | | | HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-04 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-04 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-11-21 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-21 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-21 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2014-11-21 14:25:17 | 11/21/2014 | | | PROJECT: VALLY FORGE RESIDENCE | | | PERMIT#: 14061120 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) REVISE THE RISER DIAGRAM TO INCLUDE THE FEED TO THE | | | PANEL IN THE GARAGEANY POWER IN THE SHED BUILDING AND | | | TO INDICATE THE NEW PANEL IS NEMA 3R APPROVED FOR USE | | | OUTDOORS. | | | | | | 2) PROVIDE ELECTRICAL PANEL SCHEDULE FOR BOTH | | | ELECTRICAL PANELS. | | | | | | 3) VERIFY THE EXISTANCE OR THE INSTALLATION OF SMOKE/CO | | | DETECTORS IN COMPLIANCE WITH THE FBC -R 314, 315 | | | | | | 4) PROVIDE CIRCUITING ON THE FLOOR PLAN THAT COINCIDES | | | WITH THE PANEL SCHEDULES TO BE PROVIDED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-18 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-18 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2014-07-18 13:30:07 | DATE: 7/18/2014 | | | PROJECT: PINSKY ADDITION | | | PERMIT#: 14061120 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | CLARIFICATION REQUIRED. SITE PLAN INDICATE THE EXISTING | | | ELECTRICAL METER AT A SHED IN THE BACK YARD. THE | | | ELECTRICAL PLAN INDICATES A NEW SERVICE BUT THE | | | LOCATION OF THE SERVICE IS NOT IDENTIFIED. FBC WPB | | | AMENDMENTS. 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND | | | LEAVE THE PREVIOUSLY REVIEWED SHEETS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-14 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2014-07-14 14:25:27 | A SEPARATE GAS PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED. NO APPLICATION OR PLANS FOR GAS WERE | | | SUBMITTED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-04 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-05-20 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-21 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-21 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-10-23 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-18 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-06-24 |
Time |
17:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2015-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-04 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-04 |
Time |
07:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-19 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-17 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2014-11-19 16:20:58 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-14 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2014-07-14 13:38:59 | IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. 233-5025 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2015-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-04 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-04 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2015-06-04 07:25:58 | A MECHANICAL APPLICATION IS ATTACHED, BUT THERE IS | | | MECHANICAL DESIGN SUBMITTED. THIS APPLICATION SHOULD BE | | | WITHDRAWN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2014-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-17 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-17 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2014-11-17 08:18:37 | A SEPARATE MECHANICAL PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED. NO APPLICATION OR PLANS FOR MECHANICAL WORK | | | WERE SUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-14 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2014-07-14 15:37:27 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED. SUBMIT TWO SETS | | | OF MECHANICAL PLANS. SPECIFY THE DUCT SIZES AND | | | LOCATIONS. SPECIFY THE GRILL LOCATIONS, SIZES AND CFMS | | | AT EACH OUTLET. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 3) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | | CITY AMENDMENTS 107.2.1 | | | | | | 5) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | | 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-19 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-19 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-14 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-14 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2014-07-14 15:15:22 | ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED. | | | | | | 1) GAF ASPHALT SHINGLES - FL #10124 | | | | | | 2) GAF RUBEROID MODIFIED BITUMEN - NOA NO. 13-0424.14 | | | (REQUIRES RAS 117 CALCULATIONS) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-10-27 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-10-27 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-10-24 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2014-10-27 08:20:40 | 10/27/14 | | | | | | 1. APPLICANT SUBMITTED LANDSCAPE SKETCH DEMONSTRATING | | | COMPLIANCE WITH MINIMUM LANDSCAPING REQUIREMENTS. NO | | | ADDITION PLANTINGS REQUIRED. | | | | | | 2. SITE PLAN SHOWS 'TREE TO BE REMOVED' WHICH DOES NOT | | | EXIST AND NOTATION ADDED TO PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-06-30 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-06-30 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-06-30 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2014-06-30 14:25:22 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 6/30/14 | | | | | | 1. NEW AC UNIT CANNOT PROJECT MORE THAN FOUR (4) FEET | | | INTO A REQUIRED SETBACK. PROVISO WILL BE ADDED TO THE | | | PLANS. | | | | | | 2. THE VALUE OF THE CONSTRUCTION ($50,000) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($86,809) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR SEC. | | | 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT | | | LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE | | | PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR | | | PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT | | | LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE | | | FEET OF OPEN SPACE OR PORTION THEREOF.) | | | | | | 3. TREE ALTERATION PERMIT THROUGH THE PLANNING DEPT. IS | | | REQUIRED FOR THE REMOVAL OR RELOCATION OF ANY TREES | | | REQUIRED FOR THE NEW CONSTRUCTION. HTTP://WPB.ORG/PLANN | | | ING/WP-CONTENT/UPLOADS/SITES/37/2013/04/TREEALTERATIONP | | | ERMITREVISED03-12-09.PDF | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | | | 2014-06-25 11:52:13 | 6/25/14 |
|
|