| 2014-06-24 08:59:15 | ELECTRICAL PERMIT WAS CHANGED TO A SUB PERMIT UNDER |
| | PRIMARY PERMIT #14070238. ELECTRICAL WAS PASSED UNDER A |
| | SUBSEQUENT REVIEW BY RL. SEE PERMIT #14070238 FOR NEW |
| | ELECTRICAL PLAN REVIEW. |
| | |
| | DATE: 6/24/2014 |
| | PROJECT: FED EX |
| | PERMIT#: 14060928 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: |
| | FBC 107.2.1, 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED |
| | AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA |
| | DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE |
| | BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5).. ELECTRICAL_OVERCURRENT PROTECTION, |
| | GROUNDING, WIRING METHODS AND MATERIALS. |
| | 107.2.5_107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION |
| | |
| | 1) ADDITIONAL PERMITS SUCH AND A BUILDING PERMIT TO |
| | EXAMINE THE CODE REQUITEMENTS OF THE STRUCTUAL SUPPORT |
| | AND INSTALLATION, A FIRE PERMIT TO EXAMINE THE LIFE |
| | SAFETY ISSUES, ASSOCIATED WITH THE CONVEYOR SYSTEM AND |
| | HOW THE NEW INSTALLATION AFFECTS THE CURRENT LIFE |
| | SAFETY EXIT REQUIREMNTS OF THE FACILITY MAY BE REQUIRED |
| | FOR THE COMPLETE INSTALLATION OF THE NEW CONVEYOR |
| | SYSTEM. THE ELECTRICAL PERMIT CANNOT BE ISSUED UNTIL |
| | THE PERMIT FOR THE INSTALLATION OF THE CONVEYOR SYSTEM |
| | HAS BEEN APPROVED AND ISSUED. PLEASE SUBMIT ALL |
| | SUPPORTING DOCUMENTATION LISTED BELOW AND UPON REVEIW |
| | OF SUPPORTING DOCCUMENTATION ADDITIONAL PERMIT TYPES |
| | SHALL BE ASSIGNED AND THE CONTRACTOR WILL BE NOTIFIED. |
| | |
| | 2) ADDITIONAL INFORMATION REQUIRED. FBC WPB AMENDMENTS. |
| | 107.2.1. PLANS ARE INCOMPLETE. ALL ASPECTS OF THE |
| | OVERALL INSTALLATION SHALL BE INCLUDED WITH THE |
| | SUBMITTAL. THE CONNECTION UP OF THE NEW CONVEYOR SYSTEM |
| | WILL REQUIRE BUT NOT BE LIMITED TO THE FOLLOWING |
| | ADDITIONAL DOCUMENTATION: |
| | |
| | A) A SITE PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL SERVICE. |
| | B) ANY DEMOLITION THAT MAY OR MAY NOT BE INVOLVED TO |
| | MAKE ROOM FOR THE NEW CONVEYOR SYSTEM. |
| | C) A FLOOR PLAN INDICATING THE LAYOUT OF THE NEW |
| | CONVEYOR SYSTEM AND LOCATION OF ELECTRICAL PANELS, |
| | DISCONNECTS, STARTERS, VFD'S ETC.. REQUIRED FOR THE |
| | CONNECTION AND SAFE OPERATION OF THE NEW CONVEYOR |
| | SYSTEM. |
| | THE FLOOR PLAN SHALL ALSO PROVIDE AND ILLUSTRATE THE |
| | SAFE WORKING CLEARANCES AND DEDICATED WORKING SPACE AND |
| | ILLUMINATION AT ALL ELECTRICAL EQUIPMENT, PANEL BOARDS |
| | AND TRANSFORMERS PER THE NEC 110.26 AND 240.24. |
| | D) A LIFE SAFETY PLAN INDICATING THE REQUIRED EXIT |
| | PATHS FOR THE NUMBER OF PEOPLE IN THE SPACE. NFPA 101 |
| | E) A LIGHTING PLAN INDICATING PROPER ILLUMINATION |
| | AROUND THE CONVEYOR SYSTEM AND RELATED ELECTRICAL |
| | EQUIPMENT FOR ITS SAFE OPERATION NEC 110.26(D) |
| | F) THE LIGHTING PLAN SHALL INCLUDE ALL EMERGENCY AND |
| | EXIT LIGTING FOR A SAFE ILLUMINATED MEANS OF EGRESS |
| | ALONG THE LIFE SAFETY PLAN. NFPA 101 |
| | G) DEPENDING ON THE SCOPE OF WORK AND SIZE OF THE |
| | BUILDING THE PROJECT MAY NEED TO BE IN COMPLIANCE WITH |
| | CHAPTER 505 OF THE FBC-ENERGY. |
| | H) A SINGLE LINE RISER DIAGRAM INDICATING FROM THE |
| | SOURCE, METER, MAINS, OCPD'S REQUIRED FOR THE |
| | CONNECTION OF THE NEW CONVEYOR SYSTEM. FBC 107.2.1 |
| | I) THE DEMOLITION OF ANY ELECTRICAL EQUIPMENT THAT MAY |
| | OR MAY NOT BE PROPOSED TO BE REMOVED TO MAKE WAY FOR |
| | THE NEW CONVEYOR SYSTEM. |
| | J) A LOAD CALCULATION INDICATING THE AVIALABILITY OF |
| | THE CAPACITY REQUIRED TO ADD THE ADDITIONAL LOAD OF THE |
| | NEW CONVEYOR SYSTEM. NEC 220 |
| | K) THE PANEL SCHEDULES REQUIRED TO INDICATE THE |
| | CIRCUITRY REQUIRED FOR THE CONNECTION OF ANY NEW |
| | EQUIPMENT RELATED TO THE CONNECTION OF THE NEW CONVEYOR |
| | SYSTEM. NEC 408 |
| | L) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 |
| | M) SHOP DRAWINGS, EQUPMENT MANUALS AND SPECIFICATIONS |
| | FROM THE MAUFACTURER ON ALL ASPECTS OF THE NEW CONVEYOR |
| | SYSTEM, INCLUDING BUT NOT LIMITED TO ELECTRICAL |
| | SPECIFICATIONS, MECHANICAL AND STRUCTURAL SUPPORT |
| | SPECIFICATIONS. |
| | |