2014-07-10 11:33:416651 NORTH JOG ROAD - REFUSE BUILDING: CLEAN AGENT
 SYSTEM
 PERMIT #14060916
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TO BE CONSIDERED A "FULLY SPRINKLERED" BUILDING, THE
 STATE OF FLORIDA REQUIRES AREAS PROTECTED BY CLEAN
 AGENT SYSTEMS TO ALSO BE PROTECTED WITH AUTOMATIC
 SPRINKLERS. THE FIRE DEPARTMENT RECOMMENDS PROTECTING
 THESE SPACES WITH A DOUBLE INTERLOCK PREACTION SYSTEM
 AS BACK-UP PROTECTION TO THE CLEAN AGENT SYSTEM.
  
 NOTE: FULLY SPRINKLERED BUILDINGS ARE ALLOWED
 TRADE-OFFS SUCH AS BUILDING HEIGHT AND AREA INCREASES,
 TRAVEL DISTANCE TO EXIT INCREASES, ETC.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-15 Cont ID  
Sent By hmoser Date 2014-07-15 Time 14:11 Rev Time 0.00
Received By hmoser Date 2014-06-23 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-07-15 Cont ID  
Sent By hmoser Date 2014-07-15 Time 14:11 Rev Time 0.00
Received By hmoser Date 2014-07-15 Time 13:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-07-29 Cont ID  
Sent By skennedy Date 2014-07-29 Time 10:41 Rev Time 0.00
Received By skennedy Date 2014-07-25 Time 15:48 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved