| 2014-07-12 10:04:32 | BUILDING PLAN REVIEW |
| | PERMIT: 14060889 |
| | ADD: 1865 PALM BEACH LAKES SUITE # B24 |
| | CONT: IBEX CONSTRUCTION |
| | TEL: (786)586-2636 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JULY 12/ 2014 |
| | ACTION: DENIED |
| | |
| | BUILDING TYPE : IIB |
| | |
| | 1) THE PLANS DO NOT HAVE THE JOBSITE ADDRESS ON THE |
| | PLANS. THE PERMIT APPLICATIONS' ADDRESS HAD THE WRONG |
| | SUITE NUMBER, THE CORRECT SUITE NUMBER IS B-24. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. . CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED. |
| | 2010 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS NUMBERS OR LETTERS. |
| | |
| | 2A) THE PLANS HAVE NOT BEEN STAMPED APPROVED BY THE |
| | LANDLORD COORDINATOR NEW ENGLAND DEVELOPMENT PALM BEACH |
| | OUTLET MALL SKYE GROUP TENANT COORDINATOR. |
| | |
| | 2B) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF |
| | BOTH THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT |
| | BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT |
| | BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL |
| | DATA REQUIRED. |
| | |
| | 3) THE PLANS HAVE NOT BEEN STAMPED BY THE DESIGNER OF |
| | RECORD. FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE |
| | FOR SUPERVISING AND REVIEWING ALL PROJECT DATA, |
| | REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 4) THE SUBMITTED PLANS ARE NOT ALL STAMPED BY THE |
| | DESIGN ENGINEER FOR THE MCM PANELS. SHEETS MISSING SEAL |
| | & SIGNATURE ARE 001, 002, 003, 200 & 201. THE ACTUAL |
| | ENGINEERING SHEETS ALL NEED TO BE SIGNED AND SEALED |
| | 61G15-23.002(2) ALLOWS FOR REPORTS AND SPECIFICATIONS |
| | TO HAVE A COVER SHEET SEALED ONLY. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, MCM PANELS |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) PLEASE MAKE THE FOLLOWING CORRESTIONS TO THE |
| | STRUCTURAL CALCULATIONS SUBMITTED. |
| | 7A) THE LOCATION STATES THIS LOCATION IS PALM BEACH , |
| | FL. THE OUTLET MALL IS LOCATED IN WEST PALM BEACH, FL. |
| | PALM BEACH WOULD BE CONSIDERED A "D" EXPOSURE WEST PALM |
| | BEACH, FL IS CONSIDERED A " C" EXPOSURE. 2010 FBC-B |
| | 1609. 4.2&3. |
| | |
| | 7B) THE ALUMINIUM PANEL WIND LOAD CALCULATION SHEET THE |
| | WIND DESIGN IS TO THE ASCE & -05. THE 2010 FBC-B USES |
| | THE ASCE 7-10 VULT AS THE CORRECT DESIGN. PRESSURES |
| | WILL NEED TO BE IN VULT AND VASD SINCE THE PRODUCT |
| | APPROVALS ARE IN VASD. 2010 FBC-B 1609.1.5. |
| | |
| | 8) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. |
| | WHERE INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 1407.10.1 THROUGH 1407.10.4, OR SECTION 1407.11. |
| | |
| | 1407.10.1 SURFACE-BURNING CHARACTERISTICS. |
| | MCM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 |
| | AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 WHEN |
| | TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED |
| | FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |