Plan Review Details - Permit 14060869
Plan Review Stops For Permit 14060869
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-17 Cont ID  
Sent By rmcdouga Date 2014-09-17 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2014-09-17 Time 10:24 Sent To E
Notes
2014-12-10 10:26:15THE STRUCTURE IS NOT TO BE USED AS AN ACCESSORY
 APARTMENT. IT IS TO REMAIN AS A UTILITY OCCUPANCY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-09 Time 11:32 Rev Time 0.00
Received By rmcdouga Date 2014-07-09 Time 06:38 Sent To  
Notes
2014-07-09 07:24:162010 FBC
  
 DENIED BY BUILDING
  
 THE SCOPE OF WORK FOR THIS PERMIT IS TO ADDRESS THE
 ILLEGAL CONVERSION OF AN EXISTING GARAGE TO AN
 APARTMENT OR ACCESSORY STRUCTURE.
 ACCORDING TO CITY RECORDS, THIS STRUCTURE WAS
 ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE. IT WAS
 CONVERTED TO AN APARTMENT WITH A KITCHEN, BEDROOM AND
 BATHROOM WITHOUT THE REQUIRED PERMITS OR INSPECTIONS.
 UNDER THE 2010 FBC EXISTING BUILDING THIS IS CONSIDERED
 A CHANGE OF OCCUPANCY. IN ORDER FOR THIS STRUCTURE-TO
 BE BROUGHT INTO COMPLIANCE, IT WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBC EXISTING BUILDING FOR A CHANGE
 OF OCCUPANCY FROM A UTILITY TO AN R-3 OCCUPANCY. THIS
 CHANGE IS FROM A LOWER HAZARD CATEGORY TO A HIGHER ONE.
 THEREFORE, THE FOLLOWING ITEMS WILL NEED TO BE BROUGHT
 INTO COMPLIANCE. THE STRUCTURE WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBCR WINDLOAD REQUIREMENTS FOR THE
 BUILDING ENVELOPE ( IN ADDITION TO GRAVITY LOADS),
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND WINDOWS,
 EGRESS REQUIREMENTS, LIGHT AND VENTILATION, SMOKE AND
 CARBON MONOXIDE ALARMS, FIRE PROTECTION REQUIREMENTS
 (SEPARATION DISTANCE AND ALLOWABLE OPENINGS), THE
 REQUIREMENTS OF THE 2010 FBC ENERGY CONSERVATION, THE
 REQUIREMENTS OF THE 2010 FBCR MECHANICAL, THE
 REQUIREMENTS OF THE 2010 FBCR PLUMBING AND THE
 ELECTRICAL SYSTEM WILL BE REQUIRED TO COMPLY WITH THE
 2008 NATIONAL ELECTRICAL CODE. THE PLANS WILL NEED TO
 SHOW HOW THE GARAGE WILL BE CONVERTED TO HABITABLE
 SPACE IN COMPLIANCE WITH THE 2010 FBC AND 2008 NEC. THE
 PLANS WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY TO
 DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 1) THIS IS NOT A LEVEL 2 ALTERATION AS INDICATED ON
 SHEET 1 OF THE PLANS. THIS IS A CHANGE OF OCCUPANCY
 FROM A LOWER HAZARD (U, UTILITY/GARAGE ) TO A HIGHER
 ONE (R-3, RESIDENTIAL). FBC EXISTING BUILDING SECTION
 406. PLEASE CORRECT.
  
 2) SHOW THAT THE EXTERIOR DOOR COMPLIES WITH FBCR 311.2
 FOR EGRESS.
  
 3) THE ROOM WITH THE CLOSET APPEARS TO BE A BEDROOM
 ALTHOUGH IT IS SPECIFIED AS A RECREATION ROOM ON THE
 PLANS. THIS ROOM IS REQUIRED TO HAVE AN EMERGENCY AND
 RESCUE OPENING. AN EXISTING OPERABLE WINDOW WITH CLEAR
 OPENING AREA NO LESS THAN 4 SQUARE FEET AND WITH
 MINIMUM OPENING WIDTH AND HEIGHT OF 22 INCHES AND 20
 INCHES RESPECTIVELY, WITH MAXIMUM SILL HEIGHT AT 44
 INCHES ABOVE THE FLOOR IS ALLOWED BY FBC EXISTING
 BUILDING SECTION 912.4.1 EXCEPTION NUMBER 7.
  
 4) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS
 AS REQUIRED FOR NEW DWELLINGS.
  
 5) FBC EXISTING BUILDING SECTION 907.2 REQUIRES THE
 STRUCTURE TO BE ANALYZED AND MADE TO COMPLY WITH THE
 APPLICABLE WINDLOADS OF THE FLORIDA BUILDING CODE.
 PROVIDE DOCUMENTATION TO SHOW COMPLIANCE. SUBMIT
 STRUCTURAL DRAWINGS AND DETAILS. CITY AMENDMENTS
 107.2.1
  
 6) SUBMIT PRODUCT APPROVALS FOR EXTERIOR DOORS AND
 WINDOWS AS REQUIRED BY DCA RULE 9N-3.
  
 7) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR LARGE
 MISSILE IMPACT PROTECTION OF EXTERIOR GLAZED OPENINGS.
  
 8) THE DESIGN CRITERIA ON SHEET 1 STATES THAT THIS IS A
 PARTICALLY OPEN STRUCTURE. THE PLANS THAT WERE
 SUBMITTED SHOW THIS IS AN ENCLOSED STRUCTURE. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 9) PROVIDE A RESPONSE LETTER INDICATING HOW THE REVIEW
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-12-10 Cont ID  
Sent By dhayes Date 2014-12-10 Time 09:33 Rev Time 0.00
Received By dhayes Date 2014-12-10 Time 09:33 Sent To  
Notes
2014-12-10 09:40:20SEE ELECTRICAL PERMIT #14090886 WHICH WAS ISSUED AS A
 STAND ALONE PERMIT SUBMITTED SEPARATLY AT A LATER DATE
 BY NON-STOP ELECTRIC HIRED DIRECTLY BY THE OWNER NOT BY
 MAKO CONSRTUCTION TO COMPLETE THE ELECTRICAL SERVICE,
 SUB-PANEL AND ELECTRICAL TANKLESS WATER HEATER SCOPE OF
 WORK. THE PERMIT WAS ISSUED. THE WORK WAS COMPLETED,
 INSPECTED AND FINALED ON 10/09/14 SEE INSPECTION
 RESULTS BELOW:
  
 PERMIT #14090886
 203 1 0008-E 10/09/2014 10/09/2014 P
  
 THIS IS FOR THE ELECTRICAL SERVICE RISER, SUB-PANEL AND
 CONNECTION OF THE ELECTRIC TANKLESS WATER HEATER ONLY.
 THE SAME ELECTRICAL CONTRACTOR HAS STATED HE WILL COME
 IN TODAY OR TOMORROW TO SUBMIT ANOTHER PERMIT
 APPLICATION FOR THE BALANCE OF ELECTRICAL WORK ON THIS
 PLAN.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 09:22 Rev Time 0.00
Received By dhayes Date 2014-12-01 Time 09:21 Sent To  
Notes
2014-12-01 11:54:48DATE: 12/1/2014
 PROJECT: UTILITY STRUCTURE RENNOVATION
 PERMIT#: 14060869
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE SITE PLAN THE LOCATION OF THE ELECTRICAL
 SERVICE WITH 200AMP MAIN (PANEL), THE HOUSE PANEL, AND
 TANKLESS WATER HEATER,
  
 2) PROVIDE A COMPLETE LOAD CALCULATION. LOADS FOR NEW
 CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY WIRED
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 NEC 220.12 OR 220.14, AS APPLICABLE. NEC 220.40, NEC
 220.16(2)
  
 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION IN THE PANEL
 SCHEDULE SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR,
 EVIDENT, AND SPECIFIC PURPOSE OR USE. ADD CIRCUIT IN
 THE SUB-PANEL TO IDENTIFY THE A/C CU. NEC 408.4,
  
 4) REVISE THE RISER DIAGRAM TO INDICATE HOW THE 150AMP
 HOUSE PANEL, THE 125AMP UTILITY RM PANEL, AND NOW THE
 TANKLESS WATER HEATER ARE FED.
  
 5) REVISE THE RISER DIAGRAM TO INDICATE THE CORRECT
 SIZED CONDUCTORS ARE IN THE SERVICE RISER MAST AND
 NIPPLE TO THE "MAIN"(PANEL) ARE APPROVED FOR THE TOTAL
 CONNECTED LOAD TO BE SERVED. THE CONDUCTOR SIZES
 CURRENTLY INDICATED ON THE RISER DIAGRAM ARE NOT
 APPROVED FOR THE LOAD TO BE SERVED.
  
 6) INDICATE THE LOCATION AND MEANS OF DISCONNECT FOR
 THE TANKLESS WATER HEATER, A/C CU, AND AHU. NEC 422.31,
 WPB AMENDMENTS TO FBC 107.3.2
  
 7) REVISE THE FLOOR PLAN TO INCLUDE THE CIRCUIT NUMBERS
 TO COINCIDE WITH THE PANEL SCHEDULE. ADD THE CIRCUIT
 FOR THE A/C, CU AND THE TANKLESSS WATER HEATER. FBC- 1
 07.3.5.3
  
 8) VERIFY THE FLOOR PLAN TO INDICATE RECEPTACLE OUTLETS
 ARE INSTALLED AT EACH KITCHEN COUNTERTOP SPACE THAT IS
 12" OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24"
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE
 OUTLET. NEC 210.52(C)(1)
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 11) A BONDING STRIP IS REQUIRED AT SERVICE GROUND. NEC
 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-18 Cont ID  
Sent By dhayes Date 2014-09-18 Time 07:48 Rev Time 0.00
Received By dhayes Date 2014-09-18 Time 07:48 Sent To  
Notes
2014-09-18 08:03:51DATE: 9/18/2014
 PROJECT: UTILITY STRUCTURE RENNOVATION
 PERMIT#: 14060869
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE TOTAL KW LOAD INDICATED AT THE UTILLITY RM SUB
 PANEL IS 35.4KW WHICH WOULD BE THE EQUIVILANT OF
 147AMPS NOT 90 AMPS AS INDICATED AT THE RISER DIAGRAM,
 THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE
 LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS
 SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE,
 AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART
 III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. NEC
 220.40
 PROVIDE A COMPLETE LOAD CALCULATION ON THE UTILITY
 STRUCTURE AND ON THE WHOLE ELECTRICAL SERVICE INCLUDING
 THE MAIN HOUSE. PROVIDE A PANEL SCHEDULE SHOWING ALL
 LOADS BALANCED. INDICATE THE PROPOSED WIRING METHOD,
 WIRE SIZE WITH OVER CURRENT PROTECTION FOR ALL
 CIRCUITS. NEC 215.5, 220.12, 220.40, 230.31
  
 2) THE ELECTRICAL SERVICE RISER DIAGRAM NEEDS TO BE
 REVISED TO INDICATE HOW THE TRANSITION IS MADE FROM THE
 200AMP MAIN BREAKER AT THE HOUSE TO FEED THE 150AMP
 HOUSE PANEL AND THE 125AMP UTILITY RM PANEL.
  
 3) INDICATE THE LOCATION AND MEANS OF DISCONNECT FOR
 THE ELECTRIC WATER HEATER, AND A/C AHU. NEC 422.31, WPB
 AMENDMENTS TO FBC 107.3.2
  
 5) A BONDING STRIP IS REQUIRED AT SERVICE GROUND. NEC
 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-09 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2014-07-09 Time 13:20 Sent To  
Notes
2014-07-09 14:15:512010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) ACCORDING TO THE ZONING REVIEW THIS LOT IS ZONED AS
 SINGLE FAMILY AND ONLY ONE METER IS ALLOWED FOR A
 SINGLE FAMILY DWELLING. SUBMIT AN ELECTRICAL RISER PLAN
 THAT SHOWS COMPLIANCE WITH THE ZONING CODE AND THE 2008
 NEC.
  
 2) THIS ACCESSORY STRUCTURE IS NOT ALLOWED TO HAVE A
 KITCHEN PER THE ZONING REVIEW. REMOVE THE KITCHEN FROM
 THE PLANS.
  
 3) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE
 SPACING.
  
 4) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT
 PROTECTION.
  
 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-10 Cont ID  
Sent By dhayes Date 2014-12-10 Time 09:33 Rev Time 0.00
Received By dhayes Date 2014-12-10 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 11:54 Rev Time 0.00
Received By dhayes Date 2014-11-22 Time 09:51 Sent To  
Notes
2014-11-22 09:51:39GAVE TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-18 Cont ID  
Sent By dhayes Date 2014-09-18 Time 09:14 Rev Time 0.00
Received By dhayes Date 2014-09-11 Time 07:19 Sent To  
Notes
2014-09-12 07:19:38SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-09 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 11:24 Sent To  
Notes
2014-06-23 11:24:43SENT TO R13 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2014-12-10 Time 10:00 Sent To  
Notes
2014-12-10 10:06:07DETACHED STRUCTURE IS TO REMAIN AS STORAGE/UTILITY.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-09-17 Cont ID  
Sent By rmcdouga Date 2014-09-17 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2014-09-17 Time 11:09 Sent To  
Notes
2014-09-17 11:11:19IMPACT FEES
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-09 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2014-07-09 Time 07:24 Sent To  
Notes
2014-07-09 07:43:03THIS WAS A GARAGE THAT WAS CONVERTED TO LIVING SPACE.
 WHEN THE PLANS HAVE BEEN APPROVED, ONE OF THE APPROVED
 SETS IS REQUIRED TO BE SIGNED OUT AN TAKEN TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT REVIEW STAMP AND A COPY OF THE PAID RECEIPT
 ARE REQUIRED TO BE RETURNED TO THE CITY BEFORE THE
 BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-11-22 Cont ID  
Sent By rmcdouga Date 2014-11-22 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2014-11-22 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-17 Cont ID  
Sent By rmcdouga Date 2014-09-17 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2014-09-17 Time 10:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-08 Cont ID  
Sent By rmcdouga Date 2014-07-08 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2014-07-08 Time 18:46 Sent To  
Notes
2014-07-08 18:49:182010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 FOR THE HEATING AND COOLING EQUIPMENT. FBCR M1401.3
  
 2) SPECIFY THE SIZE OF ALL DUCTS, GRILL SIZES AND CFMS
 AT EACH SUPPLY OUTLET ON THE PLANS.
  
 3) RETURN AIR CAN NOT BE TAKEN FROM A CLOSET. SHOW HOW
 THE RETURN AIR TO THE AIR HANDLER WILL BE PROVIDED.
 FBCR M 1602.2
  
 4) SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED
 RETURN AIR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-11-22 Cont ID  
Sent By rmcdouga Date 2014-11-22 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2014-11-22 Time 09:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-17 Cont ID  
Sent By rmcdouga Date 2014-09-17 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2014-09-17 Time 10:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-08 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2014-07-08 Time 18:41 Sent To  
Notes
2014-07-08 18:45:112010 FBC
  
 DENIED BY PLUMBING
  
 1) SPECIFY THE SIZES OF ALL SANITARY AND VENT PIPING ON
 THE PLANS. FBCR P3001.1 AND P3101.1
  
 2) THE FIXTURE OUTLET AT THE KITCHEN IS LABELED AS A
 LAVATORY AND THE CLOTHES WASHER IS ALSO LABELED AS A
 LAVATORY. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By dkittred Date 2014-09-12 Time 09:50 Rev Time 0.00
Received By dkittred Date 2014-09-12 Time 09:49 Sent To  
Notes
2014-09-12 10:07:159/12/14 - SENT TO RM. DK

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-25 Cont ID  
Sent By dkittred Date 2014-06-25 Time 12:32 Rev Time 0.00
Received By dkittred Date 2014-06-25 Time 12:15 Sent To  
Notes
2014-06-25 12:32:36PLANNING AND ZONING COMMENTS: ***FAILED***
  
 6/25/14
  
 ZONING OF 430 NOTTINGHAM BLVD. IS MF20. BASED ON A LOT
 SIZE OF 50' X 100', ONLY A SINGLE FAMILY RESIDENCE IS
 PERMITTED AT THIS LOCATION. IT APPEARS THE ACCESSORY
 STRUCTURE IS BEING CONVERTED TO AN ACCESSORY APARTMENT.
 ACCESSORY STRUCTURE IS PERMITTED TO BE CONVERTED TO
 HABITABLE SPACE FOR USE BY THE MAIN RESIDENCE ONLY, BUT
 CAN NOT BE A SEPARATE ACCESSORY APARTMENT. AS A
 RESULT...
  
 1. NO KITCHEN FACILITIES, WHICH INCLUDES STOVE (OR
 OTHER COOKING FACILITIES), FULL SIZE REFRIGERATOR,
 AND/OR FULL SINK ARE PERMITTED IN THE RENOVATED
 ACCESSORY STRUCTURE. PLEASE INDICATE COMPLIANCE WITH
 THIS ITEM AS THE PLANS CURRENTLY DEPICT WHAT APPEARS TO
 BE A KITCHEN IN THE ACCESSORY STRUCTURE,
  
 2. MULTIPLE ELECTRIC METERS FOR THE PROPERTY ARE NOT
 PERMITTED. IT APPEARS ON THE PLAN THAT THERE ARE TWO
 ELECTRIC METERS FOR THE SUBJECT PROPERTY. ONLY ONE WILL
 BE PERMITTED. PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  