Plan Review Details - Permit 14060858
Plan Review Stops For Permit 14060858
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-14 Cont ID  
Sent By rlecky Date 2014-08-14 Time 10:39 Rev Time 0.00
Received By rlecky Date 2014-08-14 Time 10:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-25 Cont ID  
Sent By cpuell Date 2014-09-25 Time 11:33 Rev Time 0.00
Received By cpuell Date 2014-09-19 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By hmoser Date 2014-08-15 Time 14:18 Rev Time 0.00
Received By hmoser Date 2014-07-17 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-15 Cont ID  
Sent By hmoser Date 2014-08-15 Time 14:17 Rev Time 0.00
Received By hmoser Date 2014-08-15 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 11: Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 15:11 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 13:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-09-25 Cont ID  
Sent By eschneid Date 2014-09-25 Time 11:11 Rev Time 0.00
Received By eschneid Date 2014-09-25 Time 11:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2014-08-21 Cont ID  
Sent By eschneid Date 2014-08-21 Time 15:24 Rev Time 0.25
Received By eschneid Date 2014-08-21 Time 15:24 Sent To  
Notes
2014-08-21 15:24:06FAILED
  
 PERMIT 14080386 WAS VOIDED - NO LONGER INCONSISTENCIES.
  
 PLEASE RESPOND IN WRITING.
  
 1) SHEET M201 SHOWS A GROUND MOUNTED AC UNIT (CU1).
 THIS UNIT APPEARS TO BE LOCATED IN THE SIDEWALK WHICH
 RUNS ALONG THE BUILDING. PROVIDE A SITE PLAN SHOWING
 THE LOCATION OF THE AC UNIT, INCLUDING THE SETBACK FROM
 PALM BEACH LAKES BOULEVARD.
  
 2) ADDITIONALLY, NO INFORMATION WAS PROVIDED AS TO HOW
 THIS UNIT WILL BE SCREENED FROM PALM BEACH LAKES
 BOULEVARD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-14 Cont ID  
Sent By eschneid Date 2014-08-14 Time 14:10 Rev Time 0.75
Received By eschneid Date 2014-08-14 Time 14:10 Sent To  
Notes
2014-08-14 14:17:16FAILED
  
 THESE PLANS HAVE A 7/1/14 DATE, YET THE PLANS WITH
 REVISION PERMIT 14080386 HAVE A 6/13/14 DATE. DUE TO
 THE OVERLAPPING PLANS CONFLICTING, STAFF IS UNABLE TO
 DETERMINE WHICH ONE IS TO BE REVIEWED AS THE CORRECT
 VERSION.
  
 COMMENTS RELATING SPECIFICALLY TO THIS REVIEW THAT WERE
 IDENTIFIED PRIOR TO THE VERSION INCONSISTENCY:
  
 SHEET M201 SHOWS A GROUND MOUNTED AC UNIT (CU1). THIS
 UNIT APPEARS TO BE LOCATED IN THE SIDEWALK WHICH RUNS
 ALONG THE BUILDING. ADDITIONALLY, NO INFORMATION WAS
 PROVIDED AS TO HOW THIS UNIT WILL BE SCREENED FROM PALM
 BEACH LAKES BOULEVARD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.