Plan Review Details - Permit 14060781
Plan Review Stops For Permit 14060781
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2014-08-08 Time 05:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-25 Cont ID  
Sent By jwitmer Date 2014-07-25 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2014-07-25 Time 06:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-30 Cont ID  
Sent By jwitmer Date 2014-06-30 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2014-06-28 Time 10:30 Sent To  
Notes
2014-06-30 13:52:47BUILDING PLAN REVIEW
 PERMIT: 14060781
 ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 30/ 2014
 ACTION: DENIED
  
 1) SHEET CS-2 INDICATES UNDER THE CODE ANALYSIS
 EXISTING BUILDING. NOTE THIS IS A SHELL BUILDING, NO
 FIRST TENANCY, THE 2010 FBC-BUILDING WILL BE USED FOR
 NEW BUILDINGS SINCE THERE HAS NEVER BEEN A C. O.
 ISSUED.
  
 2) SHEET CS-2 INDICATES A MEZZANINE AREA D-3 TO BE USED
 SOLEY FOR REFRIGARANT / WATER HEATING, NO STORAGE. THE
 UPPER HALF OF THE STAIRWAY IS ENCLOSED WITH A DOOR. THE
 2010 FBC-B 505.4 DOES ALLOW FOR ENCLOSED MEZZANINES
 WITH AN OCCUPANT LOAD OF LESS THAN 10 WHICH THIS DOES.
 THE ENCLOSING THE UPPER HALF OF THE STAIR DOES NOT GIVE
 A WORK MAN IN THIS SPACE ANY NOTIFICATION OF A FIRE AND
 SMOKE AND THE AMOUNT OF NOISE THE REFRIGARATION
 EQUIPMENT. FOR THIS REASON WE WOULD LIKE TO SUGGEST A
 STROBE THAT WOULD TIE INTO THE ALARM SYSTEM TO ALERT
 ANY WORKMAN IN THIS LIMITED SPACE TO EVACUATE. THIS
 SPACE NOW DOES NOT COMMUNICATE WITH THE REMAINDER OF
 THE 1 ST FLOOR. THERE IS NO ACTUAL CODE SECTION TO
 ADDRESS OUR CONCERNS, THIS CAN ONLY BE A SUGGESTION.
  
 3) SHEET A2.07 IDENTIFIES THE DOORS WITHIN TTHE
 TENANCY. DOORS 100,& 101 ARE IDENTIFIED AS EXISTING THE
 DOOR SCHEDULE FOUND ON A702
 THE NOTES DO NOT PROVIDE THE TYPE OF HARDWARE, NOTES
 INDICATE CYLINDER LOCK TO BE INSTALLED. PLEASE SHOW
 COMPLIANCE WITH 2010 FBC-B
 008.1.9.3 LOCKS AND LATCHES. 2.2. A READILY VISIBLE
 DURABLE SIGN IS POSTED ON THE EGRESS SIDE ON OR
 ADJACENT TO THE DOOR STATING: THIS DOOR TO REMAIN
 UNLOCKED WHEN BUILDING IS OCCUPIED. THE SIGN SHALL BE
 IN LETTERS 1 INCH (25 MM) HIGH ON A CONTRASTING
 BACKGROUND.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By dhayes Date 2014-07-17 Time 10:47 Rev Time 0.00
Received By dhayes Date 2014-07-17 Time 07:27 Sent To  
Notes
2014-07-17 13:59:02DATE: 7/14/2014
 PROJECT: WHOLE FOODS WPB
 PERMIT : 14060781
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) EMERGENCY LIGHTING REQUIRED FOR MEZZANINE AND
 STAIRWAY TO MEZZANINE.
  
 2) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR,
 GENERATOR, FIRE ALARM, SECURITY, NETWORK, ENERGY
 MANAGEMENT, REFRIGERATION CONTROL, AND POINT OF SALE
 SYSTEMS
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-28 Cont ID  
Sent By scaldero Date 2014-07-28 Time 11:25 Rev Time 0.00
Received By scaldero Date 2014-07-28 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-07-02 Cont ID  
Sent By scaldero Date 2014-07-02 Time 15:13 Rev Time 0.00
Received By scaldero Date 2014-07-02 Time 14:28 Sent To  
Notes
2014-07-02 15:11:52PERMIT # 14060781
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***FAILED COMMENTS TO BE ADDRESSED IN RESUBMITAL****
  
 1) THE REFLECTED CEILING PLAN A202 SHOWS THE LOCATION
 OF THE EXIT SIGNS, BUT DOES NOT INDICATE ANY EMERGENCY
 LIGHTING.
  
 2) PROVIDE DRAWING NOTE INDICATING THAT WHERE MUSIC
 SYSTEMS ARE BEING INSTALLED A RELAY TO THE FIRE ALARM
 SYSTEM MUST BE INCLUDED SO AS TO SHUT-OFF THE MUSIC
 UPON ACTIVATION OF THE FIRE ALARM SYSTEM.
  
 ***COMMENTS TO BE ADDRESSED IN THE FIELD.***
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOCKROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-07-25 Cont ID  
Sent By jwitmer Date 2014-07-25 Time 09:06 Rev Time 0.00
Received By jwitmer Date 2014-07-25 Time 07:47 Sent To  
Notes
2014-07-25 08:15:42FUEL GAS PLAN REVIEW
 PERMIT: 14060781
 ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW 1ST REVIEW WAS PART OF THE PLUMBING REVIEW
 DATE: FRI. JULY 25/ 2014
  
 ACTION: PROVISO
 FUEL GAS APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 NOTE: A SEPARATE PERMIT WILL ALSO NEED TO BE OBTAINED
 FOR A FUEL GAS PERMIT. SHEET P301 SHOWS THE GAS
 ISOMETRIC. THESE ARE THE REQUIREMENTS TO OBTAIN A FUEL
 GAS PERMIT:
  
 1) WITHOUT THE SUBMITTAL OF THE MANUFACTURERS
 SPECIFICATION SHEETS FOR THE GAS EQUIPMENT TO BE
 INSTALLED SIZING CAN NOT BE VARIFIED, CONTRACTOR IS AT
 OWN RISK. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2010 FUEL GAS SEC. 402.2. THE
 MANUFACTURER'S SPECIFICATIONS CAN BE SUBMITTED AS A
 DEFERRAL BUT AT RISK.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2014-08-07 Time 16:31 Sent To  
Notes
2014-08-07 16:32:31INCOMING SENT TO ZONING, ERIC TOOK PLANS TO 2ND FLOOR.
 JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-07 Cont ID  
Sent By hmoser Date 2014-08-07 Time 13:42 Rev Time 0.00
Received By hmoser Date 2014-07-24 Time 06:35 Sent To  
Notes
2014-07-25 09:20:13SENT TO C-26. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-21 Cont ID  
Sent By hmoser Date 2014-07-21 Time 13:21 Rev Time 0.00
Received By hmoser Date 2014-06-18 Time 19:15 Sent To  
Notes
2014-06-18 19:15:47INCOMING SENT TO C-32. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-07 Cont ID  
Sent By hmoser Date 2014-08-07 Time 13:42 Rev Time 0.00
Received By hmoser Date 2014-08-07 Time 10:22 Sent To  
Notes
2014-08-07 13:42:19PASS PROVISO
  
 1) SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR
 HOODS AND COOLERS
 2) PROVIDE ENGINEER DETAIL ON ROOF TOP FANS TIED TO
 CURB BY FINAL INSPECTION
 PER SECTION 301.12 WIND RESISTANCE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-21 Cont ID  
Sent By hmoser Date 2014-07-21 Time 13:20 Rev Time 0.00
Received By hmoser Date 2014-07-17 Time 15:09 Sent To  
Notes
2014-07-21 13:20:46PLAN DENIED
 1) SEPARATE PLANS, APPLICATION AND PERMIT REQUIRED FOR
 HOOD AND REFRIGATION. PER SECTION 107 FBC 2010
 2) PROVIDE ENGINEER DETAIL ON THE HOOD EXHAUST FAN AND
 SUPPLY FANS, CURB TIE DOWN TO THE ROOF AND FAN TIE DOWN
 TO CURB. PROVIDE SPACING ON THE ANCHOR PROVIDE TYPE
 AND SIZE OF ANCHOR USED. ON HOOD PLANS. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 3) PROVIDE AN ENGINEER DETAIL ON REFRIGATION CONDENSER
 STAND
 TIE DOWN TO ROOF AND CONDENSER TIE DOWN TO STAND. PER
 SECTION
 301.12 WIND RESISTANCE 2010 FBC (M).
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-06 Cont ID  
Sent By jwitmer Date 2014-08-06 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2014-07-25 Time 09:06 Sent To  
Notes
2014-08-06 12:05:24PLUMBING PLAN REVIEW
 PERMIT: 14060781
 ADD: 1845 PALM BEACH LAKES (WHOLE FOODS)
 CONT: TO BE DETERMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. AUG. 08/2014
 ACTION: PLUMBING PROVISO
  
 1) NOTE TO DATE NO PERMIT HAS BEEN BROUGHT IN FOR THE
 SIZING OF THE CONCRETE VAULT TYPE INTERCEPTOR FOR THIS
 TENANT SPACE, NOR REVIEWED FOR CODE COMPLIANCE BY THE
 BUILDING DEPARTMENT. THE GREASE INTERCEPTOR THAT WAS
 SET UNDER THE CIVIL PLANS OF THE PALM BEACH OUTLET MALL
 DID NOT HAVE SIZING INFORMATION FOR THE OUT PARCELS AND
 MAY OR MAY NOT BE SIZED ADEQUATELY TO MEET THE DEMANDS
 FOR THIS USAGE OF THIS TENANT. THIS GREASE INTERCEPTOR
 IS A CONCRETE VAULT TYPE INTERCEPTOR AND SHOULD BE
 SIZED USING THE 2010 FBC-P (TABLE 1003.5.1 THIS IS A
 FLORIDA SPECIFIC AMENDMENT TO THE ICC BASE CODE). MV+A
 IS USING THE SIZING METHOD OF "DFU" METHOD OF SIZING
 WHICH IS FOR HYDROMECHANICAL TYPE INTERCEPTORS.
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE
 REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE
 INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S
 MUNICIPAL CODE OF ORDINANCES.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-30 Cont ID  
Sent By jwitmer Date 2014-06-30 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2014-06-28 Time 10:42 Sent To  
Notes
2014-06-30 15:22:41PLUMBING PLAN REVIEW
 PERMIT: 14060781
 ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 30/ 2014
 ACTION: DENIED
  
 1) A SEPARATE PERMIT IS REQUIRED FOR GREASE
 INTERCEPTORS. SHEET P101 INDICATES THERE IS A EXISTING
 4 INCH EXISTING GREASY BUILDING DRAIN. NOTE TO DATE
 THERE HAS BEEN NO GREASE INTERCEPTOR APPLIED FOR OR
 REVIEWED BY THIS DEPARTMENT. THERE IS APPARENTLY GREASE
 INTERCEPTORS THAT WERE REVIEWED BY THE ENGINEERING
 DEPARTMENT BUT NOT BY THE BUILDING DEPARTMENT. ALL
 GREASE INTERCEPTORS ARE TO COMPLY WITH THE 2010
 FBC-PLUMBING , IF THIS IS A CONCRETE VAULT TYPE OF
 GREASE INTERCEPTORS THEY ARE TO BE DESIGNED TO FBC-
 PLUMBING TABLE 1003.5.1.
  
 2) A SEPARATE PERMIT WILL ALSO NEED TO BE OBTAINED FOR
 A FUEL GAS PERMIT. SHEET P301 SHOWS THE GAS ISOMETRIC.
 THESE ARE THE REQUIREMENTS TO OBTAIN A FUEL GAS PERMIT:
  
 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE, DIAMETER AND CORRESPONDING
 LENGTHS PER FBC-2010 FUEL GAS.
  
 2.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 2.3. TYPE OF GAS, (LP OR NATURAL).
  
 2.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 2.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 2.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 2.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 2.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 2.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 3) PLEASE PROVIDE ADDITIONAL INFORMATION 107.2.1.3.
 SHEET A101 IN (2) OF THE REFRIGARATED ROOMS THERE IS
 EQUIPMENT IDENTIFIED AS EQ. 801 GRINDER THIS EQUIPMENT
 DOES NOT SHOW UP ON P101 NOR P401, IS A DETAIL ON P402
 IF THIS IS PART OF THE PLUMBING SYSTEM, THAT SHOULD GO
 TO THE GREASY WASTE NOT LOCATED ON PLANS, THEY WILL
 NEED TO COMPLY WITH 2010 FBC-P 1003.3.2 PROVIDE THE
 MANUFACTURERS SPECIFICATIONS. .
  
 4) NEITHER P101 NOR P102 INDICATE THE AMOUNT OF
 DRAINAGE FIXTURE UNITS ON THE HORIZONTAL FIXTURE
 BRANCHES (TABLE 710.1(2) NOR THE BUILDING DRAIN FOR THE
 SANITARY OR GREASY WASTE TABLE 710.1(1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-07 Cont ID  
Sent By eschneid Date 2014-08-07 Time 16:57 Rev Time 0.50
Received By eschneid Date 2014-08-07 Time 16:57 Sent To B
Notes
2014-08-07 16:58:18ALL ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-07-29 Cont ID  
Sent By eschneid Date 2014-07-29 Time 09:34 Rev Time 0.50
Received By eschneid Date 2014-07-29 Time 09:34 Sent To  
Notes
2014-07-29 10:29:38FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE APPROVED SHELL PERMIT SHOWS A
 BUILDING SQUARE FOOTAGE OF 41,534 SQ. FT FOR THE GROUND
 FLOOR AND 1,198 SQ. FT. FOR THE MEZZANINE. THE INTERIOR
 BUILD OUT PERMIT LISTS A SQUARE FOOTAGE OF 40,636 SQ.
 FT. FOR THE GROUND FLOOR AND 925 SQ. FT. FOR THE
 MEZZANINE. PLEASE EXPLAIN AND CORRECT THE DISCREPANCY.
  
 2) REPEAT COMMENT: SHEET A408 (COFFEE BAR DETAILS) WAS
 NOT INCLUDED WITH THE PERMIT APPLICATION YET IS
 REFERENCED ON SHEET A204, A205.
  
 3) REPEAT COMMENT: NO INFORMATION IS INCLUDED FOR THE
 HEIGHT, FROM THE ROOF, OF THE NEW ROOFTOP EQUIPMENT (TO
 INCLUDE THE EXHAUST FANS AND MAKE UP FANS) INCLUDING
 THE CURBS THEY WILL BE MOUNTED ON. VERIFY THAT THE NEW
 EQUIPMENT IS SCREENED IN ACCORDANCE WITH THE PALM BEACH
 OUTLETS DESIGN GUIDELINES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By eschneid Date 2014-06-27 Time 11:15 Rev Time 2.00
Received By eschneid Date 2014-06-27 Time 11:15 Sent To  
Notes
2014-06-27 15:14:44FAILED
  
 1) THE APPROVED SHELL PERMIT SHOWS A BUILDING SQUARE
 FOOTAGE OF 41,534 SQ. FT FOR THE GROUND FLOOR AND 1,198
 SQ. FT. FOR THE MEZZANINE. THE INTERIOR BUILD OUT
 PERMIT LISTS A SQUARE FOOTAGE OF 40,636 SQ. FT. FOR THE
 GROUND FLOOR AND 925 SQ. FT. FOR THE MEZZANINE. PLEASE
 EXPLAIN AND CORRECT THE DISCREPANCY.
  
 2) SHEET A408 WAS NOT INCLUDED WITH THE PERMIT
 APPLICATION YET IS REFERENCED ON THE SHEETS THAT ARE
 INCLUDED.
  
 3) NO INFORMATION IS INCLUDED FOR THE HEIGHT, FROM THE
 ROOF, OF THE NEW ROOFTOP EQUIPMENT (TO INCLUDE THE
 EXHAUST FANS AND MAKE UP FANS) INCLUDING THE CURBS THEY
 WILL BE MOUNTED ON. VERIFY THAT THE NEW EQUIPMENT IS
 SCREENED IN ACCORDANCE WITH THE PALM BEACH OUTLETS
 DESIGN GUIDELINES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-06-25 11:34:426/25/14