| 2014-07-08 08:47:24 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. AS DISCUSSED, PLEASE PROVIDE AN ORIGINAL ELEVATION |
| | CERTIFICATE. THE SURVEYOR HAS AGREED TO PROVIDE THIS |
| | DIRECTLY TO ME. CITY OF WEST PALM BEACH MUNICIPAL CODE |
| | 94-546(B) |
| | |
| | 2. FBC 2010 ACCESSIBILITY 202.1, 224.2, 402, 806.2.2, |
| | PROVIDE INFORMATION REGARDING ACCESSIBLE ROOMS. IT IS |
| | NOT CLEAR WHETHER THESE ROOMS ARE AFFECTED BY THE |
| | PROPOSED RENOVATION. |
| | |
| | INDICATE WHICH OPTION ARE PROPOSED, INCLUDING SILL |
| | HEIGHT, SEE SHEETS 7-9. |
| | |
| | 3. THE PRODUCT APPROVALS WERE PRINTED IN "PORTRAIT" |
| | ORIENTATION. PLEASE REPRINT THE DRAWING SHEETS IN |
| | "LANDSCAPE" SO THEY PRINT FULL SIZE. THE SHEETS |
| | SUBMITTED ARE TOO SMALL TO READ, REVIEW, INSPECT FROM, |
| | AND SCAN, FBC 107. |
| | |
| | 4. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOOR |
| | INSTALLATION. APPLICATION DESCRIPTION STATES THAT YOU |
| | PROPOSE TO "REPLACE EXISTING CORRIDOR AND STAIRWAY |
| | WINDOWS WITH NEW IMPACT WINDOWS." CORRIDORS AS DEFINED |
| | IN FBC 1002 ARE RATED. SOME STAIRS ARE REQUIRED TO BE |
| | RATED. NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO |
| | DETERMINE CODE COMPLIANCE. |
| | |
| | 5. STOREFRONT DOOR PRODUCT APPROVALS SUBMITTED. PROVIDE |
| | A PLAN SHOWING PROPOSED LOCATION. INDICATE HARDWARE |
| | PROPOSED (PANIC/FIRE EXIT HARDWARE, SILL), FBC |
| | 1008.1.10, FBC 2010 ACCESSIBILITY 402. NOT ENOUGH |
| | INFORMATION PROVIDED TO DETERMINE CODE COMPLIANCE. |
| | |
| | SEE SHEET 3 OF STOREFRONT DOOR NOA. THERE ARE TWO |
| | OPTIONS FOR THRESHOLD COVER; THE ADA COVER IS LIKELY |
| | REQUIRED. |
| | |
| | IF FIRE EXIT HARDWARE AND ADA THRESHOLD SILL ARE |
| | PROPOSED, A LIFE SAFETY PLAN IS NOT REQUIRED. IF |
| | PROPOSED INSTALLATION DOES NOT INCLUDE FIRE EXIT |
| | HARDWARE AND/OR ADA THRESHOLD, A LIFE SAFETY PLAN WILL |
| | BE REQUIRED TO DEMONSTRATE THAT THEY ARE NOT REQUIRED. |
| | |
| | 6. THIS PROPERTY HAS SEVERAL EXPIRED PERMITS. PLEASE |
| | HAVE THE OWNER RESOLVE. |
| | |
| | THE OWNER CAN SEE THE EXPIRED PERMITS AT THE FOLLOWING |
| | WEBSITE: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER THE ADDRESS ONLY (600 NORTHPOINT). FOR PERMITS |
| | FOR WHICH THE WORK WAS NEVER STARTED, FAX A NOTARIZED |
| | LETTER STATING THIS TO 561-805-6676 (INCLUDE ADDRESS, |
| | PERMIT NUMBER, AND SCOPE OF PERMIT). |
| | |
| | FOR PERMITS WHICH WERE ISSUED, OBTAINED ALL REQUIRED |
| | INSPECTIONS EXCEPT FOR A FINAL INSPECTION, AN |
| | "INSPECTION ONLY" PERMIT CAN BE APPLIED FOR TO OBTAIN A |
| | PERMIT TO CLOSE THE EXPIRED PERMIT. |
| | |
| | FOR PERMITS WHICH WERE ISSUED AND NEED MORE INSPECTIONS |
| | THAN THE FINAL ONLY, A CONTRACTOR IS TO APPLY FOR A |
| | "REISSUE" PERMIT. |
| | |
| | FOR PERMITS WHICH WERE NEVER ISSUED BUT THE WORK WAS |
| | STARTED WITHOUT PERMIT, A CONTRACTOR IS TO APPLY FOR A |
| | NEW PERMIT. |
| | |
| | |
| | |
| | |