| 2014-07-02 16:39:44 | BUILDING PLAN REVIEW |
| | PERMIT: 14060741 |
| | ADD: 1253 OKEECHOBEE ROAD , SUITE # 100 |
| | CONT: FISHER |
| | TEL: (561)691-4716 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 02/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE CODE SUMMARY FOUND ON SHEET 1.1 INDICATES TENANT |
| | SPACE TO BE A BUSINESS OCCUPANCY. THE FLOOR PLAN FOUND |
| | ON SHEET 3.1 THE MAJORITY OF THE FLOOR AREA IS |
| | INDICATED TO BE A DISPLAY AREA. BY DEFINITION |
| | MERCANTILE: MERCANTILE GROUP M OCCUPANCY INCLUDES, |
| | AMONG OTHERS, THE USE OF A BUILDING OR STRUCTURE OR A |
| | PORTION THEREOF, FOR THE DISPLAY AND SALE OF |
| | MERCHANDISE AND INVOLVES STOCKS OF GOODS, WARES OR |
| | MERCHANDISE INCIDENTAL TO SUCH PURPOSES AND ACCESSIBLE |
| | TO THE PUBLIC. 2010 FBC-B 309.1 MERCANTILE GROUP M. |
| | |
| | 2) SHEET 3.1 NOTE INDICATES PAINT EXISTING ROLL UP |
| | DOOR. ALTERNATE REPLACE EXISTING DOOR WITH A INSULATED |
| | ROLL UP DOOR. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" |
| | OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 3) NOTE IF THIS DOES IN FACT IN UP BEING A MERCANTILE |
| | OCCUPANCY PLEASE REFIGURE THE OCCUPANT LOAD @ 30 SQ FT |
| | PER OCCUPANT AND THE OFFICE AREA @ 100 SQ FT / |
| | OCCUPANT. THIS MAY PUT THE OCCUPANT LOAD OVER 50 WHICH |
| | WOULD REQUIRE 2 EXITS. PLEASE SEE 2010 FBC-B SECTION |
| | 1015.2.1 AND THE 1/2 THE DIAGONAL DISTANCE APART FOR |
| | REQUIED EXITS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |