Plan Review Details - Permit 14060732
| Plan Review Stops For Permit 14060732 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-15 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-07-15 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-14 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-07-14 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2014-07-14 07:47:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 1008.1.10, PANIC/FIRE EXIT HARDWARE REQUIRED. | | | ALSO SEE FBC 1008.2 REGARDING GATES. THIS PROPOSED GATE | | | SERVES AN ASSEMBLY OCCUPANCY OVER 50. | | | | | | | | 2014-07-11 14:53:30 | CALLED RALPH 954 444 2271. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-07-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-07-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-07-03 |
Time |
14:21 |
Sent To |
B |
|
| Notes |
| 2014-07-03 14:27:52 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS SIDE. | | | | | | 2. PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING | | | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT | | | MORE THAN ONE RELEASING OPERATION. THE RELEASING | | | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING | | | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT | | | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO | | | OPERATE. | | | | | | 3. A FIRE INSPECTOR SHALL FIELD VERIFY CODE COMPLIANT | | | EXITING MECHANISM/ARRANGEMENT ON FINAL INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-14 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-06-27 |
Time |
13:24 |
Sent To |
Z |
|
| Notes |
| 2014-07-05 13:00:12 | MISC 2 | | | | | 2014-07-03 12:40:51 | TO FIRE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-15 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-06-17 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2014-06-17 10:51:42 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-14 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-07-01 |
Time |
16:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-06-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-06-19 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-06-19 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2014-06-19 08:57:43 | 6/19/14 ZONING FAILED | | | | | | 1. PROVIDE 2 COPIES OF AN UP TO DATE SITE PLAN, | | | HIGHLIGHTING THE LOCATION OF GATE AND FILLER FENCE |
|
|
|