| Plan Review Stops For Permit 14060652 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2014-07-18 08:47:05 | PASSED WITH EXCEPTION. DIFICIENCIES LISTED ON THE PLANS | | | ARE REQUIRED TO BE CORRECTED PRIOR TO INSPECTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-03 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
10:01 |
Sent To |
Z |
|
| Notes |
| 2014-07-03 14:51:39 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THERE IS ANOTHER PERMIT ( #14060659) THAT HAS BEEN | | | APPLIED FOR A TRASH ENCLOSURE AT THIS ADDRESS. IS THIS | | | THE SAME ONE THAT IS #3 ON THE LIST OF WORK THAT WAS | | | SUBMITTED? PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF PLANS AND STRUCTURAL DETAILS FOR | | | THE EXTERIOR ENCLOSED EGRESS STAIRS THAT ARE BEING | | | REPLACED. FBCR 311.7 | | | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE DRAWINGS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 4) SUBMIT TWO SETS OF FLOOR PLANS FOR THE FIRST AND | | | SECOND FLOORS WITH THE ROOM TYPES LABELED AND THE | | | WINDOW TYPES AND SIZES SPECIFIED ON THE PLANS. IF ANY | | | OF THE OPENINGS HAVE MULTIPLE WINDOW TYPES JOINED | | | TOGETHER WITH STRUCTURAL MULLIONS SPECIFY THE TYPE AND | | | SIZE OF EACH WINDOW AND THE MULL LENGTH AND ORIENTATION | | | ( PROVIDE AN ELEVATION OF THE WINDOWS IF NECESSARY FOR | | | CLARITY). CITY AMENDMENTS 107.2.1 & FBCR 301.2.1 | | | | | | 5) THE PRODUCT APPROVAL ( NOA NO. 11-1013.19) THAT WAS | | | SUBMITTED FOR THE LARGE MISSILE IMPACT RATED SINGLE | | | HUNG PGT WINDOWS IS EXPIRED. SUBMIT TWO COPIES OF | | | CURRENT PRODUCT APPROVALS FOR THE WINDOWS. DCA RULE | | | 9N-3 | | | | | | 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE | | | ALARMS. | | | | | | 7) IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-14 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2014-07-14 11:44:51 | TO R.M'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-07-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-08 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-06-16 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-07-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-03 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2014-07-03 14:40:14 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) A MECHANICAL PERMIT IS REQUIRED TO REPLACE AN | | | EXISTING A/C CONDENSER AND AIR HANDLER. IF THIS IS AN | | | EXACT CHANGE OUT, YOU WILL NEED TO SUBMIT TWO COPIES OF | | | AN A/C CHANGE OUT FORM AND TWO COPIES OF THE AHRI | | | CERTIFICATE FOR THE EQUIPMENT. IF DUCTWORK IS BEING | | | INSTALLED OR CHANGED, SUBMIT TWO COPIES OF A DUCT | | | LAYOUT PLAN. IF A HEATING AND COOLING SYSTEM IS BEING | | | INSTALLED WHERE THERE PREVIOUSLY WAS NONE, THEN | | | EQUIPMENT SIZING CALCULATIONS AND DUCT LAYOUT PLANS | | | WITH AN EQUIPMENT SCHEDULE IS REQUIRED. THE LOCATION OF | | | THE AIR HANDLER AND CONDENSING UNITS ARE REQUIRED ON | | | THE PLANS. CITY AMENDMENTS 105.1, 107.2.1 & 107.5.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-07-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-03 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-03 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2014-07-03 11:26:54 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) CLARIFY THE SCOPE OF PLUMBING WORK THAT WILL BE | | | DONE. CITY AMENDMENTS 107.2.1 & 107.3.5.3 | | | | | | 2) PROVIDE A FLOOR PLAN OF KITCHEN AND BATHROOM THAT | | | ARE BEING REMODELED. IF YOU WILL BE REPLACING THE | | | EXISTING FIXTURES IN THE SAME LOCATIONS, NOTE THAT ON | | | THE PLAN. IF YOU WILL BE CHANGING THE FIXTURE LOCATIONS | | | OR ADDING FIXTURES, SUBMIT TWO COPIES OF A PLUMBING | | | RISER DIAGRAM. CITY AMENDMENTS 107.2.1 & 107.3.5.3 | | | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 4) A PLUMBING PERMIT IS REQUIRED. CITY AMENDMENTS 105.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-07-07 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-07-07 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-07-07 |
Time |
13:00 |
Sent To |
B |
|
| Notes |
| 2014-07-07 13:02:49 | 7/7/14 NOTE: THERE SHOULD BE ONE APARTMENT IN THE | | | TWO-STORY BUILDING ON THE SECOND AND A GARAGE ON THE | | | FIRST FLOOR | | 2014-06-25 11:45:40 | 6/25/14 |
|
|