Plan Review Details - Permit 14060569
Plan Review Stops For Permit 14060569
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By jwitmer Date 2014-07-15 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 08:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-03 Cont ID  
Sent By jwitmer Date 2014-07-03 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 07:07 Sent To  
Notes
2014-07-03 07:42:35BUILDING PLAN REVIEW
 PERMIT:14060569
 ADD: 500 BELVEDERE DR SUITE # 640
 CONT: ALL PURPOSE CONSTRUCTION
 TEL: (561)718-7578
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 03/ 2014
 ACTION: DENIED
  
 1) THE HALL WAY BETWEEN THE COUNSELING OFFICE AND THE
 DOCTORS OFFICE THE PLANS INDICATE A HALL WAY WIDTH OF
 3'-8" WIDE. THERE IS A 6 INCH OFFSET IN THE CORRIDOR
 WALL INCREASING THE WIDTH TO 4'-2" WHERE TOLIET ROOMS
 ARE LOCATED. WHEN MEASURING THE ROOM WITH A SCALE THEY
 MEASURE 6'-6", PLEASE REVIEW SHEET A2 THIS DETAIL
 MEASURES A 7'-0" INTERIOR MEASUREMENT. DISCREPANCY IN
 PLANS.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) ALL THREE TOLIET ROOMS ARE INDICATED TO HAVE ALL NEW
 WALLS, PLEASE REVIEW THE 2010 FL ACCESIBILITY CODE IN
 REGUARDS TO
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 3) THE WIDTH OF THE CORRIDOR AND DOOR SWING IS ALSO A
 CONCERN, THE NEED TO COMPLY WITH FBC-B 008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
 THE MINIMUM CORRIDOR WIDTH FOR THIS OCCUPANT LOAD WOULD
 BE 36+18= 54 INCHES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By dhayes Date 2014-07-15 Time 09:07 Rev Time 0.00
Received By dhayes Date 2014-07-15 Time 09:07 Sent To FIRE
Notes
2014-07-15 09:47:46DATE: 7/14/2014
 PROJECT: BELLMART SHOPPES LEASE SPACE 640
 PERMIT#: 14060569
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH NEC
 517.13(A) AND (B).
  
 2) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52
  
 3) ALL EMERGENCY LIGHTING SHALL BE CONNECTED TO A
 LIGHTING CIRCUIT WITHIN THE AREA THEY OCCUPY. NEC
 700.12(F)
  
 4) UNLESS SPECIFICALLY PERMITTED IN FLEXIBLE CORDS
 SHALL NOT BE USED FOR THE FOLLOWING: WHERE CONCEALED BY
 WALLS, FLOORS, OR CEILINGS OR LOCATED ABOVE SUSPENDED
 OR DROPPED CEILINGS NEC 400.7,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 12:14 Rev Time 0.00
Received By dhayes Date 2014-07-14 Time 12:01 Sent To  
Notes
2014-07-14 12:13:59DATE: 7/14/2014
 PROJECT: BELLMART SHOPPES LEASE SPACE 640
 PERMIT#: 14060569
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH NEC
 517.13(A) AND (B).
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By pleduc Date 2014-07-15 Time   Rev Time 0.00
Received By pleduc Date 2014-07-15 Time 12:43 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-07-01 Cont ID  
Sent By pleduc Date 2014-07-01 Time   Rev Time 0.00
Received By pleduc Date 2014-07-01 Time 11:50 Sent To PC
Notes
2014-07-01 12:04:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENT:
  
 PLEASE ENSURE THAT EXIT LIGHTS ARE PROVIDED FOR WHERE
 HIGHLIGHTED ON THE PLAN IF NOT ALREADY EXISTING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-15 Cont ID  
Sent By pleduc Date 2014-07-15 Time 13:56 Rev Time 0.00
Received By pleduc Date 2014-07-14 Time 08:41 Sent To PC
Notes
2014-07-15 08:42:06ROUTED TO JW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-14 Cont ID  
Sent By jwitmer Date 2014-07-14 Time 08:41 Rev Time 0.00
Received By jwitmer Date 2014-06-13 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-07-15 Cont ID  
Sent By jwitmer Date 2014-07-15 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 08:39 Sent To  
Notes
2014-07-15 08:40:07NO MECHANICAL PLANS SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By jwitmer Date 2014-07-15 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 08:39 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-03 Cont ID  
Sent By jwitmer Date 2014-07-03 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 07:44 Sent To  
Notes
2014-07-03 07:45:11PLUMBING PLAN REVIEW
 PERMIT:14060569
 ADD: 500 BELVEDERE DR SUITE # 640
 CONT: ALL PURPOSE CONSTRUCTION
 TEL: (561)718-7578
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 03/ 2014
 ACTION: DENIED
  
 1) ALL THREE TOLIET ROOMS ARE INDICATED TO HAVE ALL NEW
 WALLS, PLEASE REVIEW THE 2010 FL ACCESIBILITY CODE IN
 REGUARDS TO
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  