Plan Review Details - Permit 14060545
Plan Review Stops For Permit 14060545
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-17 Cont ID  
Sent By skennedy Date 2014-06-17 Time 15:38 Rev Time 0.00
Received By skennedy Date 2014-06-17 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-16 Cont ID  
Sent By skennedy Date 2014-06-16 Time 07:44 Rev Time 0.00
Received By skennedy Date 2014-06-16 Time 07:41 Sent To FIRE
Notes
2014-06-16 07:52:281ST REVIEW:
  
 THE APPLICATION INCLUDES REPLACING FLOORING. PLEASE
 PROVIDE SPECIFICATIONS IN THE FORM OF SUBMITTAL
 DOCUMENTS ON FLOORING AND SOUND INSULATION TO
 DEMONSTRATE COMPLIANCE WITH THE THE FBC SECTIONS BELOW,
  
 1207.1 SCOPE.
 THIS SECTION SHALL APPLY TO COMMON INTERIOR WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES BETWEEN
 ADJACENT DWELLING UNITS OR BETWEEN DWELLING UNITS AND
 ADJACENT PUBLIC AREAS SUCH AS HALLS, CORRIDORS, STAIRS
 OR SERVICE AREAS.
  
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 EXCEPTION: IN BUILDINGS OF TYPE IA CONSTRUCTION
 EXCEEDING TWO STORIES ABOVE GRADE PLANE,
 FIRE-RETARDANT-TREATED WOOD IS NOT PERMITTED IN ROOF
 CONSTRUCTION WHEN THE VERTICAL DISTANCE FROM THE UPPER
 FLOOR TO THE ROOF IS LESS THAN 20 FEET (6096 MM).
  
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
  
 EXCEPTIONS:
  
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-13 Cont ID  
Sent By dhayes Date 2014-06-13 Time 14:57 Rev Time 0.00
Received By dhayes Date 2014-06-13 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-16 Cont ID  
Sent By pleduc Date 2014-06-16 Time   Rev Time 0.00
Received By pleduc Date 2014-06-16 Time 11:14 Sent To PC
Notes
2014-06-16 11:26:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 A FIRE SPRINKLER HEAD LOCATION REVIEW IS REQUIRED TO
 ENSURE AND MAAINTAIN COVERAGE IN THE REMODELED AREAS.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-16 Cont ID  
Sent By skennedy Date 2014-06-16 Time   Rev Time 0.00
Received By pleduc Date 2014-06-13 Time 14:25 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-16 Cont ID  
Sent By skennedy Date 2014-06-16 Time 07:40 Rev Time 0.00
Received By skennedy Date 2014-06-16 Time 07:40 Sent To  
Notes
***NONE***