Plan Review Details - Permit 14060543
Plan Review Stops For Permit 14060543
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By skennedy Date 2014-06-30 Time 07:49 Rev Time 0.00
Received By skennedy Date 2014-06-30 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-17 Cont ID  
Sent By skennedy Date 2014-06-17 Time 07:12 Rev Time 0.00
Received By skennedy Date 2014-06-17 Time 06:49 Sent To FIRE
Notes
2014-06-17 07:21:411ST REVIEW:
  
 THE DOOR/WINDOW REPLACEMENT ASPECT OF THIS PROJECT IS
 REQUIRED TO BE EVALUATED BY A DESIGN PROFESSIONAL.
 PLEASE PROVIDE AN ENGINEERED WIND DESIGN WHICH
 CONSIDERS BUILDING HEIGHT, WIND SPEED, WIND EXPOSURE,
 AND LOCATION OF THE OPENINGS. THE PROPOSED INSTALLATION
 MUST MEET THE RESULTING DESIGN PRESSURES.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-16 Cont ID  
Sent By dhayes Date 2014-06-13 Time 07:29 Rev Time 0.00
Received By dhayes Date 2014-06-13 Time 07:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-17 Cont ID  
Sent By pleduc Date 2014-06-17 Time   Rev Time 0.00
Received By pleduc Date 2014-06-17 Time 14:45 Sent To PC
Notes
2014-06-17 15:06:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-30 Cont ID  
Sent By skennedy Date 2014-06-30 Time 07:49 Rev Time 0.00
Received By skennedy Date 2014-06-24 Time 17:12 Sent To  
Notes
2014-06-24 17:12:50SENT TO S KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-17 Cont ID  
Sent By pleduc Date 2014-06-17 Time 15:06 Rev Time 0.00
Received By pleduc Date 2014-06-13 Time 07:28 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-17 Cont ID  
Sent By skennedy Date 2014-06-17 Time 06:48 Rev Time 0.00
Received By skennedy Date 2014-06-17 Time 06:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-17 Cont ID  
Sent By skennedy Date 2014-06-17 Time 06:48 Rev Time 0.00
Received By skennedy Date 2014-06-17 Time 06:48 Sent To  
Notes
***NONE***